Daikin VRV HXY48TAVJU Installation And Operation Manual Download Page 19

Installation and operation manual

18

HXY48TAVJU

VRV System indoor unit

3P616151-1A – 2021.12

Once all checks are fulfilled, the unit must be closed, only then can
the unit be powered on. When the power supply to the indoor unit is
turned  on,  "

88

"  is  displayed  on  the  user  interface  during  its

initialization, which might take up to 30 seconds. During this process
the user interface can not be operated.

8.2.

Final air purging

To get rid of all the air in the system, the pump should be operated.

Therefore, change the field setting [E-04] as explained in the chapter
"8.3. Field  settings"  on  page 18.  More  details  about  setting  "[E-04]
Pump only operation (air purge function)" can be found on page 21.

8.3.

Field settings

The  hydro  unit  should  be  configured  by  the  installer  to  match  the
installation environment (outdoor climate, installed options, etc.) and
user  demand.  Therefore,  a  number  of  so  called  field  settings  are
available.  These  field  settings  are  accessible  and  programmable
through the user interface on the indoor unit.

Each field setting is assigned a 3-digit number or code, for example
[5-03], which is indicated on the user interface display. The first digit
[5]  indicates  the  'first  code'  or  field  setting  group.  The  second  and
third digit [03] together indicate the 'second code'.

A list of all field settings and default values is given in the "8.4. Field
setting list for Installation Manual" on page 22. In this list we provided
2 columns to  register  the date and value of  altered  field  settings  at
variance with the default value.

8.3.1.

Procedure

To change one or more field settings, proceed as follows.

1

Press the 

z

 button for a minimum of 5 seconds to enter FIELD

SET MODE.
The 

$

  icon  (3)  will  be  displayed.  The  current  selected

field  setting  code  is  indicated 

;

  (2),  with  the  set  value

displayed to the right 

-

 (1).

2

Press the 

ébi

 button to select the appropriate field setting

first code.

3

Press the 

ébj

 button to select the appropriate field setting

second code.

4

Press  the 

pfi

  button  and 

pfj

  button  to  change

the set value of the select field setting.

5

Save the new value by pressing the 

pr

 button.

6

Repeat  step  2  through  4  to  change  other  field  settings  as
required.

7

When finished, press the 

z

 button to exit FIELD SET MODE.

8.3.2.

Detailed description

For a summary of all field settings refer to "8.4. Field setting list for
Installation Manual" on page 22.

[0] Remote control setup

[0-00]

 User permission level

The user interface can be programmed to make certain buttons
and functions unavailable for  the user. There  are 2 permission
levels defined. Both levels (level 2 and level 3) are basically the
same, the only difference is that for level 3 no water temperature
settings are possible (see table below).

NOTE

Operating the system with closed valves will damage the
pump!

INFORMATION

Changes  made  to  a  specific  field  setting  are  only
stored when the 

pr

 button is pressed. Navigating to

a new field setting code or pressing the 

z

 button will

discard the change made.

The field settings are grouped by their field setting first
code.

For example, field settings [0-00]; [0-01]; [0-02]; [0-03]
are defined as "Group 0".

When  different  values  are  changed  within  the  same
group, pressing the 

pr

 button will save all the values

changed within this group.

Be  aware  of  this  when  changing  field  settings  within
the same group and pressing on the 

pr

 button.

INFORMATION

Before  shipping,  the  set  values  have  been  set  as
shown  under  "8.4. Field  setting  list  for  Installation
Manual" on page 22.

When  exiting  FIELD  SET  MODE,  "

88

"  may  be

displayed  on  the  user  interface  LCD  while  the  unit
initializes itself.

NOTE

When  running  through  the  field  settings  you  may  notice
that  there  are  some  more  field  settings  as  there  are
mentioned  in  the  "8.4. Field  setting  list  for  Installation
Manual" on page 22. 

These field settings are not appli-

cable and may not be changed!

Permission

level 2

level 3

Operation ON/OFF

Operable

Operable

Setting the leaving water temperature

Operable

Setting the room temperature

Operable

Operable

Weather dependent set point operation 

ON/OFF

Operable

Setting the clock

Programming the schedule timer

Schedule timer operation ON/OFF

Operable

Operable

Field settings

malfunction code display

Operable

Operable

Test operation

01_EN_3P616151-1A.fm  18 ページ  2021年12月14日 火曜日 午後1時29分

Summary of Contents for VRV HXY48TAVJU

Page 1: ...English Fran ais Espa ol INSTALLATION AND OPERATION MANUAL HXY48TAVJU System indoor unit 00_CV_3P616151 1A fm 1...

Page 2: ...rk 14 7 3 2 System overview of field wiring 15 7 3 3 Requirements 15 7 3 4 To open the switch box cover 15 7 3 5 To connect the electrical wiring on the indoor unit 15 7 3 6 To connect the user interf...

Page 3: ...fied personnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation may result in water leakage electric shock or fire When...

Page 4: ...additional refrigerant must be charged in its liquid state If the refrigerant is charged in a state of gas its composition can change and the system will not work properly The indoor unit is for R410...

Page 5: ...mage must be reported immediately to the carrier s claims agent Bring the packed unit as close as possible to its final installation position to prevent damage during transport 3 1 Indoor unit 3 1 1 T...

Page 6: ...ntification 4 2 1 Identification label Indoor unit Location Model identification Modelname HXY48TAVJU 4 3 Possible combinations of unit and options 4 3 1 List of options for indoor unit User interface...

Page 7: ...eaving water temperature zone B One single room C One single room a Outdoor VRV b VRV Direct Expansion DX Indoor unit cassette c HXY48 d Optional EKRUAHTB user interface main e Refrigerant piping f Wa...

Page 8: ...kage When installing the unit in a small room take measures in order to keep the refrigerant concentration from exceeding allowable safety limits in the event of a refrigerant leak Do not climb sit or...

Page 9: ...e is 50 F 10 C cooling The maximum water pressure is 44 psi 3 bar Provide adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded All installed piping and piping a...

Page 10: ...r volume Check that the total water volume in the installation is minimum 5 3 gallon 20 liter the internal water volume of the indoor unit NOT included a Outdoor unit VRV b Indoor unit HXY48 c Heat ex...

Page 11: ...35 H 10 4 35 0 10 4 35 psi 0 3 bar The corresponding maximum water volume at 4 35 psi 0 3 bar is 108 3 gal 410 l See the graph in the chapter above Because 92 gal 350 l is lower than 108 3 gal 410 l...

Page 12: ...1 Indoor unit power supply 2 GND a a Refer to name plate on the indoor unit 2 Malfunction output 2 0 3 A b b Minimum cable section 0 75 mm AWG18 3 Operation ON OFF output 2 0 3 A b 4 Cooling heating...

Page 13: ...he water outlet Mind their position Orientation of the integrated drain valves is important for servicing 1 Install the shut off valves on the water pipes a Water inlet b Water outlet c Adaptors 2 Scr...

Page 14: ...w switch During filling it may not be possible to remove all the air from the circuit Remaining air will be removed through the automatic air purge valves during the initial operating hours of the sys...

Page 15: ...50 50 Total hardness mg CaCO3 l 200 70 70 Calcium hardness mg CaCO3 l 150 50 Ionic state silica mg SiO2 l 50 30 30 Reference items Iron mg Fe l 1 0 0 3 1 0 0 3 Copper mg Cu l 0 3 0 1 1 0 0 1 Sulfate i...

Page 16: ...nd sharp edges 7 3 6 To connect the user interface The unit is equipped with a user interface offering a user friendly way to set up use and maintain the unit Before operating the user interface follo...

Page 17: ...ape of the backside of the user interface by overtightening the mounting screws a b P1 P2 a Rear part of the user interface b Front part of the user interface 1 2 1 NOTE Be careful NOT to distort the...

Page 18: ...is properly installed to avoid abnormal noises and vibrations when starting up the unit 6 Damaged equipment Check the inside of the unit on damaged components or squeezed pipes 7 Refrigerant leak Chec...

Page 19: ...he select field setting 5 Save the new value by pressing the pr button 6 Repeat step 2 through 4 to change other field settings as required 7 When finished press the z button to exit FIELD SET MODE 8...

Page 20: ...room temperature During operation During schedule timer operation the operation LED is lit continuously When pushing the y button The schedule timer for space heating will stop and will not start agai...

Page 21: ...roller and the real set point E g a positive shift value means that the real temperature set point will be higher than the calculated set point It is advised to use the weather dependent set point bec...

Page 22: ...l be used for the logic Eg when the ambient temperature is high during cooling mode the logic will correct the measured value of the leaving water thermistor to a lower value to take into account infl...

Page 23: ...01 High ambient temperature Hi_A 59 15 50 68 10 20 1 8 1 F C 02 Set point at low ambient temperature Lo_Ti 104 40 77 176 25 80 1 8 1 F C 03 Set point at high ambient temperature Hi_Ti 77 25 77 176 25...

Page 24: ...03 Set point cooling leaving water minimum temperature 50 10 41 64 5 18 1 8 1 F C 04 Not applicable Do not change the default value 0 d Settings are not applicable E Service mode 00 Not applicable Do...

Page 25: ...ave this mode If no button is pressed the user interface leaves the display mode after 10 seconds Procedure for space heating cooling 1 Check the leaving water and entering water temperature through t...

Page 26: ...onent box are hot Make sure you do not touch a conductive section Do not rinse the unit This may cause electric shocks or fire Play it safe Touch a metal part by hand such as piping sheet metal in ord...

Page 27: ...ace cooling heating operation Tick when checked Q Explain to the user what sytem is installed on site Complete the fill in below for each unit The information may be useful for the user in future serv...

Page 28: ...PECTION REQUIRED k and l These icons indicate that inspection is required on the installation Consult your dealer 11 TEMPERATURE DISPLAY 9 The display shows the current temperature of the installation...

Page 29: ...ERATURE ADJUST BUTTONS bi and bj These buttons are used to adjust the leaving water temperature set point in normal operation mode or in schedule timer programming mode If the controller is set to per...

Page 30: ...int The operation LED 0 lights up 2 Use the bi and bj buttons to set the desired room temperature Temperature range for heating 61 90 F 16 32 C room temperature In order to avoid overheating space hea...

Page 31: ...is enabled 3 Press the ba button to deactivate weather dependent set point operation The bi and bj buttons are used to set the leaving water temperature Field settings define the parameters for the we...

Page 32: ...g schedule timer can be programmed in 2 different ways Based on the temperature set point leaving water temperature and room temperature Based on the ON OFF instruction The desired method is set throu...

Page 33: ...ation LED will stop working However the schedule timer icon will stay displayed When pushing the pr button The schedule timer for space heating will be stopped and will not start again The schedule ti...

Page 34: ...This form can help you define the required actions for each day Take your time to enter all data accurately Try to program the actions in a chronological way start with action 1 for the first action...

Page 35: ...g water temperature 9 Use the bi and bj buttons to set the room temperature 10 Use the ba button to select x to switch cooling and the user interface off 11 Repeat steps 6 to 10 to program the other a...

Page 36: ...out as follows 1 Press the button to enter the programming consulting mode 2 Select the operation mode you would like to consult by means of the pi and pj buttons The actual mode is blinking 3 Press t...

Page 37: ...e unit There are 2 inputs that allow Remote thermo on off Remote unit on off For more details about this option kit refer to the wiring diagram of the unit 10 3 12 Operating the optional user interfac...

Page 38: ...field settings as required 7 When finished press the z button to exit FIELD SET MODE NOTE Changes made to a specific field setting are only stored when the pr button is pressed Navigating to a new fi...

Page 39: ...e this procedure for resetting the safety is not successful contact your local dealer For other malfunction codes which may be displayed during the system test run or operation see the installation ma...

Page 40: ...0A 2 1 8 F1U SS1 4 2 X12A 1 4 1 1 F1U 6 1 2 NORM EMG R1T BRN 1 208 230V 60Hz 2 2 X1M 2 X27A 2 2 YLW 3 K6R WHT 2 X5A 2 1 C3 X15A K1R C2 S1L HAP 2 X1M X1A 5 X15A 1 1 X14A BLU BLU 2 2 X20A X18A MS A1P L2...

Page 41: ...refrigerant of oil and of other parts must be done in accordance with the applicable legislation Do not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant...

Page 42: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 3P616151 1A EM21A030 2021 12 00_CV_3P616151 1A fm 2...

Reviews: