RZQS71~125B7V3
Split System air conditioners
4PW32097-1
Installation manual
2
B
EFORE
INSTALLATION
Precautions for R410A
■
The refrigerant requires strict cautions for keeping the system
clean, dry and tight.
-
Clean and dry
Foreign materials (including mineral oils or moisture) should be
prevented from getting mixed into the system.
-
Tight
Read
"Precautions on refrigerant piping" on page 6
follow these procedures correctly.
■
Since R410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state. (If the refrigerant
is in state of gas, its composition changes and the system will
not work properly).
■
The connected indoor units must be indoor units designed
exclusively for R410A.
Installation
■
For installation of the indoor unit(s), refer to the indoor unit
installation manual.
■
Illustrations show class 125 outdoor unit type. Other types also
follow this installation manual.
■
This outdoor unit requires the pipe branching kit (optional) when
used as the outdoor unit for the simultaneous operation system.
Refer to catalogues for details.
■
Never operate the unit without the thermistor (R3T, R4T),
burning of the compressor may result.
■
Be sure to confirm the model name and the serial no. of the
outer (front) plates when attaching/detaching the plates to avoid
mistakes.
■
When closing the service panels, take care that the tightening
torque does not exceed 4.1 N•m.
WARNING
■
Live parts can be easily touched by accident.
Never leave the unit unattended during installation or
servicing when the service panel is removed.
■
When planning to relocate former installed units, you
must first recover the refrigerant after the pumping-
down operation. Refer to chapter
pumping-down operation" on page 10
■
Never directly touch any accidental leaking
refrigerant. This could result in severe wounds caused
by frostbite.
CAUTION
■
Ground the air conditioner.
Grounding resistance should be according to national
regulations
Do not connect the earth wire to gas or
water pipes, lightning conductor or
telephone earth wire.
Incomplete grounding may cause electric
shocks.
■
Gas pipe.
Ignition or explosion may occur if the gas leaks.
■
Water pipe.
Hard vinyl tubes are not effective grounds.
■
Lightning conductor or telephone ground wire.
Electric potential may rise abnormally if struck by a
lightning bolt.
■
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may cause
electric shocks and fire.
■
Install drain piping according to this installation
manual to ensure good drainage, and insulate the
pipe to prevent condensation.
Improper drain piping may cause water leakage, and
make the furnitures get wet.
■
Install the indoor and outdoor units, power wire and
connecting wire at least 1 meter away from televisions
or radios to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter
may not be sufficient to eliminate the noise.)
■
Do not rinse the outdoor unit. This may cause electric
shocks or fire.
CAUTION
■
Do not install the air conditioner in places such as the
following:
■
Where there is mist of mineral oil, oil spray or
vapor for example a kitchen.
Plastic parts may deteriorate, and cause them to
fall out or water to leak.
■
Where corrosive gas, such as sulfurous acid gas,
is produced.
Corrosion of copper pipes or soldered parts may
cause the refrigerant to leak.
■
Where there is machinery which emits
electromagnetic waves.
Electromagnetic waves may disturb the control
system, and cause malfunction of the equipment.
■
Where flammable gases may leak, where carbon
fiber or ignitable dust is suspended in the air or
where volatile flammables, such as thinner or
gasoline, are handled.
Such gases may cause a fire.
■
Where the air contains high levels of salt such as
that near the ocean.
■
Where voltage fluctuates a lot, such as that in
factories.
■
In vehicles or vessels.
■
Where acidic or alkaline vapour is present.
Since maximum working pressure is 4.0 MPa or 40 bar,
pipes of larger wall thickness may be required. Refer to
paragraph