background image

6 Installation

Installer reference guide

18

RZASG71~Y1

Sky Air Advance-series

4P486047-1 – 2017.04

a

b

c

a

Internal service port

b

Stop valve with service port (liquid)

c

Stop valve with service port (gas)

Typical  workflow  –  Completely  recharging  refrigerant  typically
consists of the following stages:

1 Determining how much refrigerant to charge.

2 Charging refrigerant.

3 Filling in the fluorinated greenhouse gases label, and fixing it to

the inside of the outdoor unit.

6.6.2

About the refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

Refrigerant type: R32

Global warming potential (GWP) value: 675

WARNING: FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

WARNING

▪ Do NOT pierce or burn refrigerant cycle parts.

▪ Do NOT use cleaning materials or means to accelerate

the  defrosting  process  other  than  those  recommended
by the manufacturer.

▪ Be  aware  that  the  refrigerant  inside  the  system  is

odourless.

WARNING

The  refrigerant  inside  the  unit  is  mildly  flammable,  but
normally does not leak. If the refrigerant leaks in the room
and comes in contact with fire from a burner, a heater, or a
cooker, this may result in fire, or the formation of a harmful
gas.

Turn  off  any  combustible  heating  devices,  ventilate  the
room,  and  contact  the  dealer  from  which  you  purchased
the unit.

Do not use the unit until a service person confirms that the
portion from which the refrigerant leaked is repaired.

6.6.3

Precautions when charging refrigerant

INFORMATION

Also  read  the  precautions  and  requirements  in  the
following chapters:

▪ General safety precautions

▪ Preparation

6.6.4

Definitions: L1~L7, H1, H2

Pair

(a)

H1

L1

Twin

(a)

H1

H2

L1

L2

L3

Triple

(a)

L2

L3

L4

H1

H2

L1

Double twin

(a)

H1

H2

L1

L2

L3

L4

L5

L6

L7

(a)

Assume that the longest line in the illustration corresponds
with the actual longest pipe, and the highest unit in the
illustration corresponds with the actual highest unit.

L1

Main piping

L2~L7

Branch piping

H1

Height difference between the highest indoor unit and the
outdoor unit

H2

Height difference between the highest and the lowest
indoor unit
Refrigerant branch kit

6.6.5

To determine the additional refrigerant
amount

To determine if adding additional refrigerant is necessary

If

Then

(L1+L2+L3+L4+L5+L6+L7)≤
30 m (chargeless length)

You do not have to add
additional refrigerant.

(L1+L2+L3+L4+L5+L6+L7)>
30 m (chargeless length)

You must add additional
refrigerant.

For future servicing, encircle the
selected amount in the tables
below.

Summary of Contents for Sky Air Advance Series

Page 1: ...Installer reference guide Sky Air Advance series English Installer reference guide Sky Air Advance series RZASG71M2V1B RZASG100M7V1B RZASG125M7V1B RZASG140M7V1B RZASG100M7Y1B RZASG125M7Y1B RZASG140M7Y1B ...

Page 2: ...Precautions when checking the refrigerant piping 16 6 5 3 Checking refrigerant piping Setup 16 6 5 4 To check for leaks 16 6 5 5 To perform vacuum drying 17 6 6 Charging refrigerant 17 6 6 1 About charging refrigerant 17 6 6 2 About the refrigerant 18 6 6 3 Precautions when charging refrigerant 18 6 6 4 Definitions L1 L7 H1 H2 18 6 6 5 To determine the additional refrigerant amount 18 6 6 6 To det...

Page 3: ...NOT touch the refrigerant piping water piping or internal parts during and immediately after operation It could be too hot or too cold Give it time to return to normal temperature If you must touch it wear protective gloves Do NOT touch any accidental leaking refrigerant WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make con...

Page 4: ...Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case re charge is required refer to the nameplate of the unit It states the type of refrigerant and necessary amount The unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional charging of refrigerant Only u...

Page 5: ... earth leakage protector make sure it is compatible with the inverter resistant to high frequency electric noise to avoid unnecessary opening of the earth leakage protector NOTICE Precautions when laying power wiring Do not connect wiring of different thicknesses to the power terminal block slack in the power wiring may cause abnormal heat When connecting wiring which is the same thickness do as s...

Page 6: ... do and know to install the system Commissioning What to do and know to commission the system after it is installed Hand over to the user What to give and explain to the user Maintenance and service How to maintain and service the units Troubleshooting What to do in case of problems Disposal How to dispose of the system Technical data Specifications of the system Glossary Definition of terms 3 Abo...

Page 7: ...on manual of the refrigerant branch kit Demand adaptor kit SB KRP58M52 Includes the additional mounting plate EKMKSA2 Can be used for the following Low noise To lower the operation sound of the outdoor unit I demand function To limit the power consumption from the system example budget control limit power consumption during peak moments For installation instructions see the installation manual of ...

Page 8: ...ight be higher than the sound pressure level mentioned in Sound spectrum in the data book due to environmental noise and sound reflections INFORMATION The sound pressure level is less than 70 dBA In places where a mineral oil mist spray or vapour may be present in the atmosphere Plastic parts may deteriorate and fall off or cause water leakage It is NOT recommended to install the unit in the follo...

Page 9: ...ponds with the actual highest unit L1 Main piping L2 L7 Branch piping H1 Height difference between the highest indoor unit and the outdoor unit H2 Height difference between the highest and the lowest indoor unit Refrigerant branch kit Refrigerant piping material Piping material Phosphoric acid deoxidised seamless copper Piping temper grade and thickness Outer diameter Ø Temper grade Thickness t a ...

Page 10: ...win L2 L3 Limit L4 L5 Limit L6 L7 Limit L2 L4 L3 L7 Limit 10 m 6 Maximum height between indoor and outdoor Pair twin triple and double twin H1 Limit 30 m 7 Maximum height between indoors Pair N A Twin triple and double twin H2 Limit 0 5 m a Parenthesised figure represents the equivalent length Example If the system layout is as follows Then the requirements are RZASG125 Triple L2 L3 L4 H1 H2 L1 Ø ...

Page 11: ...ping Charging refrigerant Connecting the electrical wiring Finishing the outdoor installation Finishing the indoor installation INFORMATION For installation of the indoor unit mounting the indoor unit connecting the refrigerant piping to the indoor unit connecting the electrical wiring to the indoor unit see the installation manual of the indoor unit 6 2 Opening the units 6 2 1 About opening the u...

Page 12: ...e unit in order to prevent the invasion of water in the unit and to avoid the drain water dripping see the following illustration INFORMATION If necessary you can use a drain plug kit field supply to prevent drain water from dripping NOTICE If drain holes of the outdoor unit are covered by a mounting base or by floor surface raise the unit to provide a free space of more than 150 mm under the outd...

Page 13: ...ything but the designated refrigerant to get mixed into the refrigerant cycle e g air Only use R32 when adding refrigerant Only use installation tools e g manifold gauge set that are exclusively used for R32 installations to withstand the pressure and to prevent foreign materials e g mineral oils and moisture from mixing into the system Install the piping so that the flare is NOT subjected to mech...

Page 14: ...sed film on the inside of the piping This film adversely affects valves and compressors in the refrigerating system and prevents proper operation Set the nitrogen pressure to 20 kPa 0 2 bar just enough so it can be felt on the skin with a pressure reducing valve a b c d e f f a Refrigerant piping b Part to be brazed c Taping d Manual valve e Pressure reducing valve f Nitrogen Do NOT use anti oxida...

Page 15: ...door unit Piping length Keep field piping as short as possible Piping protection Protect the field piping against physical damage 1 Do the following Remove the service cover a with screw b Remove the piping intake plate c with screw d c a b d 2 Choose a piping route a b c or d a b c d 3 If you have chosen the downwards piping route Drill a 4 and remove the knockout hole b Cut out the slits c with ...

Page 16: ...sists of the following stages 1 Checking for leaks in the refrigerant piping 2 Performing vacuum drying to remove all moisture air or nitrogen from the refrigerant piping If there is a possibility of moisture being present in the refrigerant piping for example water may have entered the piping first carry out the vacuum drying procedure below until all moisture has been removed 6 5 2 Precautions w...

Page 17: ...nit is factory charged with refrigerant but in some cases the following might be necessary What When Charging additional refrigerant When the total liquid piping length is more than specified see later Completely recharging refrigerant Example When relocating the system After a leak Charging additional refrigerant Before charging additional refrigerant make sure the outdoor unit s external refrige...

Page 18: ...eak If the refrigerant leaks in the room and comes in contact with fire from a burner a heater or a cooker this may result in fire or the formation of a harmful gas Turn off any combustible heating devices ventilate the room and contact the dealer from which you purchased the unit Do not use the unit until a service person confirms that the portion from which the refrigerant leaked is repaired 6 6...

Page 19: ...2 contains fluorinated greenhouse gases Its global warming potential GWP value is 675 Do NOT vent these gases into the atmosphere When charging refrigerant always use protective gloves and safety glasses CAUTION To avoid compressor breakdown do NOT charge more than the specified amount of refrigerant Prerequisite Before charging refrigerant make sure the refrigerant piping is connected and checked...

Page 20: ...efrigerant charge in the system expressed as tonnes CO2 equivalent is used to determine the maintenance intervals Follow the applicable legislation Formula to calculate the greenhouse gas emissions GWP value of the refrigerant Total refrigerant charge in kg 1000 2 Fix the label on the inside of the outdoor unit There is a dedicated place for it on the wiring diagram label 6 7 Connecting the electr...

Page 21: ...able legislation Interconnection cables Minimum cable section of 2 5 mm and applicable for 230 V Recommended field fuse 20 A 25 A 32 A 16 A 20 A Earth leakage circuit breaker Must comply with applicable legislation a MCA Minimum circuit ampacity Stated values are maximum values see electrical data of combination with indoor units for exact values 6 7 6 To connect the electrical wiring on the outdo...

Page 22: ...he frame When cables are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at the knockout hole When you do not use a wire conduit protect the wires with vinyl tubes to prevent the edge of the knockout hole from cutting the wires a b c d e A B A Inside of the outdoor unit B Outside of the outdoor unit a Wire b Bush c Nut d Frame e Hose 6 Reattach the service c...

Page 23: ... heat up the compressor oil to avoid oil shortage and compressor breakdown during startup NOTICE NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor might result NOTICE Do NOT operate the unit until the refrigerant piping is complete when operated this way the compressor will break NOTICE Cooling operation mode Perform the test run in cooling opera...

Page 24: ...rvice cover to prevent electric shocks 3 Turn ON power for at least 6 hours before starting operation to protect the compressor 4 On the user interface set the unit to cooling operation mode 2 Start the test run Action Result 1 Go to the home menu Cool Set to 28 C 2 Press at least 4 seconds The Service Settings menu is displayed Action Result 3 Select Test Operation Return Setting Service Settings...

Page 25: ...g the unit 9 Maintenance and service NOTICE Maintenance must be done by an authorised installer or service agent We recommend to do maintenance at least once a year However applicable legislation might require shorter maintenance intervals NOTICE In Europe the greenhouse gas emissions of the total refrigerant charge in the system expressed as tonnes CO2 equivalent is used to determine the maintena...

Page 26: ...ty for reuse recycling and recovery 11 1 Overview Disposal Typical workflow Disposing of the system typically consists of the following stages 1 Pumping down the system 2 Bringing the system to a specialized treatment facility INFORMATION For more details see the service manual 11 2 About pump down The unit is equipped with an automatic pump down function with which you can collect all refrigerant...

Page 27: ... row of units A E a b c d e eB eD a b c d e eB eD A B C D E B HU HD H B 100 A B C 250 100 100 B E 100 1000 500 A B C E 250 150 150 1000 500 D 500 D E 500 1000 500 B D 100 500 B D E 1 2 1 HB HD HB HU 250 750 1000 500 HU HB HU 250 1000 1000 500 HB HU HB HD HD HU 100 1000 1000 500 HU HD HU 200 1000 1000 500 HD HU A B C 250 300 1000 A B C E 250 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 ...

Page 28: ...he upper unit high enough above the lower unit to prevent ice buildup at the upper unit s bottom plate B1 B2 B1 If there is no danger of drainage dripping and freezing between the upper and lower units B2 Then it is not required to install a roof but seal the gap between the upper and lower units to prevent discharged air from flowing back to the suction side through the bottom of the unit 12 3 Pi...

Page 29: ...tective devices S1PH S1PLand Q1E 3 Refer to the combination table and the option manual for how to connect the wiring to X6A X28A and X77A 4 Colours BLK black RED red BLU blue WHT white GRN green 4 Legend English Translation Legend Legend Field supply Field supply Optional Optional Part n Part n Description Description A1P Printed circuit board main A2P Printed circuit board noise filter BS1 BS3 A...

Page 30: ...plicable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual Instruction manual specified for a certain product or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Mainten...

Page 31: ......

Page 32: ...4P486047 1 2017 04 Copyright 2017 Daikin ...

Reviews: