11
Sound Data
Sound Data
Sound Pressure Level
Model
1/1 Octave Sound Pressure (dB, ref 20μPa)
Overall
(dBA)
Noise
Criteria
125Hz 250Hz 500Hz 1kHz
2kHz
4kHz
8kHz
UATN60C
64
64
58
56
50
47
35
61
57
UATN90C
69
63
56
58
51
50
43
62
58
UATN120C
70
67
62
60
54
53
50
65
60
UATN150C
75
66
61
64
55
52
50
67
65
UATN180C
78
69
63
63
58
57
52
68
69
UATN210C
73
68
65
65
60
56
52
69
64
UATN240C
72
69
67
66
60
58
53
70
65
UATN300C
70
68
68
66
66
63
57
72
67
Measuring Location
Microphone position:
(1) Measurement at open field.
(2) For all microphone position, the distance will be from the unit center in 1m horizontal follow by 1m
vertical.
Standard: JIS B 8616-1999