• Outdoor Unit • Outdoor units optimized for seasonal efficiency • RZQSG-LY1

1

2

• Split - Sky Air • Outdoor Unit

6

2

Specifications

 Notes

 (1) PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
 (2) See separate drawing for electrical data
 (3) Equipment complying with EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-
voltage system with input current \> 16A and 

 75A per phase

 (4) Short-circuit power
 (5) See separate drawings for electrical data
 (6) European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A 
and 

 75A per phase.

 (7) Related to 3D076918

Refrigerant oil

Type

FVC50K

Charged volume

l

0.9

1.35

Piping connections

Liquid

Quantity

1

Type

Flare connection

OD

mm

9.52

Gas

Quantity

1

Type

Flare connection

OD

mm

15.9

Drain

Quantity

5

Type

Hole

ID

mm

-

OD

mm

26

Piping length

OU - IU Min.

m

5

Max.

m

50

System Equiva-

lent

m

70

Charge-
less

m

30

Additional refrigerant charge

kg/m

See installation manual 4P302555-1

Level difference

IU - OU Max.

m

30.0

IU - IU

Max.

m

0.5

Heat insulation

Both liquid and gas pipes

Defrost method

Pressure equalising

Defrost control

Sensor for outdoor heat exchanger temperature

Safety devices

Item

01

High pressure switch

02

Fan motor thermal protection

03

Fuse

2-3 Electrical Specifications

RZQSG100LY1

RZQSG125LY1

RZQSG140LY1

Power supply

Name

Y1

Phase

3N~

Frequency

Hz

50

Voltage

V

380-415

Voltage range

Min.

%

10

Max.

%

10

Current

Zmax

List

Complies to EN61000-3-11

Recommended fuses

A

20

25

Wiring connections

For power supply

Remark

See installation manual 4P302555-1

For connection with 
indoor

Remark

See installation manual 4P302555-1

Power supply intake

Outdoor unit only

2-2 Technical Specifications

RZQSG100LY1

RZQSG125LY1

RZQSG140LY1

Summary of Contents for RZQSG125LY1

Page 1: ...RZQSG LY1 Technical Data E E D E N 1 2 1 0 0 O u t d o o r u n i t s o p t i m i z e d f o r s e a s o n a l e f f i c i e n c y Air Conditioners...

Page 2: ...bles 11 Heating Capacity Tables 14 Capacity Correction Factor 17 7 Dimensional drawings 18 Dimensional Drawings 18 8 Centre of gravity 19 Centre of Gravity 19 9 Piping diagrams 20 Piping Diagrams 20 P...

Page 3: ...ives an indication on how efficient an air conditioner operates over an entire heating or cooling season Re use of existing R 22 or R 407C technology The use of inverter type outdoor units results in...

Page 4: ...4 15 5 4 Power input Cooling Nom kW 2 88 3 74 4 45 Heating Nom kW 3 05 3 96 4 54 EER 3 30 3 21 3 01 COP 3 54 3 41 SEER 5 11 6 SCOP 3 80 6 3 81 6 Annual energy consumption kWh 1 440 1 870 2 225 Energy...

Page 5: ...Heating capacity Nom kW 10 8 4 13 5 4 15 5 4 Power input Cooling Nom kW 2 87 3 74 4 44 Heating Nom kW 2 96 3 85 4 54 EER 3 31 3 21 3 02 COP 3 65 3 51 3 41 SEER 5 11 6 4 35 6 SCOP 3 81 6 Annual energy...

Page 6: ...Anti corrosion treatment PE Fan Type Propeller fan Discharge direction Horizontal Quantity 1 2 Air flow rate Cooling Nom m min 76 77 83 Super low m min cfm Heating Nom m min 83 62 Super low m min cfm...

Page 7: ...ctions Liquid Quantity 1 Type Flare connection OD mm 9 52 Gas Quantity 1 Type Flare connection OD mm 15 9 Drain Quantity 5 Type Hole ID mm OD mm 26 Piping length OU IU Min m 5 Max m 50 System Equiva l...

Page 8: ...3 1 3 Split Sky Air Outdoor Unit 7 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 3 Electrical data 3 1 Electrical Data...

Page 9: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 3 Split Sky Air Outdoor Unit 8 3 Electrical data 3 1 Electrical Data...

Page 10: ...3 1 4 Split Sky Air Outdoor Unit 9 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 4 Options 4 1 Options...

Page 11: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 5 Split Sky Air Outdoor Unit 10 5 Combination table 5 1 Combination Table...

Page 12: ...3 1 6 Split Sky Air Outdoor Unit 11 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 6 Capacity tables 6 1 Cooling Capacity Tables...

Page 13: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 6 Split Sky Air Outdoor Unit 12 6 Capacity tables 6 1 Cooling Capacity Tables...

Page 14: ...3 1 6 Split Sky Air Outdoor Unit 13 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 6 Capacity tables 6 1 Cooling Capacity Tables...

Page 15: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 6 Split Sky Air Outdoor Unit 14 6 Capacity tables 6 2 Heating Capacity Tables...

Page 16: ...3 1 6 Split Sky Air Outdoor Unit 15 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 6 Capacity tables 6 2 Heating Capacity Tables...

Page 17: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 6 Split Sky Air Outdoor Unit 16 6 Capacity tables 6 2 Heating Capacity Tables...

Page 18: ...3 1 6 Split Sky Air Outdoor Unit 17 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 6 Capacity tables 6 3 Capacity Correction Factor...

Page 19: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 7 Split Sky Air Outdoor Unit 18 7 Dimensional drawings 7 1 Dimensional Drawings...

Page 20: ...3 1 8 Split Sky Air Outdoor Unit 19 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 8 Centre of gravity 8 1 Centre of Gravity...

Page 21: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 9 Split Sky Air Outdoor Unit 20 9 Piping diagrams 9 1 Piping Diagrams...

Page 22: ...3 1 9 Split Sky Air Outdoor Unit 21 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 9 Piping diagrams 9 2 Piping Diagram Twin Application...

Page 23: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 9 Split Sky Air Outdoor Unit 22 9 Piping diagrams 9 3 Piping Diagram Triple Application...

Page 24: ...3 1 9 Split Sky Air Outdoor Unit 23 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 9 Piping diagrams 9 4 Piping Diagram Double Twin Application...

Page 25: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 10 Split Sky Air Outdoor Unit 24 10 Wiring diagrams 10 1 Wiring Diagrams Three Phase...

Page 26: ...3 1 11 Split Sky Air Outdoor Unit 25 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 11 Sound data 11 1 Sound Power Spectrum...

Page 27: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 11 Split Sky Air Outdoor Unit 26 11 Sound data 11 2 Sound Pressure Spectrum Cooling...

Page 28: ...3 1 11 Split Sky Air Outdoor Unit 27 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 11 Sound data 11 3 Sound Pressure Spectrum Heating...

Page 29: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 11 Split Sky Air Outdoor Unit 28 11 Sound data 11 4 Sound Pressure Spectrum Quiet Mode...

Page 30: ...3 1 12 Split Sky Air Outdoor Unit 29 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 12 Installation 12 1 Installation Method...

Page 31: ...Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 1 12 Split Sky Air Outdoor Unit 30 12 Installation 12 1 Installation Method...

Page 32: ...3 1 13 Split Sky Air Outdoor Unit 31 Outdoor Unit Outdoor units optimized for seasonal efficiency RZQSG LY1 13 Operation range 13 1 Operation Range...

Page 33: ...ted by Daikin Europe N V Daikin s unique position as a manufacturer of air conditioning equipment compressors and refrigerants has led to its close involvement in environmental issues For several year...

Reviews: