VAM350~200 EKVDX32~100A2VEB
VRV system air conditioner
ESIE22-07 – 2022.02
VAM field settings (user interface: indoor unit 1)
Mode
SW
SW description
SW position
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
17(27)
4
Initial fan speed
(a)
High
Ultra-high
—
—
—
—
—
—
—
—
—
—
—
—
—
5
(b)
Yes/No setting for duct connection with VRV system
Without duct
With duct
Without duct
With duct
Without duct
With
duct
—
—
—
Setting for cold areas when heater thermostat is
OFF)
(c)
—
—
Stop/Stop
Low/Low
Stop/stop
Low/Low
—
—
—
—
—
—
—
—
—
Fan operation when defrost/oil return/hot start
(c)
—
—
Stop/Stop
Stop/Stop
Stop/Stop
Stop/Stop
Stop/—
Stop/Stop
Stop/—
—
—
—
—
—
—
6
Nighttime free cooling (fan settings)
(d)
High
Ultra-high
—
—
—
—
—
—
—
—
—
—
—
—
—
18(28)
0
External signal
(e)
JC/J2
Last command
Priority on external
input
Priority on operation
Disable nighttime free
cooling / Perform
forced stop
—
24 hours
ventilation ON/OFF
Disable JC/J2
—
—
—
—
—
—
—
—
1
Direct power ON
(f)
OFF
ON
—
—
—
—
—
—
—
—
—
—
—
—
—
2
Auto restart
(f)
OFF
ON
—
—
—
—
—
—
—
—
—
—
—
—
—
8
External input terminal function selection
(g)
(JC/J1)
Fresh-up
Error output
Error output and
stop operation
Forced off
Fan forced off
Air-flow up
—
—
—
—
—
—
—
—
—
10
EKVDX connected?
(h)
No
Yes
—
—
—
—
—
—
—
—
—
—
—
—
—
13
Cooling set point (with EKVDX)
13°C
15°C
16°C
17°C
18°C
19°C
20°C
21°C
22°C
23°C
24°C
25°C
26°C
28°C
30°C
14
Heating set point (with EKVDX)
24°C
26°C
27°C
28°C
29°C
30°C
31°C
32°C
33°C
35°C
37°C
39°C
41°C
43°C
45°C
19(29)
15
R32 safety system
(i)
OFF
ON
—
—
—
—
—
—
—
—
—
—
—
—
—
(a
)
When connected to an EKVDX, set to 2 or 4.
(b
)
When connected to an EKVDX, 17(27)-5 can be set to 1, 3, 4, 7 or 8.
(c
)
(Supply air/Exhaust air), e.g. Low/Low means: Supply air low/Exhaust air low.
(d
)
In case VAM and EKVDX are combined and the R32 safety system of the VAM is active, the nighttime free cooling is disabled.
(e
)
When connected to an EKVDX, JC/J2 cannot be used. Set to 18(28)-0-7. Instead, use T1 T2 of the EKVDX. See the EKVDX Installation and operation manual.
(f
)
When connected to an EKVDX, do not change the default settings.
(g
)
When connected to an EKVDX, JC/J1 cannot be used. Instead, use T1 T2 of the EKVDX. See the EKVDX Installation and operation manual.
(h
)
When connected to an EKVDX, set to 18(28)-10-2.
(i
)
When connected to an EKVDX, setting 2 (safety ON) is required in case R32 refrigerant is used. Setting 1 (safety OFF) is required in case R410A refrigerant is used.