3 Preparation

Installation manual

6

RZAG71~Y1

Sky Air Alpha-series

4P485927-1 – 2017.04

3

Preparation

3.1

Preparing installation site

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

3.1.1

Installation site requirements of the
outdoor unit

Mind the spacing guidelines. See the "Technical data" chapter, and
the figures on the inside of the front cover.

INFORMATION

The sound pressure level is less than 70 dBA.

CAUTION

Appliance not accessible to the general public, install it in a
secured area, protected from easy access.

This  unit,  both  indoor  and  outdoor,  is  suitable  for
installation 

in 

commercial 

and 

light 

industrial

environment.

4

Installation

4.1

Mounting the outdoor unit

4.1.1

To provide the installation structure

Prepare  4  sets  of  anchor  bolts,  nuts  and  washers  (field  supply)  as
follows:

(mm)

>150

620

350

(345-355)

4× M12

a

a

Make sure not to cover the drain holes of the bottom plate
of the unit.

INFORMATION

The  recommended  height  of  the  upper  protruding  part  of
the bolts is 20 mm.

20

NOTICE

Fix the outdoor unit to the foundation bolts using nuts with
resin  washers  (a).  If  the  coating  on  the  fastening  area  is
stripped off, the nuts rust easily.

a

4.1.2

To install the outdoor unit

4× M12

4.1.3

To provide drainage

INFORMATION

If  necessary,  you  can  use  a  drain  plug  kit  (field  supply)  to
prevent drain water from dripping.

NOTICE

If drain holes of the outdoor unit are covered by a mounting
base  or  by  floor  surface,  raise  the  unit  to  provide  a  free
space of more than 150 mm under the outdoor unit.

≥150 mm

Drain holes (dimensions in mm)

A

B

B

C

D

E

160

160

620

36
61

262

416

595

285

279

260

161

(345~355)

A

Discharge side

B

Distance between anchor points

C

Bottom frame

D

Drain holes

E

Knockout hole for snow

Snow

In regions with snowfall, snow might build up and freeze between the
heat  exchanger  and  the  external  plate.  This  might  decrease  the
operating efficiency. To prevent this:

1

Drill (a, 4×) and remove the knockout hole (b).

Summary of Contents for SkyAir RZAG71M7V1B

Page 1: ...Installation manual Sky Air Alpha series English Installation manual Sky Air Alpha series RZAG71M7V1B RZAG100M7V1B RZAG125M7V1B RZAG140M7V1B RZAG71M7Y1B RZAG100M7Y1B RZAG125M7Y1B RZAG140M7Y1B...

Page 2: ...1000 1000 500 HD HU HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB H...

Page 3: ...onforme altera o em 10 11 12 13 14 15 16 17 Direktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m...

Page 4: ...PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplo...

Page 5: ...tion 13 4 6 2 To check the insulation resistance of the compressor 14 5 Commissioning 14 5 1 Checklist before commissioning 14 5 2 To perform a test run 14 5 3 Error codes when performing a test run 1...

Page 6: ...150 6 2 0 350 3 4 5 3 5 5 4 M12 a a Make sure not to cover the drain holes of the bottom plate of the unit INFORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOT...

Page 7: ...cover a with screw b Remove the piping intake plate c with screw d c a b d 2 Choose a piping route a b c or d a b c d 3 If you have chosen the downwards piping route Drill a 4 and remove the knockout...

Page 8: ...t least 200 kPa 2 bar It is recommended to pressurize to 3000 kPa 30 bar in order to detect small leaks 2 Check for leaks by applying the bubble test solution to all connections 3 Discharge all nitrog...

Page 9: ...ng or recharging activate field setting vacuum mode After finishing vacuum drying or recharging deactivate field setting vacuum mode WARNING Some sections of the refrigerant circuit may be isolated fr...

Page 10: ...e of twin triple and double twin 1 Determine G1 and G2 G1 m Total length of x liquid piping x 9 5 mm standard x 12 7 mm size up G2 m Total length of 6 4 mm liquid piping 2 Determine R1 and R2 If Then...

Page 11: ...e 2 28 3 When 2 28 is reached press the BS3 button once 4 Change the setting to 1 by pressing the BS2 button once 5 Push the BS3 button once 6 When the display is not blinking anymore press the BS3 bu...

Page 12: ...per phase RZAG71 140M7Y1B Equipment complying with EN IEC 61000 3 2 European International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low vo...

Page 13: ...Routing through the frame Choose one of the 3 possibilities a b a b a b 2 3 1 a Power supply cable b Interconnection cable Connecting to the frame When cables are routed from the unit a protection sl...

Page 14: ...arthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have not been bypassed The power supply voltage matches the...

Page 15: ...wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit and user interface The fuse on the outdoor unit PCB has blown out E3 E4 or L8 The stop valv...

Page 16: ...les walls baffle plates E Obstacle roof a b c d e Minimum service space between the unit and obstacles A B C D and E eB Maximum distance between the unit and the edge of obstacle E in the direction of...

Page 17: ...or See note See note Outdoor Outdoor Indoor Indoor Upper Upper Lower Lower Fan Fan ON ON OFF OFF 2 Layout English Translation Layout Layout Front Front Back Back Position of compressor terminal Positi...

Page 18: ...arth leakage circuit breaker 30 mA Q1E Overload protection R1 R8 A1P Y1 only Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T Thermistor heat exchanger R5T Thermistor he...

Page 19: ......

Page 20: ...4P485927 1 2017 04 Copyright 2017 Daikin 4P485927 1 0000000X...

Reviews: