Daikin SkyAir FCAHG71GVEB Installer And User Manual Download Page 16

6 Installation

Installer and user reference guide

16

FCAHG71~140GVEB

Split system air conditioners

4P482875-1 – 2017.03

Piping size

(mm)

Tightening

torque (N•m)

Flare

dimensions (A)

(mm)

Flare shape

(mm)

Ø9.5

33~39

12.8~13.2

R=0.4~0.8

45° ±2

90°±2

A

Ø15.9

63~75

19.3~19.7

6.3.4

Pipe bending guidelines

Use  a  pipe  bender  for  bending.  All  pipe  bends  should  be  as  gentle
as possible (bending radius should be 30~40 mm or larger).

6.3.5

To flare the pipe end

CAUTION

▪ Incomplete flaring may cause refrigerant gas leakage.

▪ Do  NOT  re-use  flares.  Use  new  flares  to  prevent

refrigerant gas leakage.

▪ Use  flare  nuts  that  are  included  with  the  unit.  Using

different flare nuts may cause refrigerant gas leakage.

1

Cut the pipe end with a pipe cutter.

2

Remove  burrs  with  the  cut  surface  facing  down  so  that  the
chips do not enter the pipe.

a

b

a

Cut exactly at right angles.

b

Remove burrs.

3

Remove  the  flare  nut  from  the  stop  valve  and  put  the  flare  nut
on the pipe.

4

Flare  the  pipe.  Set  exactly  at  the  position  as  shown  in  the
following illustration.

A

Flare tool for

R410A or R32

(clutch type)

Conventional flare tool

Clutch type

(Ridgid-type)

Wing nut type

(Imperial-type)

A

0~0.5 mm

1.0~1.5 mm

1.5~2.0 mm

5

Check that the flaring is properly made.

a

b

c

a

Flare’s inner surface must be flawless.

b

The pipe end must be evenly flared in a perfect circle.

c

Make sure the flare nut is fitted.

6.3.6

To braze the pipe end

The  indoor  unit  and  outdoor  unit  have  flare  connections.  Connect
both  ends  without  brazing.  If  brazing  should  be  needed,  take  the
following into account:

▪ When  brazing,  blow  through  with  nitrogen  to  prevent  creation  of

large  quantities  of  oxidised  film  on  the  inside  of  the  piping.  This
film adversely affects valves and compressors in the refrigerating
system and prevents proper operation.

▪ Set  the  nitrogen  pressure  to  20  kPa  (0.2  bar)  (just  enough  so  it

can be felt on the skin) with a pressure-reducing valve.

a

b

c

d

e

f

f

a

Refrigerant piping

b

Part to be brazed

c

Taping

d

Manual valve

e

Pressure-reducing valve

f

Nitrogen

▪ Do NOT use anti-oxidants when brazing pipe joints.

Residue can clog pipes and break equipment.

▪ Do  NOT  use  flux  when  brazing  copper-to-copper  refrigerant

piping.  Use  phosphor  copper  brazing  filler  alloy  (BCuP),  which
does not require flux.
Flux  has  an  extremely  harmful  influence  on  refrigerant  piping
systems. For instance, if chlorine based flux is used, it will cause
pipe  corrosion  or,  in  particular,  if  the  flux  contains  fluorine,  it  will
deteriorate the refrigerant oil.

6.3.7

To connect the refrigerant piping to the
indoor unit

WARNING: FLAMMABLE MATERIAL

The  R32  refrigerant  (if  applicable)  in  this  unit  is  mildly
flammable.

2

Pipe length

. Keep refrigerant piping as short as possible.

Flare  connections

.  Connect  refrigerant  piping  to  the  unit  using

flare connections.

Insulation

.  Insulate  the  refrigerant  piping  on  the  indoor  unit  as

follows:

A

B

a

d

c

e f

b

b

a

d

c

e f

b

b

2

4

3

g

1

2

3

4

g

A

B

1

A

Gas piping

B

Liquid piping

a

Insulation material (field supply)

b

Cable tie (accessory)

c

Insulation pieces: Large (gas pipe), small (liquid pipe)
(accessories)

d

Flare nut (attached to the unit)

e

Refrigerant pipe connection (attached to the unit)

f

Unit

g

Sealing pads: Medium 1 (gas pipe), medium 2 (liquid pipe)
(accessories)

1

Turn up the seams of the insulation pieces.

2

Attach to the base of the unit.

3

Tighten the cable ties on the insulation pieces.

4

Wrap the sealing pad from the base of the unit to the top of
the flare nut.

NOTICE

Make  sure  to  insulate  all  refrigerant  piping.  Any  exposed
piping might cause condensation.

(2)

Refer to the outdoor unit specifications for the type of refrigerant to be used.

Summary of Contents for SkyAir FCAHG71GVEB

Page 1: ...Installer and user reference guide Split system air conditioners English Installer and user reference guide Split system air conditioners FCAHG71GVEB FCAHG100GVEB FCAHG125GVEB FCAHG140GVEB...

Page 2: ...ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis...

Page 3: ...wiring components 17 6 4 5 To connect the electrical wiring on the indoor unit 17 7 Configuration 18 7 1 Field settings 18 8 Commissioning 20 8 1 Overview Commissioning 20 8 2 Precautions when commis...

Page 4: ...ildren aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning us...

