Installation manual

5

(C) In case of multiple-row installation (for roof top use, etc.)

1.

In case of installing one unit per row.

2.

In case of installing multiple units (2 units or more) in lateral
connection per row.

Relation of dimensions of H, A and L are shown in the table below.

Refrigerant pipe size and allowable pipe 
length

Selection of piping material

Piping and other pressure containing parts shall comply with the
national and international codes and shall be suitable for
refrigerant, use phosphoric acid deoxidised seamless copper for
refrigerant.

Temper grade: use piping with temper grade in function of the
pipe diameter as listed in table below.

The pipe thickness of the refrigerant piping should comply with
relevant local and national regulations. The minimal pipe
thickness for R410A piping must be in accordance with the table
below.

O=Annealed
1/2H=Half hard

Only use annealed material for flare connections.

Allowable pipe length and height difference

See the table below concerning lengths and heights. Refer to
figure

2

.

Allowable pipe length

L

A

L

H

0<L

1/2H

150 (250)

1/2H<L

200 (300)

H<L

Installation impossible

Installation shall be done by a licensed refrigeration
technician, the choice of materials and installation shall
comply with the applicable national and international
codes. In Europe, EN378 is the applicable standard that
shall be used.

To persons in charge of piping work:

Be sure to open the stop valve after piping installing
and vacuming is complete. (Running the system with
the valve closed may break the compressor.)

It is forbidden to discharge refrigerant into the
atmosphere. Collect the refrigerant in accordance with
the freon collection and destruction law.

Do not use flux when brazing the refrigerant piping.
For brazing, use phosphor copper brazing filler metal
(BCuP) which does not require a flux.
(If a chlorine flux is used, the piping will corrode, and if
the flux contains fluoride, it will cause the coolant oil to
deteriorate, adversely affecting the coolant piping
system.

500

(1000)

100

(200)

1000

(2000)

50

(100)

1000

(1500)

400 (600)

2000

(3000)

A

H

L

Pipe Ø

Temper grade 

of piping material

Minimal thickness t (mm)

6.4 / 9.5 / 12.7

O

0.80

15.9

O

1.00

19.1

1/2H

Allowable pipe length

Model

71

100

125

140

Maximum total one-way piping length

(a)

(a) Parenthesized figure represents the equivalent length.

L1

50 m  (70 m)

75 m  (95 m)

Maximum height between indoor and outdoor

H1

30 m

Chargeless length

L1

30 m

Summary of Contents for SIESTA SERIES

Page 1: ...INSTALLATION MANUAL AZQS71B2V1B Split System air conditioners...

Page 2: ...e establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecid...

Page 3: ...0 Hz 220 240 V R410A 1 2 4 5 6 3 1 3 2 4 5 A B A E B C D H H1 L1 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L...

Page 4: ...ion work may result in accidents due to fall of equipment Make certain that all electrical work is carried out by qualified personnel according to the local laws and regulations and this installation...

Page 5: ...ge fluctuates a lot such as that in factories In vehicles or vessels Where acidic or alkaline vapour is present Provide a logbook In accordance with the relevant national and international codes it ma...

Page 6: ...unit the fan can start rotating very fast until it breaks Refer to the figures for installation of this unit in a place where the wind direction can be foreseen Turn the air outlet side toward the bu...

Page 7: ...mple if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain works properly Installation servicing space The numerical figures used in here r...

Page 8: ...ation impossible Installation shall be done by a licensed refrigeration technician the choice of materials and installation shall comply with the applicable national and international codes In Europe...

Page 9: ...surfaces to prevent rusting Preventing foreign objects from entering Plug the pipe through holes with putty or insulating material procured locally to stop up all gaps as shown in the figure Insects o...

Page 10: ...0 C and the humidity is higher than RH 80 then the thickness of the sealing materials should be at least 20 mm in order to avoid condensation on the surface of the sealing Be sure to insulate the liqu...

Page 11: ...2 1 Evacuate the pipes and check vacuum 1 No pressure increase for 1 minute 2 Break the vacuum with a minimum of 2 bar of nitrogen Never pressurize more than 4 0 MPa 3 Conduct leak test by applying so...

Page 12: ...l charging weight of the refrigerant after a leak etc The total charging amounts relate to the refrigerant piping length as in Maximum total one way piping length of the table in paragraph Allowable p...

Page 13: ...make contact with the pipes especially on high pressure side Secure the electrical wiring with clamping material as shown in the figure below so that it does not come in contact with the piping parti...

Page 14: ...on Do not connect wires of different gauge to the same power supply terminal Looseness in the connection may cause overheating When connecting wires of the same gauge connect them according to the fig...

Page 15: ...Check all functions according to the operation manual AZQS 71V1 100V1 125V1 140V1 Minimum circuit amps MCA a a Stated values are maximum values see electrical data of combination with indoor units fo...

Page 16: ...ws E3 E4 or L8 as an error code there is a possibility that either the stop valves are closed or that air inlet or air outlet are blocked If the error code U2 is displayed on the remote controller che...

Page 17: ...ischarge pipe for W1 models only R3T Thermistor suction pipe for V1 models only R4T Thermistor suction pipe for W1 models only R4T Thermistor coil for V1 models only R5T Thermistor power module for W1...

Page 18: ......

Page 19: ......

Page 20: ...3P327449 6E 2014 01 Copyright 2013 Daikin...

Reviews: