Control Functions
SiE00-01
22
Control Functions
1. Control Functions
1.1
List of Control Functions
Note:
Note 1
Requires optional humidifier and optional printed circuit board (KRP50-2 : Wiring adapter for remote
contact).
Classification
Function name
Outline of function
1. Basic functions
(functions related to
basic performance)
1.1 Ventilation
operation control
function
Controls supply air fan motor, exhaust air fan motor and damper
motor.
1.2 Abnormality
control function
Detects abnormalities in thermistor, damper motor and data
transmission to prevent errors.
2. Additional functions 2.1 Ventilation mode
changeover function
Operates equipment in selected ventilation mode (total heat
exchange, normal, automatic).
2.2 Automatic
ventilation operation
function
Selects the most suitable ventilation mode by controlling
damper motor according to temperature controller mode,
temperature setting and thermistor data.
2.3 Ventilation
capacity changeover
function
Operates equipment at set airflow rate.
2.4 Humidifier
operation control
function
Controls humidifier output based on temperature controller
judgment. Note 1
2.5 Pre-cool/pre-heat
function
Prevents equipment operation for a preset time (set time) after
air conditioner is turned on.
2.6 Freshup function
Sets motor tap so that supply air fan airflow rate is larger than
exhaust air fan airflow rate.
2.7 Filter sign function Stores cumulative operation hour data and turns on air filter
cleaning indicator.
3. System control
functions
3.1 Remote controller
function
Operates equipment according to instructions from remote
controller.
3.2 Group function
Operates two or more units based on instructions from single
remote controller.
3.3 Air conditioner link
function
Follows air conditioner ON/OFF instructions.
3.4 Power ON
operation function
Operates equipment when power is turned on.
3.5 External link
operation function
Turns equipment on and off according to external link terminal
signal (no-voltage contact a).
3.6 Centralized
control function
Allows remote control operation by centralized control
equipment.
3.7 Timer function
Turns equipment on and off at set time.
4. Other support
functions
4.1 Troubleshooting
function
Displays error codes to indicate locations of error.
4.2 Field setting
function
Allows initial setting from LCD remote controller.
Summary of Contents for VAM 150FJVE
Page 5: ...SiE00 01 iv Table of Contents ...
Page 7: ...Introduction SiE00 01 vi 1 1 1 Cautions in Operation and Maintenance ...
Page 8: ...SiE00 01 Introduction vii ...
Page 13: ...General Constructions SiE00 01 4 General Constructions ...
Page 23: ...Operation SiE00 01 14 Operation ...
Page 29: ...Maintenance SiE00 01 20 Maintenance ...
Page 41: ...Circuit Operations SiE00 01 32 Circuit Operations ...
Page 73: ...Supplementary Explanation SiE00 01 64 Supplementary Explanation ...
Page 74: ...SiE00 01 Appendix 65 Part 9 Appendix 1 Appendix 66 1 1 Wiring Diagram 66 ...
Page 76: ...SiE00 01 Appendix Appendix 67 VAM1500FJVE VAM2000FJVE ...
Page 77: ...Appendix SiE00 01 68 Appendix ...
Page 81: ...SiE00 01 iv Index ...