Page 5: ...s weight and vibration Make sure the area is well ventilated Do NOT block any ventilation openings Make sure the unit is level Do NOT install the unit in the following places In potentially explosive...

Page 6: ...7 3 6 4 351 3 0 5 74 6 6 27 8 3 0 77 2 6 6 374 3 2 6 54 6 8 29 5 3 2 87 9 6 8 397 3 4 7 38 7 0 31 3 3 4 99 2 7 0 420 3 6 8 27 7 2 33 1 3 6 111 7 2 445 3 8 9 22 7 4 34 9 3 8 124 7 4 470 4 0 10 2 7 6 36...

Page 7: ...wn Open refrigerant cylinders slowly Charge the refrigerant in liquid form Adding it in gas form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing cl...

Page 8: ...e all covers are closed before starting up the unit NOTICE Only applicable if the power supply is three phase and the compressor has an ON OFF starting method If there exists the possibility of revers...

Page 9: ...e Large gas pipe 4 About the units and options 4 1 Overview About the units and options This chapter contains information about Combining outdoor and indoor units Combining the indoor unit with option...

Page 10: ...ral installation site requirements See the General safety precautions chapter Refrigerant piping requirements length height difference See further in this Preparation chapter INFORMATION The sound pre...

Page 11: ...orners open optional blocking pad kit required c Air outlet and corners closed optional blocking pad kit required B Minimum and maximum distance to the floor Minimum 2 5 m to avoid accidental touching...

Page 12: ...ion This chapter describes what you have to do and know on site to install the system Typical workflow Installation typically consists of the following stages Mounting the outdoor unit Mounting the in...

Page 13: ...een the unit and the ceiling opening C Overlap between the decoration panel and the suspended ceiling Installation guide Use the installation guide to determine the correct vertical position A B C a b...

Page 14: ...tion 2 Tighten the metal clamp until the screw head is less than 4 mm from the metal clamp part 3 Check for water leaks see To check for water leaks on page 14 4 Install the insulation piece drain pip...

Page 15: ...to account Avoid anything but the designated refrigerant to get mixed into the refrigerant cycle e g air Only use R32 or R410A1 when adding refrigerant Only use installation tools e g manifold gauge s...

Page 16: ...and compressors in the refrigerating system and prevents proper operation Set the nitrogen pressure to 20 kPa 0 2 bar just enough so it can be felt on the skin with a pressure reducing valve a b c d e...

Page 17: ...Terminal b Screw c Flat washer Tightening torques Wiring Screw size Tightening torque N m Interconnection cable indoor outdoor M4 1 18 1 44 User interface cable M3 5 0 79 0 97 6 4 4 Specifications of...

Page 18: ...ollers control 1 indoor unit 1 50 Hz 220 240 V b a e2 e1 c d a Interconnection cable b Power supply cable c Earth leakage circuit breaker d Fuse e1 Main user interface e2 Optional user interface Force...

Page 19: ...en4 M C1 C2 2500 h light 10 20 0 01 1250 h heavy 02 No notification 3 02 Individual setting in a simultaneous operation system We recommend using the optional user interface to set the slave unit Perf...

Page 20: ...kers 8 3 Checklist before commissioning Do NOT operate the system before the following checks are OK You read the complete installation instructions as described in the installer reference guide The i...

Page 21: ...er supply and outdoor unit between outdoor unit and indoor units between indoor unit and user interface The fuse on the outdoor or indoor unit PCB has blown E3 E4 or L8 The stop valves are closed The...

Page 22: ...l data Installer and user reference guide 22 FCAHG71 140GVEB Split system air conditioners 4P482875 1 2017 03 11 1 Piping diagram Indoor unit b a c a Liquid pipe connection b Gas pipe connection c Hea...

Page 23: ...L OVERLOADPROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIPSWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH F...

Page 24: ...ech Republic A B C D E FCAHG125 7 83 4 27 13 50 0 25 61 FCAHG140 8 68 4 72 15 50 0 25 61 13 User interface CAUTION Never touch the internal parts of the controller Do not remove the front panel Some p...

Page 25: ...erant cycle will reverse and energy from inside the building will be used to defrost the outdoor unit coil The indoor unit will indicate defrost operation on the display Hot start In order to prevent...

Page 26: ...keep the temperature setting at a moderate level Never place objects near the air inlet or the air outlet of the unit It may cause deterioration in the effect or stop the operation Turn off the main...

Page 27: ...loration and deformation 1 Open the suction grille 1 2 Remove the suction grille 45 1 2 3 Remove the air filter 1 2 3 4 Clean the suction grille Wash with a soft bristle brush and water or neutral det...

Page 28: ...es service and warranty 17 5 1 Warranty period This product includes a warranty card that was filled in by the dealer at the time of installation The completed card has to be checked by the customer a...

Page 29: ...to taking apart or cleaning interiors of units by anyone other than our authorised dealers may not be included in the warranty 18 Troubleshooting If one of the following malfunctions occur take the me...

Page 30: ...eration Moisture generated by defrost becomes steam and is exhausted 18 1 6 Symptom The user interface display reads U4 or U5 and stops but then restarts after a few minutes This is because the user i...

Page 31: ...can perform or coordinate the required service to the product Installation manual Instruction manual specified for a certain product or application explaining how to install configure and maintain it...

Page 32: ...4P482875 1 2017 03 Copyright 2017 Daikin...

Reviews: