Daikin SkyAir FCAHG100GVEB Installer And User Manual Download Page 15

6 Installation

Installer and user reference guide

15

FCAHG71~140GVEB
Split system air conditioners
4P482875-1 – 2017.03

≥100 mm

e

d
c

b

a

a

Plastic watering can

b

Service drain outlet (with rubber plug). Use this outlet to
drain water from the drain pan.

c

Drain pump location

d

Drain pipe connection

e

Drain pipe

5

Turn OFF the power.

6

Disconnect the electrical wiring.

▪ Remove the switch box cover.
▪ Disconnect the power supply and earth.
▪ Disconnect the user interface.
▪ Reattach the switch box cover.

6.3

Connecting the refrigerant piping

6.3.1

About connecting the refrigerant piping

Before connecting the refrigerant piping

Make sure the outdoor and indoor unit are mounted.

Typical workflow

Connecting the refrigerant piping involves:

▪ Connecting the refrigerant piping to the outdoor unit

▪ Connecting the refrigerant piping to the indoor unit

▪ Insulating the refrigerant piping

▪ Keeping in mind the guidelines for:

▪ Pipe bending

▪ Flaring pipe ends

▪ Brazing

▪ Using the stop valves

6.3.2

Precautions when connecting the
refrigerant piping

INFORMATION

Also  read  the  precautions  and  requirements  in  the
following chapters:

▪ General safety precautions

▪ Preparation

DANGER: RISK OF BURNING

CAUTION

▪ Do NOT use mineral oil on flared part.

▪ NEVER  install  a  drier  to  this  unit  to  guarantee  its

lifetime. The drying material may dissolve and damage
the system.

NOTICE

Take  the  following  precautions  on  refrigerant  piping  into
account:

▪ Avoid  anything  but  the  designated  refrigerant  to  get

mixed into the refrigerant cycle (e.g. air).

▪ Only use R32 or R410A

1

 when adding refrigerant.

▪ Only use installation tools (e.g. manifold gauge set) that

are exclusively used for R32 or R410A

1

 installations to

withstand the pressure and to prevent foreign materials
(e.g.  mineral  oils  and  moisture)  from  mixing  into  the
system.

▪ Install  the  piping  so  that  the  flare  is  NOT  subjected  to

mechanical stress.

▪ Protect the piping as described in the following table to

prevent dirt, liquid or dust from entering the piping.

▪ Use  caution  when  passing  copper  tubes  through  walls

(see figure below).

Unit

Installation period

Protection method

Outdoor unit

>1 month

Pinch the pipe

<1 month

Pinch or tape the pipe

Indoor unit

Regardless of the
period

INFORMATION

Do  NOT  open  the  refrigerant  stop  valve  before  checking
the refrigerant piping. When you need to charge additional
refrigerant  it  is  recommended  to  open  the  refrigerant  stop
valve after charging.

6.3.3

Guidelines when connecting the
refrigerant piping

Take the following guidelines into account when connecting pipes:

▪ Coat  the  flare  inner  surface  with  ether  oil  or  ester  oil  when

connecting  a  flare  nut.  Tighten  3  or  4  turns  by  hand,  before
tightening firmly.

▪ Always use 2 wrenches together when loosening a flare nut.

▪ Always  use  a  spanner  and  torque  wrench  together  to  tighten  the

flare nut when connecting the piping. This to prevent nut cracking
and leaks.

a

b

c

d

a

Torque wrench

b

Spanner

c

Piping union

d

Flare nut

(1)

Refer to the outdoor unit specifications for the type of refrigerant to be used.

Summary of Contents for SkyAir FCAHG100GVEB

Page 1: ...Installer and user reference guide Split system air conditioners English Installer and user reference guide Split system air conditioners FCAHG71GVEB FCAHG100GVEB FCAHG125GVEB FCAHG140GVEB...

Page 2: ...ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis...

Page 3: ...wiring components 17 6 4 5 To connect the electrical wiring on the indoor unit 17 7 Configuration 18 7 1 Field settings 18 8 Commissioning 20 8 1 Overview Commissioning 20 8 2 Precautions when commis...

Page 4: ...ildren aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning us...

Page 5: ...s weight and vibration Make sure the area is well ventilated Do NOT block any ventilation openings Make sure the unit is level Do NOT install the unit in the following places In potentially explosive...

Page 6: ...7 3 6 4 351 3 0 5 74 6 6 27 8 3 0 77 2 6 6 374 3 2 6 54 6 8 29 5 3 2 87 9 6 8 397 3 4 7 38 7 0 31 3 3 4 99 2 7 0 420 3 6 8 27 7 2 33 1 3 6 111 7 2 445 3 8 9 22 7 4 34 9 3 8 124 7 4 470 4 0 10 2 7 6 36...

Page 7: ...wn Open refrigerant cylinders slowly Charge the refrigerant in liquid form Adding it in gas form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing cl...

Page 8: ...e all covers are closed before starting up the unit NOTICE Only applicable if the power supply is three phase and the compressor has an ON OFF starting method If there exists the possibility of revers...

Page 9: ...e Large gas pipe 4 About the units and options 4 1 Overview About the units and options This chapter contains information about Combining outdoor and indoor units Combining the indoor unit with option...

Page 10: ...ral installation site requirements See the General safety precautions chapter Refrigerant piping requirements length height difference See further in this Preparation chapter INFORMATION The sound pre...

Page 11: ...orners open optional blocking pad kit required c Air outlet and corners closed optional blocking pad kit required B Minimum and maximum distance to the floor Minimum 2 5 m to avoid accidental touching...

Page 12: ...ion This chapter describes what you have to do and know on site to install the system Typical workflow Installation typically consists of the following stages Mounting the outdoor unit Mounting the in...

Page 13: ...een the unit and the ceiling opening C Overlap between the decoration panel and the suspended ceiling Installation guide Use the installation guide to determine the correct vertical position A B C a b...

Page 14: ...tion 2 Tighten the metal clamp until the screw head is less than 4 mm from the metal clamp part 3 Check for water leaks see To check for water leaks on page 14 4 Install the insulation piece drain pip...

Page 15: ...to account Avoid anything but the designated refrigerant to get mixed into the refrigerant cycle e g air Only use R32 or R410A1 when adding refrigerant Only use installation tools e g manifold gauge s...

Page 16: ...and compressors in the refrigerating system and prevents proper operation Set the nitrogen pressure to 20 kPa 0 2 bar just enough so it can be felt on the skin with a pressure reducing valve a b c d e...

Page 17: ...Terminal b Screw c Flat washer Tightening torques Wiring Screw size Tightening torque N m Interconnection cable indoor outdoor M4 1 18 1 44 User interface cable M3 5 0 79 0 97 6 4 4 Specifications of...

Page 18: ...ollers control 1 indoor unit 1 50 Hz 220 240 V b a e2 e1 c d a Interconnection cable b Power supply cable c Earth leakage circuit breaker d Fuse e1 Main user interface e2 Optional user interface Force...

Page 19: ...en4 M C1 C2 2500 h light 10 20 0 01 1250 h heavy 02 No notification 3 02 Individual setting in a simultaneous operation system We recommend using the optional user interface to set the slave unit Perf...

Page 20: ...kers 8 3 Checklist before commissioning Do NOT operate the system before the following checks are OK You read the complete installation instructions as described in the installer reference guide The i...

Page 21: ...er supply and outdoor unit between outdoor unit and indoor units between indoor unit and user interface The fuse on the outdoor or indoor unit PCB has blown E3 E4 or L8 The stop valves are closed The...

Page 22: ...l data Installer and user reference guide 22 FCAHG71 140GVEB Split system air conditioners 4P482875 1 2017 03 11 1 Piping diagram Indoor unit b a c a Liquid pipe connection b Gas pipe connection c Hea...

Page 23: ...L OVERLOADPROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIPSWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH F...

Page 24: ...ech Republic A B C D E FCAHG125 7 83 4 27 13 50 0 25 61 FCAHG140 8 68 4 72 15 50 0 25 61 13 User interface CAUTION Never touch the internal parts of the controller Do not remove the front panel Some p...

Page 25: ...erant cycle will reverse and energy from inside the building will be used to defrost the outdoor unit coil The indoor unit will indicate defrost operation on the display Hot start In order to prevent...

Page 26: ...keep the temperature setting at a moderate level Never place objects near the air inlet or the air outlet of the unit It may cause deterioration in the effect or stop the operation Turn off the main...

Page 27: ...loration and deformation 1 Open the suction grille 1 2 Remove the suction grille 45 1 2 3 Remove the air filter 1 2 3 4 Clean the suction grille Wash with a soft bristle brush and water or neutral det...

Page 28: ...es service and warranty 17 5 1 Warranty period This product includes a warranty card that was filled in by the dealer at the time of installation The completed card has to be checked by the customer a...

Page 29: ...to taking apart or cleaning interiors of units by anyone other than our authorised dealers may not be included in the warranty 18 Troubleshooting If one of the following malfunctions occur take the me...

Page 30: ...eration Moisture generated by defrost becomes steam and is exhausted 18 1 6 Symptom The user interface display reads U4 or U5 and stops but then restarts after a few minutes This is because the user i...

Page 31: ...can perform or coordinate the required service to the product Installation manual Instruction manual specified for a certain product or application explaining how to install configure and maintain it...

Page 32: ...4P482875 1 2017 03 Copyright 2017 Daikin...

Reviews: