Daikin VKM50GAMV1 Operation Manual Download Page 18

13

English

<Symptom>

The fans rotates after 1 minutes when pressing on on/off but-
ton.

<Cause>

This indicates that the operation is in preparation.
Wait for about 1 minute.

• Operation stops sometimes.

<Symptom>

“U5” is displayed on the remote controller and the operation 
stops but then restarts after a few minutes.

<Cause>

This indicates that the remote controller is intercepting noise 
from electrical appliances other than the HRV unit, and this 
prevents communication between the units, causing them to 
stop.
Operation automatically restarts when the noise goes away.

• “88” is displayed on the remote controller.

<Symptom>

It displays immediately after the power is turned on, and dis-
appears after several seconds.

<Cause>

This indicates that the unit is checking whether or not the 
remote controller is normal.
It is only displayed temporarily.

5.2 IF ONE OF THE FOLLOWING MALFUNCTIONS 

OCCURS, TAKE THE MEASURES SHOWN 
BELOW AND CONTACT YOUR DAIKIN DEALER

The system must be repaired by a qualified service person.
DO NOT CHECK AND REPAIR OPENING INSIDE THE UNIT 
BY YOURSELF.

WARNING

When the HRV is in abnormal conditions (smell of some-
thing burning, etc), cut off the power, and contact your 
dealer.

Continued operation under such circumstances may result in a 
failure, electric shock, and fire.

The unit does not operate at all.

a. Check if there is a power failure.

Measure:

After power has been restored, start operation 
again.

b. Check if the fuse has blown.

Measure:

Turn the power off.

c. Check if breaker has worked.

Measure:

Turn the power on with the 
breaker switch in the off 
position.
Do not turn the power on 
with the breaker switch in 
the trip position.
(Contact your dealer.)

If a safety device such as a fuse, a breaker, or an earth 
leakage breaker frequency actuates, or ON/OFF switch 
does not properly work.
Measure:

 Do not turn the power on.

The remote control buttons do not work well.
Measure:

 Turn off the main power switch.

• If the display “

” (INSPECTION), “UNIT No.” and the 

OPERATION lamp flash and the “MALFUNCTION 
CODE” appears.

Measure: 

Notify and inform the model name and what the 

malfunction code indicates to your Daikin dealer.

There are other malfunctions.
Measure:

 Stop the unit.

List of malfunction codes of Remote controller of the HRV-sys-
tem

Switch

ON

OFF

Trip position

Breaker

Opera-

tion 

lamp

Inspec

tion

indica-

tor

Unit 

No.

Mal-

func-

tion 

code

Description

On

Off

Blink-

ing

64

Indoor air thermistor mal-
function

On

Off

Blink-

ing

65

Outdoor air thermistor mal-
function

On

Off

Blink-

ing

6A

Dumper-related malfunction

Blink-

ing

Blink-

ing

Blink-

ing

6A

Dumper-related malfunction 
+ thermistor malfunction

Blink-

ing

Blink-

ing

Blink-

ing

A1

Printed circuit board  fault

On

Off

Blink-

ing

A1

Printed circuit board  fault

Blink-

ing

Blink-

ing

Blink-

ing

A9

Electric expansion valve 
drive error

Blink-

ing

Blink-

ing

Blink-

ing

C4

Liquid piping thermistor error 
(faulty connection, discon-
nection short circuit, fault)

Blink-

ing

Blink-

ing

Blink-

ing

C5

Gas piping thermistor error 
(faulty connection, cut wire, 
short circuit, fault)

Blink-

ing

Blink-

ing

Blink-

ing

C9

Intake air into coil thermistor error 
(faulty connection, disconnection, 
short circuit, fault)

Blink-

ing

Blink-

ing

Blink-

ing

U3

Test run not performed

Blink-

ing

Blink-

ing

Blink-

ing

U5

Transmission error between 
the unit and remote controller

Off

Blink-

ing

Off

U5

Setting error of remote con-
troller

Off

Blink-

ing

Off

U8

Transmission error between 
main remote controller and 
sub remote controller

Off

Blink-

ing

Blink-

ing

UA

Incorrect combination with 
indoor unit and remote controller.

On

Blink-

ing

On

UC

Central control address over 
lapping

Blink-

ing

Blink-

ing

Blink-

ing

UE

Transmission error between 
the unit and centralized con-
troller

INSPECTION
display

MALFUNCTION CODE

INDOOR UNIT No. in which
a malfunction occurs

OPERATION lamp

01_EN_3P130767-3G.fm  Page 13  Monday, March 5, 2007  10:05 AM

Summary of Contents for VKM50GAMV1

Page 1: ...ON MANUAL Total Heat Exchanger HRV Heat Reclaim Ventilation with DX Coil MODELS Ceiling mounted duct type With DX coil Humidifier VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 With DX coil VKM50GAV1 VKM80GAV1 VKM...

Page 2: ...se en combinaci n con un sistema de climatizaci n interior VRVII de tipo M RXYQ REYQ RXQ Tambi n es posible utilizar esta unidad a modo de sistema independiente Esta unidad no puede controlar la tempe...

Page 3: ...cover 6 Electric parts box 8 Heat exchanger elements 12 Gas pipe 13 Liquid pipe 16 Strainer included VKM GAMV1 series only VKM GAMV1 series only 14 Drain outlet 15 Humidifier Natural evaporating type...

Page 4: ...ent system HRV With DX Coil Remote controller for indoor unit Outdoor unit Remote controller for VRV BRC1A62 3 2 Remote controller for VRV BRC1A62 4 1 5 3 Remote controller for VKM BRC1D527 EU only 4...

Page 5: ...BRC1D527 EU only 1 2 3 6 1 Heat exchanger element 2 2 Handle 3 Rail 9 1 Air filter 8 2 8 1 3 10 11 12 1 3 2 Remote controller for VRV BRC1A62 7 6 7 UNIT No GROUP Remote controller for VKM BRC1D527 EU...

Page 6: ...t including air filters etc Be sure to stop the unit and turn off the power when cleaning or inspecting it As the fan is rotating at high speed it will cause injury Never inspect or service the unit b...

Page 7: ...When the HRV unit is to be installed in a small room it is necessary to take proper measures so that the amount of any leaked refrigerant does not exceed the limiting concen tration even when it leaks...

Page 8: ...itioner CHECK LIST CORRESPONDING TO OPERATING NOISE Is the unit installed at the following locations a Location strong enough to support the weight of the unit and which will not amplify noise or vibr...

Page 9: ...ton for programming start and or stop time 18 Temperature setting button Use this button for setting the desired temperature of air conditioner combined with this unit This button can t use for this u...

Page 10: ...ing the unit as an independent system Ask your dealer what kind of system your system is set up for before operation For the operation of the remote controller for indoor unit and centralized controll...

Page 11: ...exchange mode VRV Fan mode HRV Heat exchange mode VRV Stopping HRV Heat exchange mode When air conditioner and HRV unit are not connected via duct Operation mode VRV Cooling mode HRV Heat exchange mo...

Page 12: ...set for systems operating in cooling and heating at the same time is displayed on all remote controllers when using the VRV system cooling only type but only and can be set Select the operating mode o...

Page 13: ...driv ing factory setting The purpose of this is to maintain the amount of ventilation and humidifying The change of the layout in the room should be examined when the cold draft from air supplying op...

Page 14: ...SET THE TIMER WITH THE REMOTE CONTROLLER BRC1A62 Refer to figure 7 The timer is operated in the following two ways Programming the stop time The system stops operating after the set time has elapsed...

Page 15: ...red you must confirm the programmed actions Make sure the last schedule timer action you want to keep is selected schedule timer actions with a higher number will be deleted Now you must choose betwee...

Page 16: ...ESSARY Increase the frequency of cleaning if the unit is installed in a room where the air is etermely contaminated If the dirt becomes impossible to clean change the air filter Air filter for exchang...

Page 17: ...ller does not display any error code Usage under that status will lead to insufficient humidification and increased tap water consumption The solenoid valve should be checked at the beginning of the h...

Page 18: ...he power on The remote control buttons do not work well Measure Turn off the main power switch If the display INSPECTION UNIT No and the OPERATION lamp flash and the MALFUNCTION CODE appears Measure N...

Page 19: ...oard and other electric parts h Is the float switch broken Replace the float switch i Is the water supply pressure sufficient Re set it so that there is sufficient pressure j Is there foreign matter i...

Page 20: ...wear out parts The cycle is not the same as the warranty period Table 2 Replacement Cycle Lists Note 1 This table indicates main parts See the maintenance and inspection contract for details Note 2 Th...

Page 21: ...3P130767 3G EM05A069A 0704 HT 00_CV_3P130767 3G_01 fm Page 2 Wednesday March 7 2007 3 18 PM...

Reviews: