![Daikin VRV II Series Technical Data Manual Download Page 9](http://html2.mh-extra.com/html/daikin/vrv-ii-series/vrv-ii-series_technical-data-manual_4705057009.webp)
• VRVII & VRV-WII features
2
•
Systems • VRVII & VRV-WII features
8
2
Energy efficient solution
2-6
Operation range of outdoor temperature - VRVII
Standard operation down to -20
°
C outdoor ambient temperature
Advanced PI control of the outdoor unit enables VRVII heat recovery and Inverter cooling only/heat pump series to operate at outdoor ambients down
to -5
°
C in cooling mode and down to -20
°
C in heating mode.
VRV-WII
Wide operating range of the water-cooled units between 10 C & 45 C, both in cooling and heating.
VRV II heat pump
-20 CWB
-5 CDB
Heating
15.5 CWB
Cooling
43 CDB
50
40
30
20
10
-5
-10
-15
-20
VRVII heat recovery
-20 CWB
-5 CDB
Heating
15.5 CWB
-5 CWB
Heating
15.5 CWB
Cooling
43 CDB
50
40
30
20
10
-5
-10
-15
-20
50
40
30
20
10
0
10°C
10°C
Heating
45°C
Cooling
45°C