System Performance

Model Name

Indoor

FTQ18PBVJU FTQ24PBVJU FTQ30PBVJU FTQ36PBVJU FTQ42PBVJU 

Outdoor

RZQ18PVJU9 RZQ24PVJU9 RZQ30PVJU9 RZQ36PVJU9 RZQ42PVJU9 

Cooling Capacity (Rated)

Btu/h

18,000

24,000

30,000

36,000

40,000

Cooling Capacity (Min - Max)

Btu/h

9,000 – 18,000  9,000 – 24,000  12,000 – 30,000 12,000 – 36,000 12,000 – 42,000 

Heating Capacity (Rated) 

Btu/h

20,000

27,000

34,000

40,000

47,000

Heating Capacity (Min - Max)

Btu/h

9,000 – 20,000  9,000 – 27,000  12,000 – 34,000 12,000 – 40,000 12,000 – 47,000 

SEER 

20.0

19.0

19.5

18.0

17.0

EER

14.5

13.5

13.5

12.5

12.0

HSPF

12.0

11.5

10.0

9.5

9.0

Power Supply

V/ph/Hz

208-230/1/60

Minimum Circuit Amps

A

16.5

27.0

Maximum Overcurrent Protection

A

20.0

30.0

Power Consumption - Cooling

kW

1.19

1.68

2.06

2.65

3.05

Power Consumption - Heating

kW

1.41

1.98

2.53

3.03

4.02

Operating Current - Cooling

A

1.2

1.3

1.8

2.2

2.8

Operating Current - Heating

A

1.2

1.3

1.8

2.2

2.8

Indoor Units - FTQ Unitary

Model 

Name

FTQ18PBVJU FTQ24PBVJU FTQ30PBVJU FTQ36PBVJU FTQ42PBVJU 

External Static Pressure

“W.G.

Up to 0.50

Airflow (H/M/L)

CFM

600/510/420

800/680/560

1,000/850/700 1,200/1,020/840 1,400/1,190/980

Piping 
Connections

Liquid (O.D.)

in.

Ø 3/8 

Ø 3/8 

Ø 3/8 

Ø 3/8 

Ø 3/8

Gas (O.D.)

in.

Ø 5/8 

Ø 5/8 

Ø 5/8 

Ø 5/8 

Ø 5/8

Condensate 
Drain

in.

Ø 1 

Ø 1 

Ø 1

Ø 1

Ø 1

Dimensions (H x W x D)

in.

48-1/8 x 22 x 26 

58-1/4 x 22 x 26 

Net Weight

lbs.

150.0

192.0

203.0

Outdoor Units - RZQ_PVJU9 Heat Pump

Model Name

RZQ18PVJU9 RZQ24PVJU9 RZQ30PVJU9 RZQ36PVJU9 RZQ42PVJU9 

Sound Pressure Level -
Cooling/Heating

dB(A)

49/49 49/49 49/49 58/58 58/58 

Operating Range - Cooling

°F DB

23 - 115

23 - 115

23 - 115

23 - 115

23 - 115

Operating  Range  - Heating

°F  DB

0  - 77

0  - 77

0  - 77

0  - 77

0  - 77

Operating Range - Heating

°F WB

0 - 60 

0 - 60 

0 - 60 

0 - 60 

0 - 60 

Max. Piping Length

ft.

98.0

230.0

Max. Piping Height

ft.

98.0

164.0

Dimensions (H x W x D)   

in.

30-5/16 x 35-7/16 x 12-5/8 

52-15/16 x 35-7/16 x 12-5/8 

Net Weight

lbs.

150.0

283.0

*

1 Need 24V AC power supply

*

2 Need 16V DC power supply

*

3 Fixing box is installed beside the unit

Summary of Contents for SkyAir RZQ36PVJU9

Page 1: ...Daikin Inverter Ducted Heat Pump FTQ ...

Page 2: ...ode down to 0 F making them cheaper to run than traditional heat pump systems in most climates They are also more compact and quieter than traditional units Integrated with an inverter variable speed compressor systems deliver the capacity required to maintain desired room conditions reducing energy consumption by 30 compared to traditional fixed speed systems This technology minimizes temperature...

Page 3: ...bient conditions and absolute comfort Daikin Inverter Ducted units provide comfortable heating down to 0 F with up to 100 capacity available at temperatures as low as 14 F With the ability to operate in cooling mode from 23 F to 115 F this makes installation easier in most climates since additional supplemental electric heater is not required Hear the Difference Daikin Inverter Ducted systems have...

Page 4: ... 30 0 Power Consumption Cooling kW 1 19 1 68 2 06 2 65 3 05 Power Consumption Heating kW 1 41 1 98 2 53 3 03 4 02 Operating Current Cooling A 1 2 1 3 1 8 2 2 2 8 Operating Current Heating A 1 2 1 3 1 8 2 2 2 8 Indoor Units FTQ Unitary Model Name FTQ18PBVJU FTQ24PBVJU FTQ30PBVJU FTQ36PBVJU FTQ42PBVJU External Static Pressure W G Up to 0 50 Airflow H M L CFM 600 510 420 800 680 560 1 000 850 700 1 2...

Page 5: ...ies as follow This represents Daikin s free of mind guarantee to ensure full compatibility within the total system offered and top performance EASE OF INSTALLATION Space required for installation in H 19 1 8 Space required for installation in The installation of a secondary drain pan is necessary as shown below Always refer to installation manuals for details Connected by a pair of refrigerant lin...

Page 6: ...e User s Manual provides important safety instructions and warnings Be sure to follow these instructions and warnings For any inquiries contact your local Daikin sales office WARNINGS Organization DAIKIN INDUSTRIES LTD AIR CONDITIONING MANUFACTURING DIVISION Scope of Registration THE DESIGN DEVELOPMENT AND MANUFACTURE OF COMMERCIAL AIR CONDITIONING HEATING COOLING REFRIGERATING EQUIPMENT COMMERCIA...

Reviews: