background image

4

English

2. SPECIFICATIONS

[Single unit (Heat Pump series)]

[Single unit (Heat Recovery series)]

*1: Initial refrigerant charge

[Combination unit (Heat Pump series)]

[Combination unit (Heat Recovery series)]

Model

RQYQ140PY1 RQYQ180PY1

Power supply

Phase

-

3N

~

3N

~

Frequency

(Hz)

50

50

Voltage

(V)

380-415

380-415

Nominal cooling capacity

(kW)

14.0

18.0

Nominal heating capacity

(kW)

16.0

20.0

Dimensions H×W×D

(mm) 1680×635×765 1680×635×765

Mass

(kg)

175

175

Refrigerant type

-

R410A

R410A

Refrigerant charge 

(*1)

(kg)

11.1

11.1

Design pressure

High pressure side

(bar)

40

40

(MPa)

4.0

4.0

Low pressure side

(bar)

33

33

(MPa)

3.3

3.3

Model

RQEQ140PY13 RQEQ180PY13 RQEQ212PY13

Power supply

Phase

-

3N

~

3N

~

3N

~

Frequency

(Hz)

50

50

50

Voltage

(V)

380-415

380-415

380-415

Nominal cooling capacity

(kW)

14.0

18.0

21.2

Nominal heating capacity

(kW)

16.0

20.0

22.4

Dimensions H×W×D

(mm)

1680×635×765

1680×635×765

1680×635×765

Mass

(kg)

175

175

179

Refrigerant type

-

R410A

R410A

R410A

Refrigerant charge

 (*1)

(kg)

10.3

10.6

11.2

Design pressure

High pressure side

(bar)

40

40

40

(MPa)

4.0

4.0

4.0

Low pressure side

(bar)

33

33

33

(MPa)

3.3

3.3

3.3

Model

RQCYQ280PY1 RQCYQ360PY1 RQCYQ460PY1

Power supply

Phase

-

3N

~

3N

~

3N

~

Frequency

(Hz)

50

50

50

Voltage

(V)

380-415

380-415

380-415

Nominal cooling capacity

(kW)

28.0

36.0

46.0

Nominal heating capacity

(kW)

32.0

40.0

52.0

Dimensions H×W×D

(mm)

(1680x635x765)

+

(1680x635x765)

(1680x635x765)

+

(1680x635x765)

(1680x635x765)

+

(1680x635x765)

+

(1680x635x765)

Mass

(kg)

175+175

175+175

175+175+175

Refrigerant type

-

R410A

R410A

R410A

Refrigerant charge

(kg)

11.1+11.1

11.1+11.1

11.1+11.1+11.1

Design pressure

High pressure side

(bar)

40

40

40

(MPa)

4.0

4.0

4.0

Low pressure side

(bar)

33

33

33

(MPa)

3.3

3.3

3.3

Model

RQCYQ500PY1 RQCYQ540PY1

Power supply

Phase

-

3N

~

3N

~

Frequency

(Hz)

50

50

Voltage

(V)

380-415

380-415

Nominal cooling capacity

(kW)

50.0

54.0

Nominal heating capacity

(kW)

56.0

60.0

Dimensions H×W×D

(mm)

(1680x635x765)

+

(1680x635x765)

+

(1680x635x765)

(1680x635x765)

+

(1680x635x765)

+

(1680x635x765)

Mass

(kg)

175+175+175

175+175+175

Refrigerant type

-

R410A

R410A

Refrigerant charge

(kg)

11.1+11.1+11.1 11.1+11.1+11.1

Design pressure

High pressure side

(bar)

40

40

(MPa)

4.0

4.0

Low pressure side

(bar)

33

33

(MPa)

3.3

3.3

Model

RQCEQ280PY13 RQCEQ360PY13 RQCEQ460PY13

Power supply

Phase

-

3N

~

3N

~

3N

~

Frequency

(Hz)

50

50

50

Voltage

(V)

380-415

380-415

380-415

Nominal cooling capacity

(kW)

28.0

36.0

46.0

Nominal heating capacity

(kW)

32.0

40.0

52.0

Dimensions H×W×D

(mm)

(1680x635x765)

+

(1680x635x765)

(1680x635x765)

+

(1680x635x765)

(1680x635x765)

+

(1680x635x765)

+

(1680x635x765)

Mass

(kg)

175+175

175+175

175+175+175

Refrigerant type

-

R410A

R410A

R410A

Refrigerant charge

(kg)

10.3+10.3

10.6+10.6

10.6+10.3+10.3

Design pressure

High pressure side

(bar)

40

40

40

(MPa)

4.0

4.0

4.0

Low pressure side

(bar)

33

33

33

(MPa)

3.3

3.3

3.3

Model

RQCEQ500PY13 RQCEQ540PY13 RQCEQ636PY13

Power supply

Phase

-

3N

~

3N

~

3N

~

Frequency

(Hz)

50

50

50

Voltage

(V)

380-415

380-415

380-415

Nominal cooling capacity

(kW)

50.0

54.0

63.6

Nominal heating capacity

(kW)

56.0

60.0

67.2

Dimensions H×W×D

(mm)

(1680x635x765)

+

(1680x635x765)

+

(1680x635x765)

(1680x635x765)

+

(1680x635x765)

+

(1680x635x765)

(1680x635x765)

+

(1680x635x765)

+

(1680x635x765)

Mass

(kg)

175+175+175

175+175+175

179+179+179

Refrigerant type

-

R410A

R410A

R410A

Refrigerant charge

(kg)

10.6+10.6+10.3 10.6+10.6+10.6 11.2+11.2+11.2

Design pressure

High pressure side

(bar)

40

40

40

(MPa)

4.0

4.0

4.0

Low pressure side

(bar)

33

33

33

(MPa)

3.3

3.3

3.3

Model

RQCEQ712PY13 RQCEQ744PY13 RQCEQ816PY13

Power supply

Phase

-

3N

~

3N

~

3N

~

Frequency

(Hz)

50

50

50

Voltage

(V)

380-415

380-415

380-415

Nominal cooling capacity

(kW)

71.2

74.4

81.6

Nominal heating capacity

(kW)

78.4

80.8

87.2

Dimensions H×W×D

(mm)

(1680x635x765)

+

(1680x635x765)

+

(1680x635x765)

+

(1680x635x765)

(1680x635x765)

+

(1680x635x765)

+

(1680x635x765)

+

(1680x635x765)

(1680x635x765)

+

(1680x635x765)

+

(1680x635x765)

+

(1680x635x765)

Mass

(kg)

179+175+175+175 179+179+175+175 179+179+179+175

Refrigerant type

-

R410A

R410A

R410A

Refrigerant charge

(kg)

11.2+10.6+10.6+10.3 11.2+11.2+10.6+10.3 11.2+11.2+11.2+10.6

Design pressure

High pressure side

(bar)

40

40

40

(MPa)

4.0

4.0

4.0

Low pressure side

(bar)

33

33

33

(MPa)

3.3

3.3

3.3

Model

RQCEQ848PY13

Power supply

Phase

-

3N

~

Frequency

(Hz)

50

Voltage

(V)

380-415

Nominal cooling capacity

(kW)

84.8

Nominal heating capacity

(kW)

89.6

Dimensions H×W×D

(mm)

(1680x635x765)

+

(1680x635x765)

+

(1680x635x765)

+

(1680x635x765)

Mass

(kg)

179+179+179+179

Refrigerant type

-

R410A

Refrigerant charge

(kg)

11.2+11.2+11.2+11.2

Design pressure

High pressure side

(bar)

40

(MPa)

4.0

Low pressure side

(bar)

33

(MPa)

3.3

01_EN_3P226891-15V.fm  Page 4  Friday, September 19, 2014  9:26 AM

Summary of Contents for vrv III -Q Series

Page 1: ...PY13 OPERATION MANUAL System air conditioner Operation manual VRVIII System air conditioner Betriebsanweisung VRVIII System Klimaanlage Manuel d utilisation Conditionneur d air VRVIII System Manual de...

Page 2: ...alatarjetadegarant adelconcesionario gu rdelaen unlugarseguro Grazie per avere acquistato questo condizionatore d aria Daikin Prima di utilizzare quest ultimo leggere attentam ente il presente manuale...

Page 3: ...2 1 1 4 3 5 6 7 1 7 3 7 2 1 2 00_CV_3P226891 15V fm Page 3 Tuesday September 16 2014 6 53 PM...

Page 4: ...8 9 10 11 12 13 14 1 14 2 15 00_CV_3P226891 15V fm Page 4 Tuesday September 16 2014 6 53 PM...

Page 5: ...ly may result in property damage or personal injury which may be serious depending on the circum stances After reading keep this manual in a conve nient place so that you can refer to it whenever nece...

Page 6: ...y smoke such as cooking rooms or in places with flammable gas corrosive gas or metal dust Using the product in such places may cause fire or product failures Do not use flammable materials e g hairspr...

Page 7: ...ealth Do not let children play on or around the out door unit If they touch the unit carelessly injury may be caused Do not place water containers flower vases etc on the unit as this may result in el...

Page 8: ...3 3 3 Model RQCEQ280PY13 RQCEQ360PY13 RQCEQ460PY13 Power supply Phase 3N 3N 3N Frequency Hz 50 50 50 Voltage V 380 415 380 415 380 415 Nominal cooling capacity kW 28 0 36 0 46 0 Nominal heating capaci...

Page 9: ...y ventilation air cleaning This display shows that the ventilation unit are in operation these are optional accessories 6 Display set temperature This display shows the temperature you have set 7 Disp...

Page 10: ...s 80 or over the interiors of the indoor units may cause icing and water leakage may result Heating operation The air conditioner may stop operating for the pro tection of the machine if the outdoor t...

Page 11: ...ration it may take longer to reach the set temperature than in cooling operation We recommend starting the operation which was used before using timer operation The following operation is performed in...

Page 12: ...on off button The operation lamp lights up and the system starts operation Press the air flow direction adjust button only for FXC FXF FXH FXK FXA Refer to the chapter Adjusting the air flow directio...

Page 13: ...the sys tem after 3 hours and start the system after 4 hours the system will stop after 3 hours and start 1 hour later 6 5 SETTING THE MASTER REMOTE CON TROLLER Refer to figure 10 When one outdoor uni...

Page 14: ...TIMUM OPERATION Observe the following precautions to ensure the system operates properly Adjust the air outlet properly and avoid direct air flow to room inhabitants Adjust the room temperature proper...

Page 15: ...ng the air filter be sure to put it back in the same position See the operation manual included with the indoor unit for details on how to clean it 9 FOLLOWING SYMPTOMS ARE NOT AIR CONDITIONER TROU BL...

Page 16: ...d by defrost becomes steam and is exhausted 9 8 NOISE OF AIR CONDITIONERS Indoor unit A zeen sound is heard immediately after the power supply is turned on The electronic expansion valve inside an ind...

Page 17: ...a fuse a breaker or an earth leakage breaker frequently actuates Measure Do not turn on the main power switch If the ON OFF switch does not properly work Measure Turn off the main power switch If wat...

Page 18: ...been corrected surely before restarting operation Do not remove or reinstall the unit by yourself Incorrect installation may cause electrical shock or fire Contact your dealer When asking your dealer...

Page 19: ...ong as possible Use for appropriate maintenance design budgeting maintenance and inspection fees etc Contact your dealer for details Note Breakage due to taking apart or cleaning inside by anyone othe...

Page 20: ...3P226891 15V EM14A015 1410 HT 00_CV_3P226891 15V fm Page 5 Tuesday September 16 2014 6 53 PM...

Reviews: