ESIE16-03B
|
Part 5. Appendix
5.1. Field setting
SA R32 Sky-Air RZAG-L
Page 106
22/08/16
|
Version 1.1
5.1.3. Remote controller
Mode No.
First Code No.
Description
Second Code No.
Details
01
02
03
04
05
16 (26)
0
Night time low
noise operation
Disabled (Factory
setting)
Automatic low
noise activation
Capacity preced-
ing setting (when
using KRP58
option)
Automatic low
noise + capacity
preceding
—
Refer to
"Quiet
(Low Noise) Oper-
ation" on
page 108
.
1
Automatic low
noise start and
stop time
—
—
22h00 ~ 06h00
22h00 ~ 08h00
(Factory)
20h00 ~ 08h00
Refer to
"Quiet
(Low Noise) Oper-
ation" on
page 108
.
2
EDP room setting
Disabled (Factory
setting)
—
EDP room setting
EDP room setting
+ no freeze up
—
Refer to
"Setting
for Low Humidity
Application" on
page 109
.
3
Defrost starting
setting
Standard (Factory
setting)
Defrost slow start-
ing setting
Defrost quick
starting setting
—
—
Refer to
"Defrost
Operation" on
page 112
.
7
Slow start for EDP
applications
Normal start
Slow start
—
—
—