Original instructions
Installation manual
10
We reserve the right to make changes without any prior notice.
UATYQ*Y1
Packaged Rooftop
4P522681-1A
Example n. 2
The unit has to operate from Monday to Friday, from 07:30 to 19:30, with summer setpoint 24.0°C and winter setpoint
20.5°C; moreover, unit fans must be switched OFF from 19:30 to 07:30 and the unit has to be completely switched
OFF on Saturday and Sunday.
Masks K2 to K7 have to be set as follows:
In case the “Unit OFF by time slot” function is enabled in mask K2, the external set in mask K4 can be
whatever value, because it is not considered by the unit thermoregulation due to the fact that unit is
switched OFF.
2.6 Stop washing function (forced freecooling at unit start-up)
Unit with freecooling dampers and washing function enabled.
Main mask press "Enter" to stop washing function.
Summary of Contents for UATYQ25ABAY1
Page 2: ......
Page 22: ......
Page 23: ......
Page 24: ...Copyright 2019 Daikin 4P522681 1A 2019 01 CM_DKN_0001_Rooftop_EN_10 01 2019_rev01...