Daikin Sky Air Advance RZA200D7Y1B Installation Manual Download Page 8

4 Installation

Installation manual

8

250D7Y1B

Sky Air Advance-series

4P573384-1 – 2019.04

c

Rear

d

Bottom

INFORMATION

b

b

b

b

a

a

▪ Remove  the  knockout  hole  (a)  in  the  bottom  plate  or

cover plate by tapping on the attachment points with a
flat head screwdriver and a hammer.

▪ Optionally, cut out the slits (b) with a metal saw.

NOTICE

Precautions when making knockout holes:

▪ Avoid damaging the casing and underlying piping.

▪ After  making  the  knockout  holes,  we  recommend  to

remove  the  burrs  and  paint  the  edges  and  areas
around the edges using repair paint to prevent rusting.

▪ When  passing  electrical  wiring  through  the  knockout

holes,  wrap  the  wiring  with  protective  tape  to  prevent
damage.

3

Select  the  correct  accessory  pipes,  depending  on  the  chosen
route:

▪ Front, side and rear route: 

short

 liquid and gas pipes.

▪ Bottom route: 

long

 liquid and gas pipes.

4

Do the following:

▪ Connect the accessory liquid pipe (a) to the liquid stop valve

(brazing).

▪ Connect  the  accessory  gas  pipe  (b)  to  the  gas  stop  valve

(brazing).

a

b

5

Connect  the  field  piping  to  the  accessory  pipes  using  the
accessory  bend  pipes  (brazing).  Mind  the  orientation  of  the
bends.

NOTICE

Always  protect  the  surrounding  surfaces  (e.g.  wiring,
insulation foam, …) from heat when brazing.

6

Do the following:

▪ Insulate the liquid piping (a) and the gas piping (b).
▪ Wind  heat  insulation  around  the  curves,  and  then  cover  it

with vinyl tape (c).

▪ Make  sure  the  field  piping  does  not  touch  any  compressor

components.

▪ Seal the insulation ends (sealant etc.) (d).
▪ Wrap the field piping with vinyl tape (e) to protect it against

sharp edges

b

a

c

d

f

e

7

If  the  outdoor  unit  is  installed  above  the  indoor  unit,  cover  the
stop  valves  (f,  see  above)  with  sealing  material  to  prevent
condensed water on the stop valves from moving to the indoor
unit.

NOTICE

Any exposed piping might cause condensation.

8

Reattach the service cover and the piping intake plate.

9

Seal  all  gaps  (example:  a)  to  prevent  snow  and  small  animals
from entering the system.

a

NOTICE

Do not block the air vents. This could affect air circulation
inside the unit.

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

NOTICE

Make  sure  to  open  the  stop  valves  after  installing  the
refrigerant  piping  and  performing  vacuum  drying.  Running
the  system  with  the  stop  valves  closed  may  break  the
compressor.

Summary of Contents for Sky Air Advance RZA200D7Y1B

Page 1: ...Installation manual Sky Air Advance series English Installation manual Sky Air Advance series RZA200D7Y1B RZA250D7Y1B ...

Page 2: ... HD HU 200 1000 1000 500 HD HU A B C 200 1 300 1000 A B C E 200 1 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 250 1500 300 1500 B D E HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 500 HB HU HD HU 250 1500 1000 500 HU HD HU 300 1500 1000 500 HD HU HB HD HU mm HU a b c d e eB eD A B C D E HB HD 100 1 100 1 1 b mm 1000 200 2000 100 3000 1500 b 100 1 HB HU 100 1 100 1 HB HU b 250 HU...

Page 3: ...1 12 13 14 15 16 17 Direktiver med senere ændringer Direktiv med företagna ändringar Direktiver med foretatte endringer Direktiivejä sellaisina kuin ne ovat muutettuina v platném znění Smjernice kako je izmijenjeno irányelv ek és módosításaik rendelkezéseit z późniejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muud...

Page 4: ...rin sallittu lämpötila TS TSmin Alhaisin matalapainepuolen lämpötila L C TSmax Suurinta sallittua painetta PS vastaava kyllästyslämpötila M C Kylmäaine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maximální přípustný tlak PS K bar Minimální maximální přípustná teplota TS TSmin Minimální teplota na nízkotlaké straně L C TSmax Saturovaná teplota odpoví...

Page 5: ...ssioning 14 5 2 To perform a test run 15 5 3 Error codes when performing a test run 16 6 Disposal 16 7 Technical data 17 7 1 Service space Outdoor unit 17 7 2 Piping diagram Outdoor unit 17 7 3 Wiring diagram Outdoor unit 18 1 About the documentation 1 1 About this document Target audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops i...

Page 6: ...iance or an operating electric heater 3 1 1 Installation site requirements of the outdoor unit Mind the spacing guidelines See the Technical data chapter and the figures on the inside of the front cover INFORMATION The sound pressure level is less than 70 dBA CAUTION Appliance not accessible to the general public install it in a secured area protected from easy access This unit both indoor and out...

Page 7: ...eze between the heat exchanger and the casing of the unit This might decrease the operating efficiency INFORMATION We suggest to install the optional bottom plate heater EKBPH250D7 when the unit is installed in cold climates 4 1 4 To prevent the outdoor unit from falling over In case the unit is installed in places where strong wind can tilt the unit take following measure 1 Prepare 2 cables as in...

Page 8: ...ntation of the bends NOTICE Always protect the surrounding surfaces e g wiring insulation foam from heat when brazing 6 Do the following Insulate the liquid piping a and the gas piping b Wind heat insulation around the curves and then cover it with vinyl tape c Make sure the field piping does not touch any compressor components Seal the insulation ends sealant etc d Wrap the field piping with viny...

Page 9: ... copper flare 4 3 3 To perform vacuum drying To remove all moisture from the system proceed as follows 1 Check that with the vacuum pump turned off the target vacuum is maintained for at least 1 hour 4 4 Charging refrigerant 4 4 1 About charging refrigerant The outdoor unit is factory charged with refrigerant but in some cases the following might be necessary What When Charging additional refriger...

Page 10: ... the refrigerant This product contains fluorinated greenhouse gases Do NOT vent gases into the atmosphere Refrigerant type R32 Global warming potential GWP value 675 WARNING FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING The appliance shall be stored in a room without continuously operating ignition sources example open flames an operating gas appliance or an opera...

Page 11: ...70 R1 0 45 0 9 1 35 1 8 2 25 2 7 3 15 Standard liquid pipe size Length m 0 10 10 20 20 30 30 40 40 50 50 60 60 70 R2 0 2 0 4 0 6 0 8 1 1 2 1 4 Size up liquid pipe size Length m 0 5 5 10 10 15 15 20 20 25 25 30 R1 0 35 0 7 1 05 1 1 1 75 2 1 R2 0 18 0 35 0 53 0 7 0 88 1 05 3 Determine the additional refrigerant amount R R1 R2 Examples Layout Additional refrigerant amount R L2 7 m Ø9 5 mm L3 5 m Ø9 5...

Page 12: ...e refrigerant WARNING Only use R32 as refrigerant Other substances may cause explosions and accidents R32 contains fluorinated greenhouse gases Its global warming potential GWP value is 675 Do NOT vent these gases into the atmosphere When charging refrigerant ALWAYS use protective gloves and safety glasses Prerequisite Before completely recharging refrigerant make sure the system is pumped down th...

Page 13: ... 18 6 A 19 9 A Voltage range 380 415 V Phase 3N Frequency 50 Hz Wire sizes Must comply with applicable legislation Interconnection cables H05VV U4G2 5 Recommended field fuse 20 A Earth leakage circuit breaker Must comply with applicable legislation a MCA Minimum circuit ampacity Stated values are maximum values see electrical data of combination with indoor units for exact values 4 5 3 To connect ...

Page 14: ...ck the insulation resistance of the compressor NOTICE If after installation refrigerant accumulates in the compressor the insulation resistance over the poles can drop but if it is at least 1 MΩ then the unit will not break down Use a 500 V mega tester when measuring insulation Do not use a mega tester for low voltage circuits 1 Measure the insulation resistance over the poles If Then 1 MΩ Insulat...

Page 15: ...be lit For any other action it needs to be lit first The backlight is lit for 30 seconds when you press a button 1 Perform introductory steps Action 1 Open the liquid stop valve and gas stop valve by removing the cap and turning counterclockwise with a hex wrench until it stops 2 Close the service cover to prevent electric shocks 3 Turn ON power for at least 6 hours before starting operation to pr...

Page 16: ...case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires L4 The air inlet or air outlet is blocked U0 The stop valves are closed U2 There is a voltage imbalance There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring a...

Page 17: ...m distance between the unit and the edge of obstacle E in the direction of obstacle D HU Height of the unit HB HD Height of obstacles B and D 1 Seal the bottom of the installation frame to prevent discharged air from flowing back to the suction side through the bottom of the unit 2 Maximum two units can be installed Not allowed See figure 2 on the inside of the front cover 1 For better serviceabil...

Page 18: ...nd Legend Optional Optional Part n Part n Description Description A1P Printed circuit board main A2P Printed circuit board noise filter A3P Printed circuit board inverter A4P Printed circuit board fan A5P Printed circuit board demand C503 C506 C507 A3P Capacitor DS1 DS2 A1P DIP switch E1H Bottom plate heater E1HC Crankcase heater F1U A1P Fuse T 3 15 A 250 V F8U F9U Fuse F F101U A4P Fuse F101U F102...

Page 19: ......

Page 20: ...4P573384 1 2019 04 Copyright 2019 Daikin 4P573384 1 0000000S ...

Reviews: