background image

9

English

CAUTION

• The drain piping will be clogged with water and water leakage 

may result if the water is accumulated in the drain piping.

• Conduct drain-up piping work if the gradient is insuffi-

cient.

• Attach a support bracket at 3.3 to 4.9 ft (1 to 1.5 m) 

intervals for the prevention of piping deflection.

• Be sure to use the drain hose (2) and metal clamp (1).

Insert the drain hose (2) deep into the base of the 
drain socket, and securely fasten the metal clamp (1) 
within the taped part on the insertion front end of the 
hose.

Be sure to fasten the screw of the metal clamp (1) until 
the margin of the screw thread decreases to 3/16 in. 
(4 mm) or less.

NOTE

Be sure to follow the instructions as below.

• Do not connect the drain piping directly to a sewer that 

smells of ammonia.
The ammonia in the sewer may reach through the drain 
piping and corrode the heat exchanger of the indoor unit.

• Do not bend or twist the provided drain hose (2) in order 

not to impose excessive force on the hose. (Doing so 
may result in water leakage.)

• Take the procedure shown in the following illustration to 

perform concentrated drain piping.

• Select the diameter of the concentrated drain piping to 

suit the capacity of equipment connecting to the concen-
trated drain piping (see Engineering Data).

(2) Check that drainage flows smoothly on completion of the 

installation of the piping.

[Before electrical work]

CAUTION

• A licensed electrical engineering technician must con-

duct electrical wiring work (including grounding work).

• If no licensed electrical engineering technician is avail-

able, take steps 3 and 4 after the test operation of the air 
conditioner is finished.

1. Remove the control box cover, 

and connect the single-

phase electric wires to terminals L

1

 and L

2

 of the ter-

minal block and the ground wiring to the ground ter-
minal

.

Perform wiring according to 

10-1. CONNECTING 

POWER SUPPLY, GROUND, REMOTE CONTROLLER, 
AND TRANSMISSION WIRING

 in 

10. WIRING EXAM-

PLE AND HOW TO SET THE REMOTE CONTROLLER

.

CAUTION

• In order not to impose tension on the wire connections, per-

form clamping securely with the provided clamp (8) specified 
in 3 in 

10-1. CONNECTING POWER SUPPLY, GROUND, 

REMOTE CONTROLLER, AND TRANSMISSION WIRING

.

2. Check that the control box cover is closed before turning 

the air conditioner ON.

3. Provide 

approximately 1/4 gal (1  ) of water

 gradually 

into the drain pan through the water inlet on the bottom of 
the drain socket or the outlet. Make sure that the water is 
not spilled onto the drain pump.

4. The drain pump will operate with the power turned ON. 

Check that the pump drains water smoothly. (The drain 
pump will stop automatically in 10 minutes.)

3.3 - 4.9 ft

(1 - 1.5 m)

Support bracket

Downward slope of at least 1/100

(accessory)

(accessory)

Metal clamp (1)

Tape

Drain hose (2)

Concentrated drain piping

The drain piping will be clogged with water 
and water leakage may result if the water is 
accumulated in the drain piping.

Maintain 

a downward slope of at least 

1/100

 so that no air bank will be formed.

18 - 3/8 in.

(467 mm)

Ceiling slab

3.3 - 4.9 ft

(1 - 1.5 m)

12 in. (300 mm) 

max.

28 in. (700 mm) 

max.

Support bracket

Drain-up piping 
(field supply)

Adjustable 
(18-3/8 in. (467 mm) max.)

Metal clamp (1) (accessory)

Drain hose (2) (accessory)

Drain hose (2) (accessory)

Horizontal or 
upward slope

If there is an air bank, noise may be generated 
as a result of a water backflow when the drain 
pump comes to a stop.

Locate the drain hose horizontally 
or with a little upward gradient.

01_EN_3P530815-1.fm  Page 9  Tuesday, July 10, 2018  6:20 PM

Summary of Contents for SkyAir FBQ18PVJU

Page 1: ...y place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel à portée de main pour référence ultérieure Ce manuel doit être donné au propriétaire de l équipement Lea cuidadosamente estas instrucciones antes de instalar Guarde este manual en un lugar a mano para leer en caso de tener alguna duda Este ma...

Page 2: ...rant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause seri ous injury or death Safely dispose of all packing and tran...

Page 3: ...it is released Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter REFRIGERANT PIPING WORK and follow the procedures Since R410A is a blend the required additional refriger ant must be charged in its liquid state If the refrigerant is charged in a gaseous state its composition can change and the system will not work properly The indoor ...

Page 4: ...salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels This unit both indoor and outdoor is suitable for installation in a commercial and light industrial environment If installed as a household appliance it could cause electro magnetic interference WARNING Entrust installation to the place of purchase or a qualified ser viceman ...

