Installation and operation manual

7

FXMQ50-125P7VEB9

VRV System air conditioners

3P468515-4 – 12.2016

Specifications for field supplied fuses and wire

Allowable length of transmission wiring between indoor and outdoor
units, and between the indoor unit and the remote controller is as
follows:

1.

Outdoor unit - indoor unit: max. 1000 m (total wiring length:
2000 m)

2.

Indoor unit - remote controller: max 500 m

W

IRING

 

EXAMPLE

 

AND

 

HOW

 

TO

 

SET

 

THE

 

REMOTE

 

CONTROLLER

How to connect wiring

Remove the switch box cover as shown in 

figure 12

, and make the

connections.

PRECAUTIONS

1

Observe the notes mentioned below when wiring to the power
supply terminal board.

-

Use a round crimp-style terminal for insulation sleeve for 
connection to the terminal block for wiring the units. When 
none are available, follow the instructions below.

-

Do not connect wires of different gauge to the same power 
supply terminal. (Looseness in the connection may cause 
overheating.)

-

When connecting wires of the same gauge, connect them 
according to the figure.

Use the specified electric wire. Connect the wire securely to
the terminal. Lock the wire down without applying excessive
force to the terminal. Use torques according to the table
below.

-

When attaching the control box lid, make sure not to pinch 
any wires.

-

After all wiring connections are done, fill in any gaps in the 
casing wiring holes with putty or insulation material (field 
supply) thus to prevent small animals or dirt from entering the 
unit from outside and causing short circuits in the control box.

2

Keep total current of crossover wiring between indoor units less
than 12 A. Branch the line outside the terminal board of the unit
in accordance with electrical equipment standards, when using

two power wiring of a gauge greater than 2 mm

2

 (Ø1.6).

The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.

3

Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.

4

Remote controller cords and wires connecting the units should
be located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to electrical
noise.

5

For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.

6

Never connect the power supply wiring to the terminal board for
transmission wiring. This mistake could damage the entire
system.

7

Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the switch box
cover. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worse case, electric shock
or fire.

Power supply wiring

Model

Field fuses

Wire

Size

20~125

16 A

H05VV-U3G

Local codes

Model

Wire

Size

20~125

Sheathed wire (2)

0.75-1.25 mm

2

NOTE

For details, refer to 

"Wiring example" on page 8

.

1

Switch box cover

2

Transmission wiring port

3

Power supply wiring port

4

Wiring diagram

5

Switch box

1

2

3

1

Round crimp-style terminal

2

Attach insulation sleeve

3

Wiring

Tightening torque (N•m)

Terminal block for unit transmission and 
remote controller

0.9

Terminal block for power supply

1.2

Summary of Contents for VRV FXMQ50P7VEB9

Page 1: ...INSTALLATION AND OPERATION MANUAL FXMQ50P7VEB9 FXMQ63P7VEB9 FXMQ80P7VEB9 FXMQ100P7VEB9 FXMQ125P7VEB9 System air conditioners...

Page 2: ...680 1 5 3 4 2 7 180 460 160 160 300 425 1 3 2 180 460 350 1 2 2 3 5 0 75 625 A 300 mm 1 1 5 m 2 3 1 4 100 mm 1 0 625 mm 1 1 2 4 5 3 6a 7a 7b 7c 6b 6c 8 9 10 11 2 1 3 5 4 700 630 A B 4 3 2 1 1 1 2 4 5...

Page 3: ...B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certi cado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certi kat C 11 Information e...

Page 4: ...re machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage uctuates a lot e g in factorie...

Page 5: ...ical appliances Noise may be generated depending on the conditions under which the electric wave is generated even if 1 meter is kept When installing the wireless remote controller kit the distance be...

Page 6: ...ing surface 2 Ceiling opening 3 Service access panel optional accessory 4 Air lter 5 Air inlet duct 6 Duct service opening 7 Interchangeable plate NOTE Before installation of the unit in case of insta...

Page 7: ...han the speci ed refrigerant such as air etc inside the refrigerant circuit Use annealed material only for are connections Refer to Table 1 for the dimensions of are nut spaces and the appropriate tig...

Page 8: ...he drain raising pipes and insulate them 2 Connect the drain hose to the drain outlet on the indoor unit and tighten it with the clamp Precautions Install the drain raising pipes at a height of less t...

Page 9: ...slation Note that the operation will restart automatically if the main power supply is turned off and then turned back on again This system consists of multiple indoor units Mark each indoor unit as u...

Page 10: ...units less than 12 A Branch the line outside the terminal board of the unit in accordance with electrical equipment standards when using two power wiring of a gauge greater than 2 mm2 1 6 The branch...

Page 11: ...ndications Ultra long life lter Light 10 000 hrs Heavy 5 000 hrs Long life lter 2 500 hrs 1 250 hrs Standard lter 200 hrs 100 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensor...

Page 12: ...the outdoor unit If any other error display occurs on the display of the remote controller refer to Test operation on page 10 and the operation manual of the outdoor unit Check the defective point Us...

Page 13: ...is extremely contaminated If the dirt becomes impossible to clean change the air lter Air lter for exchange is optional 1 Open the suction grille Only for bottom suction Slide both knobs simultaneousl...

Page 14: ...he air inlet and outlet are not blocked Remove any obstacle Check if the earth is connected Clean the air lter and outside panels After cleaning the air lter make sure to attach it Turn on the main po...

Page 15: ...1M TERMINAL STRIP POWER SUPPLY X2M TERMINAL STRIP CONTROL Y1E ELECTRONIC EXPANSION VALVE Z1C Z2C NOISE FILTER FERRITE CORE Z1F NOISE FILTER CONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR...

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ...N IN D OUT D F1 F2 F1 F2 Control box P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 5 3 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control b...

Page 20: ...3P468515 4 12 2016 Copyright 2016 Daikin...

Reviews: