Installation manual

1

RZQS71~125B7V3

Split System air conditioners

4PW32097-1

C

ONTENTS

Page

Safety considerations ........................................................................ 1

Before installation.............................................................................. 2

Selecting installation site................................................................... 3

Precautions on installation ................................................................ 4

Installation servicing space ............................................................... 4

Refrigerant pipe size and allowable pipe length ................................ 5

Precautions on refrigerant piping ...................................................... 6

Refrigerant piping.............................................................................. 6

Evacuating......................................................................................... 8

Charging refrigerant .......................................................................... 9

Electrical wiring work....................................................................... 10

Test operation.................................................................................. 12

Disposal requirements .................................................................... 13

Wiring diagram ................................................................................ 14

S

AFETY

 

CONSIDERATIONS

The precautions listed here are divided into the following two types.
Both cover very important topics, so be sure to follow them carefully.

RZQS71B7V3
RZQS100B7V3
RZQS125B7V3

Split System air conditioners

Installation manual

READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.

IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.

IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.

WARNING

If the warning is not observed, it may cause 
serious casualties.

CAUTION

If the caution is not observed, it may cause 
injury or damage to the equipment.

WARNING

For year round cooling applications with low indoor
humidity conditions, such as Electronic Data
Processing rooms, contact your dealer or see the
engineering databook or the service manual.

For use of air-conditioning units in applications with
temperature alarm settings it is advised to foresee a
delay of 10 minutes for signalling the alarm in case
the alarm temperature is exceeded. The air-
conditioning unit may stop for several minutes during
normal operation for “defrosting of the indoor unit” or
when in “thermostat-stop” operation.

WARNING

Ask your dealer or qualified personnel to carry out
installation work.  Do not install the machine by
yourself.
Improper installation may result in water leakage,
electric shocks or fire.

Perform installation work in accordance with this
installation manual.
Improper installation may lead to water leakage,
electric shocks or fire.

When a unit is installed in a small room, it is
necessary to take measures so that the leaked
refrigerant amount does not exceed the limit even if it
leaks. As for the measures to prevent the leak from
not exceeding the limit, please consult with your
distributor.
If the leaked amount exceeds the limit, it may cause
an oxygen deficiency accident.

Be sure to use only the specified accessories and
parts for installation work.
Failure to use the specified parts may result in water
leakage, electric shocks, fire, or the unit falling.

Install the air conditioner on a foundation that can
withstand its weight.
Insufficient strength may result in the fall of equipment
and causing injury.

Carry out the specified installation work in consideration
of strong winds, typhoons, or earthquakes.
Improper installation work may result in accidents due
to fall of equipment.

Make certain that all electrical work is carried out by
qualified personnel according to the local laws and
regulations and this installation manual, using a
separate circuit.
Insufficient capacity of the power supply circuit or
improper electrical construction may lead to electric
shocks or fire.

Make sure that all wiring is secure, using the specified
wires and ensuring that external forces do not act on
the terminal connections or wires.
Incomplete connection or fixing may cause a fire.

When wiring between the indoor and outdoor units,
and wiring the power supply, form the wires so that
the frontside panel can be securely fastened.
If the frontside panel is not in place, overheat of the
terminals, electric shocks or a fire may be caused.

If refrigerant gas leaks during installation work,
ventilate the area immediately.
Toxic gas may be produced if refrigerant gas comes
into contact with fire.

After completing the installation work, check to make
sure that there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks
into the room and comes into contact with a source of
fire, such as a fan heater, stove or cooker.

Before touching electric terminal parts, turn off power
switch.

Summary of Contents for RZQS71B7V3

Page 1: ...INSTALLATION MANUAL RZQS71B7V3 RZQS100B7V3 RZQS125B7V3 Split System air conditioners...

Page 2: ...7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B...

Page 3: ...u condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on va...

Page 4: ...on may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage electric shocks or fire Whe...

Page 5: ...rding to national regulations Do not connect the earth wire to gas or water pipes lightning conductor or telephone earth wire Incomplete grounding may cause electric shocks Gas pipe Ignition or explos...

Page 6: ...ration of the operational capacity Frequent frost acceleration in heating operation Disruption of operation due to rise of high pressure When a strong wind blows continuously on the face of the unit t...

Page 7: ...pe disposal If drain pipe disposal from the outdoor unit causes trouble for example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain w...

Page 8: ...e sizes must have the same size as the connected indoor units pipe sizes Branch see marking on figures 3 4 and 5 Selection of branch pipe L A L H 0 L 1 2H 150 250 1 2H L 200 300 H L Installation impos...

Page 9: ...nch pipe to the indoor unit should be as short as possible Try to keep lengths of both branch pipes to the indoor unit equal REFRIGERANT PIPING Field pipes can be installed in four directions Figure F...

Page 10: ...r to the figure Take care not to damage it After operating the valve be sure to tighten the valve cover properly Check for refrigerant leakage after tightening the cap Cautions for handling service po...

Page 11: ...f oxidised film on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preventing normal operation When brazing pipes however do not use oxidation preven...

Page 12: ...0 m G1 G2 30 m Based on this decide R2 in the table R1 0 3 Total additional charge amount R R1 R2 kg Table 2 Length unit m additional charging of refrigerant unit kg Example 1 1 G1 L1 35 m G2 L2 L3 7...

Page 13: ...e bundled cables into a unit Fix cables so that cables do not make contact with the pipes especially on high pressure side Secure the electrical wiring with clamping material as shown in the figure be...

Page 14: ...wiring works Form the wires and fix the cover firmly so that the cover may be fit in properly Precautions on wiring of power supply and inter unit wiring Use a round crimp style terminal for connectio...

Page 15: ...pt displaying the heating symbol all the time and the unit will switch to heating operation automatically after elapse of that time 2 In case you cannot operate the unit in test run mode for any unusu...

Page 16: ...r code U4 or UF is displayed on the remote controller check the inter unit branch wiring connection The reversed phase protection detector of this product only works during the initialisation stage af...

Page 17: ...r air R2T Thermistor coil R3T Thermistor discharge pipe R4T Thermistor suction pipe R5T Thermistor power module RC Signal receiver circuit S1NPL Pressure sensor low S1PH Pressure switch high S1PL Pres...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW32097 1...