7 Commissioning
Installation and operation manual
30
SERHQ020~0 SEHVX20~64BAW
Split packaged air-cooled water chiller
4P508019-1C – 2018.04
A B C
A B C
a
DS1
1 2 3 4
OFF
ON
O
U
T
I
N
a
Cool/heat selector
1
Press BS5 for 5 seconds to re-initialise communication of the
unit.
▪ Cooling: voltage free contact between terminals A and C is
open
▪ Heating: voltage free contact between terminals A and C is
closed
EB0568(A)
R4 C2 R2
R1 C1 R3
X1M
PHC2
PHC1
X1A
1
A B C
INFORMATION
Thermostat input has priority over leaving water
temperature setpoint.
It is possible that the leaving water temperature becomes
lower than the setpoint if the unit is controlled by room
temperature.
7
Commissioning
After installation and once the field settings are defined, the installer
is obliged to verify correct operation. Therefore a test run MUST be
performed according to the procedures described below.
7.1
Precautions when commissioning
CAUTION
Do NOT perform the test operation while working on
the indoor units.
When performing the test operation, NOT only the outdoor
unit, but the connected indoor unit will operate as well.
Working on an indoor unit while performing a test operation
is dangerous.
NOTICE
Be sure to turn on the power 6 hours before operation in
order to have power running to the crankcase heater and
to protect the compressor.
7.2
Checklist before commissioning
the outdoor unit
After the installation of the unit, first check the following items. Once
all below checks are fulfilled, the unit MUST be closed, ONLY then
can the unit be powered up.
You read the complete installation and operation
instructions, as described in the
installer and user
reference guide
.
Installation
Check that the unit is properly installed, to avoid abnormal
noises and vibrations when starting up the unit.
Field wiring
Be sure that the field wiring has been carried out
according to the instructions described in the chapter
"5.8 Connecting the electrical wiring" on page 18
,
according to the wiring diagrams and according to the
applicable legislation.
Power supply voltage
Check the power supply voltage on the local supply panel.
The voltage MUST correspond to the voltage on the
identification label of the unit.
Earth wiring
Be sure that the earth wires have been connected
properly and that the earth terminals are tightened.
Insulation test of the main power circuit
Using a megatester for 500 V, check that the insulation
resistance of 2 MΩ or more is attained by applying a
voltage of 500 V DC between power terminals and earth.
NEVER use the megatester for the transmission wiring.
Fuses, circuit breakers, or protection devices
Check that the fuses, circuit breakers, or the locally
installed protection devices are of the size and type
specified
in
the
chapter
. Be sure that neither a fuse nor a
protection device has been bypassed.
Internal wiring
Visually check the electrical component box and the
inside of the unit on loose connections or damaged
electrical components.
Pipe size and pipe insulation
Be sure that correct pipe sizes are installed and that the
insulation work is properly executed.
Damaged equipment
Check the inside of the unit on damaged components or
squeezed pipes.
Brazing
Take care not to damage the piping insulation when
brazing field piping.
Installation date and field setting
Be sure to keep record of the installation date on the
sticker on the rear of the upper front panel according to
EN60335‑2‑40 and keep record of the contents of the field
setting(s).
Switches
Make sure that switches are set according to your
application needs before turning the power supply on.
Power supply wiring and transmission wiring
Use a designated power supply and transmission wiring
and make sure that it has been carried out according to
the instructions described in this manual, according to the
wiring diagrams and according to local and national
regulations.
Additional refrigerant charge
The amount of refrigerant to be added to the unit shall be
written on the included "Added refrigerant" plate and
attached to the rear side of the front cover.
Summary of Contents for SEHVX20BAW
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ...4P508019 1C 2018 04 Copyright 2018 Daikin 4P508019 1 C 0000000...