Installation manual

12

Specifications of standard wiring components

Equipment complying with EN/IEC 61000-3-12

(1)

.

Test operation

Pre-run checks

Be sure to perform a test run.

Be sure to fully open the liquid-side and gas-side stop valves. If
you operate the unit with stop valves closed, the compressor will
break down.

Be sure to execute the first test run of the installation in cooling
mode operation.

Never leave the unit unattended with an open front panel during
test run.

Test run

1

Be sure to turn power on at least 6 hours before starting
operation in order to protect the compressor.

2

Make sure the liquid and gas stop valves are open.

3

Be sure to close the frontside panel before operation, as not
doing so can cause electric shock.

4

Be sure to set the unit to cooling operation mode.

5

Press the inspection/test operation button of the remote
controller 4 times (2 times in case of a wireless remote
controller) to go into the test run mode.

6

Press the ON/OFF button within 10 seconds to start the test run
and check the operation status for about 6 minutes. The
refrigerant pressure may not rise immediately, even if the stop
valve is opened after an air purge is performed using a vacuum
pump. This is because the indoor unit refrigerant piping is closed
off with electric valves inside. This will not create any problems
during operation.

7

Push the air flow direction adjust button and check if the unit is
responding to the new air flow direction position.

8

Press the inspection/test operation button of the remote
controller 2 times to go into check mode and to make sure that
the malfunction code displays 

"

00

"

 (=normal). In case the

malfunction code does not display 

"

00

"

, refer to 

"Failure

diagnosis at the moment of first installation" on page 13

.

9

If the inspection/test operation button is pressed 4 times during a
test run, the unit returns to normal operation.

10

Check all functions according to the operation manual.

AZQS

71V1

100V1

125V1

140V1

Minimum circuit amps (MCA)

(a)

(a) Stated values are maximum values (see electrical data of combination with 

indoor units for exact values).

18.9

27.6

28.8

Recommended field fuse (A)

20

32

Wire type

(b)

(b) Only in protected pipes, use H07RN-F when protected pipes are not used.

H05VV-U3G

Size

Wiring size must comply with the applicable 

local and national code

Wire type of wiring between 
the units

H05VV-U4G2.5

NOTE

The earth leakage breaker must be a high-speed type
breaker of 30 mA (<0.1 s).

(1) European/International Technical Standard sets the limits for harmonic 

currents produced by equipment connected to public low-voltage systems 
with input current >16 A and 

75 A per phase.

WARNING

Live parts can be easily touched by accident.

Never leave the unit unattended during installation or
servicing when the service panel is removed.

NOTE

Note that during the first running period of the unit,
required power input may be higher. This phenomenon
originates from the compressor that requires a 50-hour
run-in period before reaching smooth operation and
stable power consumption.

Items to check

Electrical wiring
Inter-unit wiring
Ground wire

Is the wiring as mentioned on the wiring
diagram?
Make sure no wiring has been forgotten and that
there are no missing phases or reverse phases.

Is the unit properly grounded?

Is the wiring between units connected in series
correct?

Are any of the wiring attachment screws loose?

Is the insulation resistance at least 1 M

?

-

Use a 500 V mega-tester when measuring 
insulation.

-

Do not use a mega-tester for low-voltage 
circuits.

Refrigerant piping

Is the size of the piping appropriate?

Is the insulation material for the piping attached
securely?
Are both the liquid and gas pipes insulated?

Are the stop valves for both the liquid side and
the gas side open?

Extra refrigerant

Did you write down the extra refrigerant and the
refrigerant piping length?

 

Opening direction

A

Liquid side

B

Gas side

Remove the cap and turn 
counterclockwise with a 
hex wrench until it stops

A

B

Summary of Contents for SIESTA SERIES

Page 1: ...INSTALLATION MANUAL AZQS71B2V1B Split System air conditioners...

Page 2: ...e establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecid...

Page 3: ...0 Hz 220 240 V R410A 1 2 4 5 6 3 1 3 2 4 5 A B A E B C D H H1 L1 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L...

Page 4: ...ion work may result in accidents due to fall of equipment Make certain that all electrical work is carried out by qualified personnel according to the local laws and regulations and this installation...

Page 5: ...ge fluctuates a lot such as that in factories In vehicles or vessels Where acidic or alkaline vapour is present Provide a logbook In accordance with the relevant national and international codes it ma...

Page 6: ...unit the fan can start rotating very fast until it breaks Refer to the figures for installation of this unit in a place where the wind direction can be foreseen Turn the air outlet side toward the bu...

Page 7: ...mple if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain works properly Installation servicing space The numerical figures used in here r...

Page 8: ...ation impossible Installation shall be done by a licensed refrigeration technician the choice of materials and installation shall comply with the applicable national and international codes In Europe...

Page 9: ...surfaces to prevent rusting Preventing foreign objects from entering Plug the pipe through holes with putty or insulating material procured locally to stop up all gaps as shown in the figure Insects o...

Page 10: ...0 C and the humidity is higher than RH 80 then the thickness of the sealing materials should be at least 20 mm in order to avoid condensation on the surface of the sealing Be sure to insulate the liqu...

Page 11: ...2 1 Evacuate the pipes and check vacuum 1 No pressure increase for 1 minute 2 Break the vacuum with a minimum of 2 bar of nitrogen Never pressurize more than 4 0 MPa 3 Conduct leak test by applying so...

Page 12: ...l charging weight of the refrigerant after a leak etc The total charging amounts relate to the refrigerant piping length as in Maximum total one way piping length of the table in paragraph Allowable p...

Page 13: ...make contact with the pipes especially on high pressure side Secure the electrical wiring with clamping material as shown in the figure below so that it does not come in contact with the piping parti...

Page 14: ...on Do not connect wires of different gauge to the same power supply terminal Looseness in the connection may cause overheating When connecting wires of the same gauge connect them according to the fig...

Page 15: ...Check all functions according to the operation manual AZQS 71V1 100V1 125V1 140V1 Minimum circuit amps MCA a a Stated values are maximum values see electrical data of combination with indoor units fo...

Page 16: ...ws E3 E4 or L8 as an error code there is a possibility that either the stop valves are closed or that air inlet or air outlet are blocked If the error code U2 is displayed on the remote controller che...

Page 17: ...ischarge pipe for W1 models only R3T Thermistor suction pipe for V1 models only R4T Thermistor suction pipe for W1 models only R4T Thermistor coil for V1 models only R5T Thermistor power module for W1...

Page 18: ......

Page 19: ......

Page 20: ...3P327449 6E 2014 01 Copyright 2013 Daikin...

Reviews: