17
|
Unit installation
Installer and user reference guide
72
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
17 Unit installation
WARNING
The installation MUST comply with the requirements that apply to this R32
equipment. For more information, see
"16 Special requirements for R32 units"
60].
In this chapter
17.1 Preparing the installation site
Choose an installation location with sufficient space to transport the unit in and
out of the site.
Do NOT install the unit in places often used as work place. In case of construction
works (e.g. grinding works) where a lot of dust is created, the unit MUST be
covered.
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
17.1.1 Installation site requirements of the outdoor unit
INFORMATION
Also read the following requirements:
▪
General installation site requirements. See the "General safety precautions"
chapter.
▪
Service space requirements. See the "Technical data" chapter.
▪
Refrigerant piping requirements (length, height difference). See further in this
"Preparation" chapter.
INFORMATION
Equipment meets the requirement for commercial and light-industrial location when
professionally installed and maintained.
CAUTION
Appliance NOT accessible to the general public. Install it in a secured area, protected
from easy access.
This unit is suitable for installation in a commercial and light industrial environment.