4 Installation

Installation manual

7

RZQG7 RZQG71~12 RZQG140L7Y1L
Split system air conditioners
4P473073-1A – 2019.04

NOTICE

Make  sure  to  open  the  stop  valves  after  installing  the
refrigerant  piping  and  performing  vacuum  drying.  Running
the  system  with  the  stop  valves  closed  may  break  the
compressor.

4.4

Charging refrigerant

4.4.1

To determine the additional refrigerant
amount

To determine if adding additional refrigerant is necessary

If

Then

L1 ≤ chargeless length

L1 (m)

Chargeless length=

▪ 10 m (size‑down)

▪ 30 m (standard)

▪ 15 m (size‑up)

You do not have to add
additional refrigerant.

L1 > chargeless length

You must add additional
refrigerant.

For future servicing, encircle the
selected amount in the tables
below.

INFORMATION

Piping length is the largest one-way length of liquid piping.

To determine the additional refrigerant amount (R in kg)

L1 (m)

L1 (standard): 30~40 m 40~50 m 50~60 m

(a)

60~75 m

(a)

L1 (size-up): 15~20 m 20~25 m 25~30 m

(a)

30~35 m

(a)

R:

0.5 kg

1.0 kg

1.5 kg

2.0 kg

(a)

Only for RZQG100~140.

4.4.2

To determine the complete recharge
amount

When  piping  length  is  <5  m,  a  complete  recharge  of  the  unit  is
required.

To determine the complete recharge amount (kg) (in case of
standard liquid pipe size)

Model

L1 (m)

3~10 10~20 20~30 30~40 40~50 50~60 60~75

RZQG71

1.9

2.4

2.9

3.4

3.9

RZQG100~140

3.0

3.5

4.0

4.5

5.0

5.5

6.0

To determine the complete recharge amount (kg) (in case of
size‑up liquid pipe size)

Model

L1 (m)

3~5

5~10 10~15 15~20 20~25 25~30 30~35

RZQG71

1.9

2.4

2.9

3.4

3.9

RZQG100~140

3.0

3.5

4.0

4.5

5.0

5.5

6.0

To determine the complete recharge amount (kg) (in case of
size‑down liquid pipe size)

Model

L1 (m)

3~10

RZQG71

1.9

RZQG100~140

3.0

4.4.3

Charging refrigerant: Setup

See 

"4.3.1 Checking refrigerant piping: Setup" on page 6

.

4.4.4

To charge additional refrigerant

WARNING

▪ Only use R410A as refrigerant. Other substances may

cause explosions and accidents.

▪ R410A  contains  fluorinated  greenhouse  gases.  Its

global  warming  potential  (GWP)  value  is  2087.5.  Do
NOT vent these gases into the atmosphere.

▪ When  charging  refrigerant,  always  use  protective

gloves and safety glasses.

Prerequisite: 

Before charging refrigerant, make sure the refrigerant

piping is connected and checked (leak test and vacuum drying).

1

Connect  the  refrigerant  cylinder  to  both  the  service  port  of  the
gas stop valve and the service port of the liquid stop valve.

2

Charge the additional refrigerant amount.

3

Open the stop valves.

4.4.5

To fix the fluorinated greenhouse gases
label

1

Fill in the label as follows:

b

Contains fluorinated greenhouse gases

2

1

1

1

2

2

kg

tCO

2

eq

GWP × kg

1000

=
=

+

kg

=

kg

=

GWP: XXX

RXXX

a

f

c

d
e

a

If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of 

a

.

b

Factory refrigerant charge: see unit name plate

c

Additional refrigerant amount charged

d

Total refrigerant charge

e

Quantity of fluorinated greenhouse gases

 of the total

refrigerant charge expressed as tonnes CO

2

 equivalent.

f

GWP = Global warming potential

NOTICE

Applicable  legislation  on 

fluorinated  greenhouse  gases

requires  that  the  refrigerant  charge  of  the  unit  is  indicated
both in weight and CO

2

 equivalent.

Formula  to  calculate  the  quantity  in  CO

2

  equivalent

tonnes:

  GWP  value  of  the  refrigerant  ×  total  refrigerant

charge [in kg] / 1000

Use  the  GWP  value  mentioned  on  the  refrigerant  charge
label.  That  GWP  is  based  on  the  current  legislation  on
fluorinated greenhouse gases. The GWP mentioned in the
manual might be outdated.

2

Fix  the  label  on  the  inside  of  the  outdoor  unit.  There  is  a
dedicated place for it on the wiring diagram label.

Summary of Contents for RZQG100L8Y1L

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners RZQG71L9V1L RZQG71L8Y1L RZQG100L8Y1L RZQG125L8Y1L RZQG140L7Y1L...

Page 2: ...1000 1000 500 HD HU HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB H...

Page 3: ...or 9 5 Commissioning 9 5 1 Checklist before commissioning 9 5 2 To perform a test run 10 5 3 Error codes when performing a test run 11 6 Disposal 11 7 Technical data 12 7 1 Service space Outdoor unit...

Page 4: ...a Make sure not to cover the drain holes of the bottom plate of the unit INFORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOTICE Fix the outdoor unit to the fou...

Page 5: ...DANGER RISK OF BURNING 4 2 1 To connect the refrigerant piping to the outdoor unit 1 Do the following Remove the service cover a with screw b Remove the piping intake plate c with screw d c a b d 2 C...

Page 6: ...ng machine e Vacuum pump f Stop valve 4 3 2 To check for leaks NOTICE Do NOT exceed the unit s maximum working pressure see PS High on the unit name plate NOTICE Make sure to use a recommended bubble...

Page 7: ...ecking refrigerant piping Setup on page 6 4 4 4 To charge additional refrigerant WARNING Only use R410A as refrigerant Other substances may cause explosions and accidents R410A contains fluorinated gr...

Page 8: ...an or equal to the minimum Ssc value Model Minimum Ssc value RZQG71_V1 RZQG100 140_Y1 1170 kVA 4 5 2 Specifications of standard wiring components Component V1 Y1 71 71 100 125 140 Power supply cable M...

Page 9: ...ection cable d Liquid pipe e Liquid pipe insulation f Finishing tape 2 Install the service cover 4 6 2 To check the insulation resistance of the compressor NOTICE If after installation refrigerant acc...

Page 10: ...m a test run This task is only applicable when using the BRC1E52 user interface When using BRC1E51 see the installation manual of the user interface When using BRC1D see the service manual of the user...

Page 11: ...ween outdoor unit and indoor units between indoor unit and user interface The fuse on the outdoor unit PCB has blown out E3 E4 or L8 The stop valves are closed The air inlet or air outlet is blocked E...

Page 12: ...prevent discharged air from flowing back to the suction side through the bottom of the unit 2 Maximum two units can be installed Not allowed Multiple rows of units See figure 2 on the inside of the fr...

Page 13: ...citor DS1 DIP switch F1U F8U RZQG71_V1 F1U F2U Fuse F6U Fuse T 3 15 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQG_Y1 F1U F2U Fuse 31 5 A 250 V F1U A2P Fuse T 5 0 A 250 V F3U F6U Fuse T 6 3 A 250 V F...

Page 14: ......

Page 15: ......

Page 16: ...4P473073 1A 2019 04 Copyright 2017 Daikin 4P473073 1 A 0000000...

Reviews: