12
Model
Capacitor (
μ
F)
Rated Voltage
Wire size
UATQ60C
10
440V AC
AWG14~16
UATQ90C
20
UATQ120C
10
UATQ150C
20
UATQ180C
20
UATQ210C
25
UATQ240C
30
UATQ300C
30
The units can be used for power factor correction by additional capacitor bank (for QCC - Abu Dhabi certification scheme only.)
* All calculations based on ISO standard with condition 29ºC DB / 19ºC WB indoor, 46ºC DB outdoor.
* All the additional capacitor has to be field supplied based on the suggested capacitor size in table to achieve >0.9F
* All calculations subjected to change by manufacturer without prior notice.
(b) Follow the wire connection diagram as below during field installed.
UATQ60/90
UATQ120/150/180
UATQ210/240/300
(5) Optional configuration:
(a) Power factor correction
1-IM-5RTC-0315(6)-DAIKIN-EN.indd12 12
1-IM-5RTC-0315(6)-DAIKIN-EN.indd12 12
7/10/20 10:35:15 AM
7/10/20 10:35:15 AM