6 Installation
Installer and user reference guide
34
SERHQ020~0 SEHVX20~64BAW
Split packaged air-cooled water chiller
4P508020-1A – 2018.01
▪ When passing electrical wiring through the knockout holes.
prevent damage to the wires by wrapping the wiring with
protective tape, putting the wires through field supplied protective
wire conduits at that location, or install suitable field supplied wire
nipples or rubber bushings into the knockout holes.
▪ When you do not use a wire conduit, protect the wires with vinyl
tubes to prevent the edge of the knockout hole from cutting the
wires.
b
c
a
a
Knockout hole
b
Burr
c
If there are any possibilities that small animals enter the
system through the knockout holes, plug the holes with
packing materials (to be prepared on-site)
6.9.9
To install the user interface
The unit comes with a user interface offering a user-friendly way to
set up, use and maintain the unit. Before operating the user
interface, follow this installation procedure.
Wire specification
Value
Type
2 wire
Section
0.75~1.25 mm
2
Maximum length
500 m
NOTICE
The wiring for connection is NOT included.
NOTICE
The user interface MUST be mounted indoors.
1
Insert a slotted screwdriver into the slots in the rear part of the
user interface, and remove the front part of the user interface.
2
Fasten the user interface on a flat surface.
NOTICE
Be careful NOT to distort the shape of the lower part of the
user interface by overtightening the mounting screws.
3
Connect the terminals of the user interface and the terminals
inside the unit (P1 to P1, P2 to P2) as shown in the figure.
P1
P2
a
a
f
b
c
d
e
P1
P2
P2
P1
P2
P1
a
Unit
b
Rear part of the user interface
c
Front part of the user interface
d
Wired from the rear
e
Wired from the top
f
Use nippers to notch the part for the wiring to pass through
NOTICE
▪ When wiring, run the wiring away from the power
supply wiring in order to avoid receiving electric noise
(external noise).
▪ Peel the shield for the part that has to pass through the
inside of the user interface case (L).
L
4
Reattach the upper part of the user interface, starting with the
clips at the bottom.
1
CAUTION
Do NOT pinch the wiring when attaching.
If, in addition to the standard user interface, an optional user
interface (EKRUAHTB) is installed as well:
5
Connect the electrical wires of both user interfaces as
described.
6
Select a master and a slave user interface using the SS1
selector switch.
S
S
M
PCB
SS1
S
Slave
M
Master
INFORMATION
Only the user interface set as master can be used as a
room thermostat.
6.9.10
To install optional equipment
For the installation of optional equipment, refer to the installation
manual which is delivered with the optional equipment or the
addenda delivered with this unit.