ESIE16-03B
|
Part 5. Appendix
5.1. Field setting
SA R32 Sky-Air RZAG-L
22/08/16
|
Version 1.1
Page 101
5.1.1.2. Retrieve field settings BRC7
Setting
To set the field settings, you have to change:
• “Mode
No.”
• “First
code
No.”
•
“Second code No.”.
To change the field settings, proceed as follows:
1. Hold down the INSPECTION/TEST button for at least 4 s during normal mode to enter the “Field setting mode”.
2. Press the MODE button to select the desired “Mode No.”.
3. Press the UP button to select the “First code No.”.
4. Press the DOWN button to select the “Second code No.”
5. Press the RESERVE button to set the present settings.
6. Press the INSPECTION/TEST button to return to the “Normal mode”.
1. Mode No.
4. First code No.
7. DOWN button
2. Field setting mode
5. Second code No.
8. MODE button
3. RESERVE button
6. UP button
9. INSPECTION/TEST button