• Table 1 “Inspection Cycle” and “Maintenance Cycle” Lists

*1:

• When the fan motor fails, the remote controller does not dis-

play any error code.
Usage under that status will lead to insufficient ventilation.
The air supply and exhaust fans should be checked once 
every one or two months.

• You can make a simple check such as below way.

To check the wind flow, hold a bar of which the end has a 
string or other similar lightweight item over the supply grille 
and exhaust grille.

*2:

• When the solenoid valve fails, the remote controller does not 

display any error code.
Usage under that status will lead to insufficient humidification 
and increased tap water consumption.
The solenoid valve should be checked at the biginning of the 
heating season.

Note 1

This table indicates main parts.
See the maintenance and inspection contract for details.

Note 2

This maintenance cycle indicates recommended lengths of 
time until the need arises for maintenance work, in order to 
ensure the product is operational as long as possible.
Use for appropriate maintenance design (budgeting mainte-
nance and inspection fees, etc.).
Depending on the content of the maintenance and inspection 
contract, the inspection and maintenance cycles may in reality 
be shorter than those listed here.

Shortening of “maintenance cycle” and “replacement 
cycle” needs to be considered in the following cases.

• When used in hot, humid locations or locations where tem-

perature and humidity fluctuate greatly.

• When used in locations where power fluctuation (voltage, fre-

quency, wave distortion, etc.) is high.
(Cannot be used if it is outside the allowable range.)

• When installed and used in locations where bumps and 

vibrations are frequent.

• When used in bad locations where dust, salt, harmful gas or 

oil mist such as sulfurous acid and hydrogen sulfide may be 
present in the air.

• When used in locations where the machine is started and 

stopped frequently or operation time is long. (Example: 
24 hour air-conditioning)

• When the supply water is hard water the humidifier’s life 

become shorter.

„

Recommended replacement cycle of wear-out parts

[The cycle is not the same as the warranty period.]

• Table 2 “Replacement Cycle” Lists

Note 1

This table indicates main parts.
See the maintenance and inspection contract for details.

Note 2

This maintenance cycle indicates recommended lengths of 
time until the need arises for maintenance work, in order to 
ensure the product is operational as long as possible.
Use for appropriate maintenance design (budgeting mainte-
nance and inspection fees, etc.).

Note 3

Life of humidifying element is about 3 years (4,000 hours), 
under the supply water conditions of hardness: 150mg/l.
(Life of humidifying element is about 1 year (1,500 hours), 
under the supply water conditions of hardness: 400mg/l.)
Annual operating hours: 10 hours/day × 26 days/ 
month × 5 month = 1,300 hours.

Contact your dealer for details.
Note: Breakage due to taking apart or cleaning inside by any-
one other than our authorized dealers may not be included in 
the warranty.

„

Moving and discarding the unit

• Contact your dealer for removing and reinstalling the total 

enthalpy heat exchanger when moving house since they 
require technical expertise.

• This unit contains chlorofluorocarbon in the refrigent. 

When discarding, removing linstalling and maintaining the 
unit, collect the refrigent in accordance with the local law for 
the global environmental destruction prevention.
In detail contact your dealer.

„

Where to call

For after-sales service, etc., consult with your dealer.

„

Warranty period:

Warranty period:

Within one year after
installation.

• If it is necessary to repair the air conditioner within the war-

ranty period, contact your dealer.

Name of Main Part

Inspection 
Cycle

Maintenance Cycle 
[replacements and/
or repairs]

Electric motor (fan, 
damper, etc.)

1~2 months 
recom-
mended *1

20,000 hours

PC boards

1 year

25,000 hours

Heat exchanger 
element

10 years

Heat exchanger

5 years

Sensor (thermistor)

5 years

Remote controller and 
switches

25,000 hours

Drain pan

8 years

Expansion valve

1 year *2

20,000 hours

Electromagnetic valve

1 year

20,000 hours

Name of Main Part

Inspection 
Cycle

Replacement Cycle

Air filter

1 year

3 years

High efficiency filter 
(Optional accessory)

1 year

Heat exchanger ele-
ment

2 years

10 years

Humidifier element

1 year

3 years (Note 3)

01_EN_3P130767-3G.fm  Page 15  Monday, March 5, 2007  10:05 AM

Summary of Contents for VKM50GAMV1

Page 1: ...ON MANUAL Total Heat Exchanger HRV Heat Reclaim Ventilation with DX Coil MODELS Ceiling mounted duct type With DX coil Humidifier VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 With DX coil VKM50GAV1 VKM80GAV1 VKM...

Page 2: ...se en combinaci n con un sistema de climatizaci n interior VRVII de tipo M RXYQ REYQ RXQ Tambi n es posible utilizar esta unidad a modo de sistema independiente Esta unidad no puede controlar la tempe...

Page 3: ...cover 6 Electric parts box 8 Heat exchanger elements 12 Gas pipe 13 Liquid pipe 16 Strainer included VKM GAMV1 series only VKM GAMV1 series only 14 Drain outlet 15 Humidifier Natural evaporating type...

Page 4: ...ent system HRV With DX Coil Remote controller for indoor unit Outdoor unit Remote controller for VRV BRC1A62 3 2 Remote controller for VRV BRC1A62 4 1 5 3 Remote controller for VKM BRC1D527 EU only 4...

Page 5: ...BRC1D527 EU only 1 2 3 6 1 Heat exchanger element 2 2 Handle 3 Rail 9 1 Air filter 8 2 8 1 3 10 11 12 1 3 2 Remote controller for VRV BRC1A62 7 6 7 UNIT No GROUP Remote controller for VKM BRC1D527 EU...

Page 6: ...t including air filters etc Be sure to stop the unit and turn off the power when cleaning or inspecting it As the fan is rotating at high speed it will cause injury Never inspect or service the unit b...

Page 7: ...When the HRV unit is to be installed in a small room it is necessary to take proper measures so that the amount of any leaked refrigerant does not exceed the limiting concen tration even when it leaks...

Page 8: ...itioner CHECK LIST CORRESPONDING TO OPERATING NOISE Is the unit installed at the following locations a Location strong enough to support the weight of the unit and which will not amplify noise or vibr...

Page 9: ...ton for programming start and or stop time 18 Temperature setting button Use this button for setting the desired temperature of air conditioner combined with this unit This button can t use for this u...

Page 10: ...ing the unit as an independent system Ask your dealer what kind of system your system is set up for before operation For the operation of the remote controller for indoor unit and centralized controll...

Page 11: ...exchange mode VRV Fan mode HRV Heat exchange mode VRV Stopping HRV Heat exchange mode When air conditioner and HRV unit are not connected via duct Operation mode VRV Cooling mode HRV Heat exchange mo...

Page 12: ...set for systems operating in cooling and heating at the same time is displayed on all remote controllers when using the VRV system cooling only type but only and can be set Select the operating mode o...

Page 13: ...driv ing factory setting The purpose of this is to maintain the amount of ventilation and humidifying The change of the layout in the room should be examined when the cold draft from air supplying op...

Page 14: ...SET THE TIMER WITH THE REMOTE CONTROLLER BRC1A62 Refer to figure 7 The timer is operated in the following two ways Programming the stop time The system stops operating after the set time has elapsed...

Page 15: ...red you must confirm the programmed actions Make sure the last schedule timer action you want to keep is selected schedule timer actions with a higher number will be deleted Now you must choose betwee...

Page 16: ...ESSARY Increase the frequency of cleaning if the unit is installed in a room where the air is etermely contaminated If the dirt becomes impossible to clean change the air filter Air filter for exchang...

Page 17: ...ller does not display any error code Usage under that status will lead to insufficient humidification and increased tap water consumption The solenoid valve should be checked at the beginning of the h...

Page 18: ...he power on The remote control buttons do not work well Measure Turn off the main power switch If the display INSPECTION UNIT No and the OPERATION lamp flash and the MALFUNCTION CODE appears Measure N...

Page 19: ...oard and other electric parts h Is the float switch broken Replace the float switch i Is the water supply pressure sufficient Re set it so that there is sufficient pressure j Is there foreign matter i...

Page 20: ...wear out parts The cycle is not the same as the warranty period Table 2 Replacement Cycle Lists Note 1 This table indicates main parts See the maintenance and inspection contract for details Note 2 Th...