![Daikin SEHVX-BAW Installer And User Manual Download Page 35](http://html.mh-extra.com/html/daikin/sehvx-baw/sehvx-baw_installer-and-user-manual_501725035.webp)
7 Configuration
Installer and user reference guide
35
SERHQ020~0 SEHVX20~64BAW
Split packaged air-cooled water chiller
4P508020-1A – 2018.01
7
Configuration
7.1
Overview: Configuration
This chapter describes what you have to do and know to configure
the system after it is installed.
It contains information about:
▪ Making field settings
▪ Using the leak detection function
▪ Switching between cooling and heating
INFORMATION
It is important that all information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.
DANGER: RISK OF ELECTROCUTION
7.2
Making field settings
7.2.1
About making field settings
INFORMATION
The LEDs and buttons are located in the outdoor unit.
If required, carry out field settings according to the following
instructions. Refer to the service manual for more details.
Pushbuttons and DIP switches
Item
Description
Pushbuttons
By operating the pushbuttons it is possible to:
▪ Change the mode.
▪ Perform field settings (demand operation,
low noise, etc).
DIP switches
▪ DS1 (1): COOL/HEAT selector
▪ DS1 (2~4): NOT USED. DO NOT CHANGE
THE FACTORY SETTING.
▪ DS2 (1~4): NOT USED. DO NOT CHANGE
THE FACTORY SETTING.
▪ DS3 (1+2): NOT USED. DO NOT CHANGE
THE FACTORY SETTING.
Mode 1 and 2
Mode
Description
Mode 1
(monitoring
settings)
Mode 1 can be used to monitor the current
situation of the outdoor unit. Some field setting
contents can be monitored as well.
Mode 2
(field settings)
Mode 2 is used to change the field settings of
the system. Consulting the current field setting
value and changing the current field setting
value is possible.
In general, normal operation can be resumed
without special intervention after changing field
settings.
Some field settings are used for special
operation (e.g., 1 time operation, recovery/
vacuuming setting, manual adding refrigerant
setting, etc.). In such a case, it is required to
abort the special operation before normal
operation can restart. It will be indicated in
below explanations.
To continue the configuration of the system, it is required to give
some input to the PCB of the unit. This chapter will describe how
manual input is possible by operating the pushbuttons/DIP switches
on the PCB and reading the feedback from the LEDs.
INFORMATION
If you get confused in the middle of the process, push BS1.
Then it returns to setting mode 1 (H1P is off).
7.2.2
Field setting components
The components to make field settings are as follows:
BS2
SET
BS1
MODE
BS3
RETURN
BS4
TEST
BS5
RESET
H7P
MODE
TEST:
L.N.O.P. DEMAND
C/H SELECT
HWL:
IND MASTER SLAVE
MULTI
H1P
H2P
H3P
H4P
H5P
H6P
H8P
H1P~H8P
LEDs
BS1~BS5
Pushbuttons
DS1~DS3
DIP switches
ON (
) OFF ( ) Flashing (
)
Pushbuttons
Use the pushbuttons to make the field settings.
BS1
MODE: For changing the set mode
BS2
SET: For field setting
BS3
RETURN: For field setting
BS4
TEST: For test operation
BS5
RESET: For resetting the address when the wiring is
changed or when an additional indoor unit is installed
LEDs
The LEDs give feedback about the field settings, which are defined
as [Mode-Setting]=Value.
H1P
Shows the mode
H2P~H7P
Shows the settings and values, represented in binary code
H8P
NOT used for field settings, but used during initialisation
Example:
H1P H2P H3P H4P H5P H6P H7P
-
+
+
+
+
+
[
H1P
32 16
8
4
2
1]
Description
(H1P OFF)
Default situation
(H1P flashing)
Mode 1
(H1P ON)
Mode 2
+
+
+
+
+
0
0
8
0
0
0
(H2P~H7P = binary 8)
Setting 8
(in mode 2)
+
+
+
+
+
0
0
0
4
0
0
(H2P~H7P = binary 4)
Value 4
(in mode 2)
7.2.3
To access the field setting components
Remove the inspection cover to carry out field settings.
b
a
a
Inspection cover
b
Switch box cover
You can see the 5 pushbuttons, 8 LEDs and 3 DIP switches.