Specifications of standard wiring components

Only for AZQS71~140_V1: 
Equipment complying with EN/IEC 61000-3-12

(1)

.

T

EST

 

OPERATION

Pre-run checks

Be sure to perform a test run.

Be sure to fully open the liquid-side and gas-side stop valves. If
you operate the unit with stop valves closed, the compressor will
break down.

Be sure to execute the first test run of the installation in cooling
mode operation.

Never leave the unit unattended with an open front panel during
test run.

Test run

1

Be sure to turn power on at least 6 hours before starting
operation in order to protect the compressor.

2

Make sure the liquid and gas stop valves are open.

3

Be sure to close the frontside panel before operation, as not
doing so can cause electric shock.

4

Be sure to set the unit to cooling operation mode.

5

Press the inspection/test operation button of the remote
controller 4 times (2 times in case of a wireless remote
controller) to go into the test run mode.

6

Press the ON/OFF button within 10 seconds to start the test run
and check the operation status for about 6 minutes. The
refrigerant pressure may not rise immediately, even if the stop
valve is opened after an air purge is performed using a vacuum
pump. This is because the indoor unit refrigerant piping is closed
off with electric valves inside. This will not create any problems
during operation.

7

Push the air flow direction adjust button and check if the unit is
responding to the new air flow direction position.

8

Press the inspection/test operation button of the remote
controller 2 times to go into check mode and to make sure that
the malfunction code displays 

"

00

"

 (=normal). In case the

malfunction code does not display 

"

00

"

, refer to 

"Failure

diagnosis at the moment of first installation" on page 13

.

9

If the inspection/test operation button is pressed 4 times during a
test run, the unit returns to normal operation.

10

Check all functions according to the operation manual.

AZQS

71V1

100V1

125V1

140V1

100W1

125W1

140W1

Minimum circuit 
amps (MCA)

(a)

(a) Stated values are maximum values (see electrical data of combination with indoor 

units for exact values).

18.9

27.6

28.8

17.1

18.3

Recommended 
field fuse (A)

20

32

20

Wire type

(b)

(b) Only in protected pipes, use H07RN-F when protected pipes are not used.

H05VV-U3G

H05VV-U5G

Size

Wiring size must comply with the applicable local and 

national code

Wire type of 
wiring between 
the units

H05VV-U4G2.5

NOTE

The earth leakage breaker must be a high-speed type
breaker of 30 mA (<0.1 s).

(1) European/International Technical Standard setting the limits for harmonic 

currents produced by equipment connected to public low-voltage systems 
with input current >16 A and 

75 A per phase.

WARNING

Live parts can be easily touched by accident.

Never leave the unit unattended during installation or
servicing when the service panel is removed.

NOTE

Note that during the first running period of the unit,
required power input may be higher. This phenomenon
originates from the compressor that requires a 50-hour
run-in period before reaching smooth operation and
stable power consumption.

Items to check

Electrical wiring
Inter-unit wiring
Ground wire

Is the wiring as mentioned on the wiring
diagram?
Make sure no wiring has been forgotten and that
there are no missing phases or reverse phases.

Is the unit properly grounded?

Is the wiring between units connected in series
correct?

Are any of the wiring attachment screws loose?

Is the insulation resistance at least 1 M

Ω

?

-

Use a 500 V mega-tester when measuring 
insulation.

-

Do not use a mega-tester for low-voltage 
circuits.

Refrigerant piping

Is the size of the piping appropriate?

Is the insulation material for the piping attached
securely?
Are both the liquid and gas pipes insulated?

Are the stop valves for both the liquid side and
the gas side open?

Extra refrigerant

Did you write down the extra refrigerant and the
refrigerant piping length?

 

Opening direction

A

Liquid side

B

Gas side

Remove the cap and turn 
counterclockwise with a 
hex wrench until it stops

A

B

Summary of Contents for Siesta AZQS71B2V1B

Page 1: ...INSTALLATION MANUAL AZQS71B2V1B AZQS100A7V1B AZQS125A7V1B AZQS140A7V1B AZQS100A7W1B AZQS125A7W1B AZQS140A7W1B Split System air conditioners...

Page 2: ...0 Hz 220 240 V R410A 1 2 4 5 6 3 1 3 2 4 5 A B A E B C D H H1 L1 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L...

Page 3: ...como se establece en A y es valorado positivamente por B de acuerdo con el Certi cado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certi cato C 07 A B C 08 Nota tal como estabel...

Page 4: ...ositivamente da B secondo il Certi cato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certi cado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet...

Page 5: ...lation work may result in accidents due to fall of equipment Make certain that all electrical work is carried out by quali ed personnel according to the local laws and regulations and this installatio...

Page 6: ...e uctuates a lot such as that in factories In vehicles or vessels Where acidic or alkaline vapour is present Provide a logbook In accordance with the relevant national and international codes it may b...

Page 7: ...he unit the fan can start rotating very fast until it breaks Refer to the gures for installation of this unit in a place where the wind direction can be foreseen Turn the air outlet side toward the bu...

Page 8: ...r example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain works properly INSTALLATION SERVICING SPACE The numerical gures used in her...

Page 9: ...stallation impossible Installation shall be done by a licensed refrigeration technician the choice of materials and installation shall comply with the applicable national and international codes In Eu...

Page 10: ...end surfaces to prevent rusting Preventing foreign objects from entering Plug the pipe through holes with putty or insulating material procured locally to stop up all gaps as shown in the gure Insects...

Page 11: ...an 30 C and the humidity is higher than RH 80 then the thickness of the sealing materials should be at least 20 mm in order to avoid condensation on the surface of the sealing Be sure to insulate the...

Page 12: ...Evacuate the pipes and check vacuum 1 No pressure increase for 1 minute 2 Break the vacuum with a minimum of 2 bar of nitrogen Never pressurize more than 4 0 MPa 3 Conduct leak test by applying soap w...

Page 13: ...Maximum total one way piping length of the table in paragraph Allowable pipe length and height difference on page 5 Table 2 Total charging amount unit kg NOTE National implementation of EU regulation...

Page 14: ...e terminal connectors When installing the earth leakage breaker make sure that it is compatible with the inverter resistant to high frequency electrical noise to avoid unnecessary opening of the earth...

Page 15: ...n Do not connect wires of different gauge to the same power supply terminal Looseness in the connection may cause overheating When connecting wires of the same gauge connect them according to the belo...

Page 16: ...nctions according to the operation manual AZQS 71V1 100V1 125V1 140V1 100W1 125W1 140W1 Minimum circuit amps MCA a a Stated values are maximum values see electrical data of combination with indoor uni...

Page 17: ...4 or L8 as an error code there is a possibility that either the stop valves are closed or that air inlet or air outlet are blocked If the error code U2 is displayed on the remote controller check for...

Page 18: ...discharge pipe for W1 models only R3T Thermistor suction pipe for V1 models only R4T Thermistor suction pipe for W1 models only R4T Thermistor coil for V1 models only R5T Thermistor power module for...

Page 19: ......

Page 20: ...3P327449 6C...

Reviews: