WARNING
▪
Take precautions to avoid excessive vibration or pulsation to refrigeration piping.
▪
Protect the protection devices, piping and fittings as much as possible against
adverse environmental effects.
▪
Provide space for expansion and contraction of long runs of piping.
▪
Design and install piping in refrigerating systems such as to minimise the
likelihood of hydraulic shock damaging the system.
▪
Mount the indoor equipment and pipes securely and protect them to avoid
accidental rupture of equipment or pipes in case of events such as moving
furniture or reconstruction activities.
CAUTION
▪
Incomplete flaring may cause refrigerant gas leakage.
▪
Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.
▪
Use flare nuts that are included with the unit. Using different flare nuts may
cause refrigerant gas leakage.
CAUTION
Do NOT use potential sources of ignition in searching for or detection of refrigerant
leaks.
NOTICE
▪
Do NOT re-use joints and copper gaskets which have been used already.
▪
Joints made in installation between parts of refrigerant system shall be accessible
for maintenance purposes.
3.1.1 Installation space requirements
CAUTION
The total refrigerant charge in the system cannot exceed the requirements for
minimum floor area of the smallest room that is served. For minimum floor area
requirements for indoor units, see the installation and operation manual of the
outdoor unit.
WARNING
This appliance contains R32 refrigerant. For the minimum floor area of the room in
which the appliance is stored refer to installation and operation manual of the
outdoor unit.
NOTICE
▪
Protect pipework from physical damage.
▪
Keep the pipework installation to a minimum.