Page 5: ... the outdoor unit Remote controller Model Wired type BRC1E73 Wireless type 2 speed BRC4C82 3 speed BRC082A43 Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor units fixed firmly The units may drop vibrate or make noise Was the installation of the outdoor unit completed The unit may malfunction or the components burn out Is the gas leak test finished ...

Page 6: ...50 450 for the control box and inspection hatch 2 for the lower part of the product see arrow view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower part of the control box see arrow view A 2 Refer to Fig 2 3 unit in mm Ceiling Floor surface The H1 dimension indicates the height of the product Determine the H2 dimension by maintaining a downward slope of at ...

Page 7: ...just the distance to the ceiling surface in advance 5 INDOOR UNIT INSTALLATION It may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manuals provided to the accessories as well Be sure to use the accessories and specified parts for installation work 1 Temporally install the indoor unit Connect the hangers to the suspension bolts Be sure...

Page 8: ...nut provided with the unit Do not use a different flare nut such as a type 1 flare nut or otherwise refrigerant leakage may result To prevent contamination or moisture from getting into the piping take measures such as pinching or taping the ends of the pipes Be sure to use the specified type of refrigerant for the refrigeration cycle and do not contaminate the refrigerant with air Ventilate the r...

Page 9: ...g alloy BCuP 2 BCu 93P 710 795 which does not require flux for brazing Flux has a bad influence on the refrigerant piping Chlo rine based flux will cause piping corrosion Furthermore if it contains fluorine the flux will deteriorate refrigerant oil 7 DRAIN PIPING WORK 1 Conduct drain piping work Check that the piping ensures proper draining Make sure that the diam eter of the piping exclud ing the...

Page 10: ... conditioner is finished 1 Remove the control box cover and connect the single phase electric wires to terminals L1 and L2 of the ter minal block and the ground wiring to the ground ter minal Perform wiring according to 10 1 CONNECTING POWER SUPPLY GROUND REMOTE CONTROLLER AND TRANSMISSION WIRING in 10 WIRING EXAM PLE AND HOW TO SET THE REMOTE CONTROLLER CAUTION In order not to impose tension on t...

Page 11: ... the sputter will not come in contact with the drain pan or the filter If the metal duct pass through a metal lath wire lath or metal plate of a wooden structure separate the duct and wall elec trically Be sure to insulate the duct for the prevention of dew conden sation Material Glass wool or styrene foam Thickness 1 in 25 mm Be sure to attach a field supplied air filter to the air inlet of the u...

Page 12: ...ECTRICAL CHARACTERISTICS MCA Minimum Circuit Ampacity A MOP Maximum Overcurrent Protective Device A KW Fan Motor Rated Output kW FLA Full Load Ampere A 9 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Allowable lengths of transmission wiring and remote controller wiring are as follows 1 Outdoor unit Indoor unit Max 3280 ft 1 000 m 2 Indoor unit Remote controller Max 1640 ft 500 m NOTE Vinyl co...

Page 13: ...ed insulat ing tube and secure it with the included clamp separately When using the insulating tube Cut off the insulation tube at needed length WARNING Trim and lay the wiring neatly and attach the control box cover securely An electric shock or fire may result if the control box cover catches any wiring or the wires push up the cover Low voltage wiring inlet Transmission wiring Low voltage Remot...

Page 14: ...s too small and the terminal screws will not be tightened properly Do not tighten the terminal screws excessively or otherwise the screw heads may be damaged Refer to the table below for the required tightening torque val ues of the terminal screws 10 2 WIRING EXAMPLE COMPLETE SYSTEM EXAMPLE 1 When using 1 remote controller Normal operation 2 When using 2 remote controllers Tightening torque lbf f...

Page 15: ...losed on the indoor and outdoor units Field setting must be made from the remote controller in accordance with the installation conditions Setting can be made by changing the Mode No FIRST CODE NO and SECOND CODE NO For setting procedures and instructions refer to the Field Settings in the installation manual of the remote controller With wireless remote controller used Set the wireless remote con...

Page 16: ...is that 02 is set for the SECOND CODE NO in Table 2 If the air conditioner does not stop operating automatically or the SECOND CODE NO is not 02 repeat steps from 3 If the outdoor unit is not turned ON U4 or UH as explained in Table 5 will be displayed This dis play is not problematic because this function is set for the indoor unit Continue setting the function After setting this function be sure...

Page 17: ...nish work is completed If the air conditioner is operated the inside of the indoor unit may be polluted by substances generated from the coating and adhesives used for the interior finish work and cause water splash and leakage To the operator carrying out test operation After the test operation is completed before delivering the air conditioner to the customer confirm that the control box cover t...

Page 18: ... 1809 HT 3P530815 1 EM18A001 ...

Reviews: