SiBE37-701
Outline of Control (Indoor Unit)
Function
139
6. Outline of Control (Indoor Unit)
6.1
Operation Flow Chart
Start
Heating Operation
Fan Operation
Cooling Operation
Turn ON
power supply
Cooling Operation
LED in remote
controller turns ON
Drain
pump kit
Aux. electric
heater
Detect louver lock
( )
Run or Stop?
RUN indicating lamp: OFF
RUN indicating lamp: Blink
Malfunction code: Displayed
RUN indicating lamp: OFF
Malfunction mode display: Reset
Is
Restart prevention
operation in progress?
(5 min.)
Is
freeze prevention
operation in progress?
Is
test run
in progress?
Thermostat status
Fan or Temp.
control?
Cooling or
Heating?
Swing flap
Dew
prevention condition?
Swing flap
Set wind direction
Dew prevention position
Cassette type: P1
Ceiling suspended type: P0
Microcomputer dry
ON/OFF
Microcomputer dry display:
Reset
Microcomputer dry operation
Fan:
Operating with set air flow rate
A
A
A
Stop
Run
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
ON
OFF
No
No
No
Cyclic operation with
RUN/STOP pushbutton
*1
Fan
Temp. control
Heating
Cooling
*2 Fan : Stop
Louver : Stop
*3
*6
*5
*4
(Option)
(Option)
(Option)
(Option)
(Option)
(Option)
OFF
ON
MF
MF
: OFF
MP
Drain pump kit
: OFF after 5-min.
residual operation
MP
Drain pump kit
: OFF after 5-min.
residual operation
MP
Drain pump kit
:ON
MP
Drain pump kit
: ON
MP
: Closed
20E
Electronic expansion valve
: Capacity control
20E
Electronic expansion valve
: Closed
20E
MA
: OFF
52H
Aux. electric
heater
: OFF
52H
Humidifier : OFF
Mu
Humidifier : OFF
Mu
OFF
ON
a
b
Set temperature
Suction air temperature
a=b=1
(a=b=0.5 is only available for the FXCQ, FXFQ, FXHQ, and FXKQ series.)
20E
Initialize electronic
expansion valve
The previous settings of air
flow rate, wind direction, and
temperature are displayed.
Is the
safety device
activated?
Is the RUN
indicating lamp
blinking?
Press the RESET
RUN/STOP
pushbutton.
Electronic
expansion valve
Thermostat-ON-
operation signal to
outdoor unit: Output
Thermostat-ON-
operation signal to
outdoor unit: Output
*1. If any malfunction occurs, the relevant malfunction code will be displayed according to the malfunction
code display of the remote controller.
*2. When the aux. electric heater turns ON, the fan will stop after it conducts residual operation for 1 min.
*3. When the drain pump kit turns ON, the drain pump kit will stop after it conducts residual operation for a
period of 5 min.
*4. If the evaporator inlet temperature is kept at not more than -5
°
C for a period of cumulative 10 min. or
not more than -1
°
C for a cumulative period of 40 min., frost prevention operation will be conducted. If
the evaporator inlet temperature is kept at not less than 7
°
C for a consecutive period of 10 min., the
frost prevention operation will be reset.
*5. Thermostat status
*6. The FXCQ, FXFQ, FXKQ, and FXSQ series have the drain pump as standard equipment.
RUN indicating lamp: ON
Air flow rate display: Displayed
Wind direction display: Displayed
Temp. setting display: Displayed
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...