RZQ71~125B7V3B
Split System air conditioners
4PW16864-1A

Installation manual

12

Test run

1

Make sure the liquid and gas shut-off valves are open.

Be sure to close the frontside panel before operation, as not
doing so can cause electric shock.
-

The refrigerant pressure may not rise, even if the shut-off 
valve is opened after an air purge is performed using a 
vacuum pump.
This is because the indoor unit refrigerant piping is closed off
with electric valves inside. This will not create any problems
during operation.

2

Be sure to set it to cooling and press the operation switch.

3

Press the inspection/test-run switch on the remote control to put
the machine into test-run mode.

4

Make sure the compressor is not starting and stopping during
the test-run by listening. If it is starting and stopping,
immediately stop the machine using the remote control, and
check the refrigerant level, etc. There may be some sort of
malfunction.

Precautions regarding test-runs

If the remote control shows E3, E4 or L8 as an error code, there
is a possibility that either the shut-off valve is closed, or the
outlet vent is closed.

If the error code U2 is displayed on the remote contol, check for
voltage imbalance.

If the error code U4 or UF is displayed on the remote contol,
check the inter-unit branch wiring connection.

D

ISPOSAL

 

REQUIREMENTS

Dismantling of the unit, treatment of the refrigerant, oil and any other
parts should be done in accordance with the relevant local and
national regulations.

N

OTES

 Opening direction

A

Liquid side

B

Gas side

Remove the cap and turn 
counterclockwise with a 
hex wrench until it stops

A

B

Summary of Contents for RZQ71B7V3B

Page 1: ...INSTALLATION MANUAL RZQ71B7V3B RZQ100B7V3B RZQ125B7V3B Split System air conditioners...

Page 2: ...6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C...

Page 3: ...ni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid ka...

Page 4: ...may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage electric shocks or fire When a...

Page 5: ...ete grounding may cause electric shocks Gas pipe Ignition or explosion may occur if the gas leaks Water pipe Hard vinyl tubes are not effective grounds Lightning conductor or telephone ground wire Ele...

Page 6: ...inage of the unit is not easy please build up the unit on a foundation of concrete blocks etc the height of the foundation should be maximum 150 mm 5 If you install the unit on a frame please install...

Page 7: ...he table below REFRIGERANT PIPE SIZE AND ALLOWABLE PIPE LENGTH Suction side obstacle Obstacle is present Discharge side obstacle 1 In these cases close the bottom of the installation frame to prevent...

Page 8: ...0 15 9 O 1 19 1 1 2H 1 Refrigerant pipe size In case of twin triple and double twin applications the listed refrigerant pipe sizes relate to the main pipes only L1 the pipes between the outdoor unit a...

Page 9: ...s through walls In case of simultaneous operating system Upward and downward piping should be performed at the main piping line Use branch piping kit optional for branching refrigerant pipes Precautio...

Page 10: ...Take care not to damage it After operating the valve be sure to tighten the valve cover properly Check for refrigerant leakage after tightening the cap Cautions for handling service port After the wor...

Page 11: ...the air with refrigerants Use a vacuum pump to vacuum the installation No additional refrigerant is provided for air purging Pipes inside the units were checked for leaks by the manufacturer The refr...

Page 12: ...1 0 5 kg b G2 12 m 6 4 R2 0 6 kg 3 Refrigerant charge amount R R1 R2 0 5 0 6 1 1 kg Example 2 1 G1 L1 5 m G2 L2 L3 L4 17 17 20 54 2 Over 30 m a G1 5 m R1 0 0 kg b G1 G2 30 5 54 30 29 6 4 R2 0 9 kg 3 R...

Page 13: ...may cause capacitor abnormal heating accident due to high frequency waves Therefore never install a phase advancing capacitor Secure the wiring in the order shown below 1 Secure the ground wire to th...

Page 14: ...ning torques for the terminal screws Refer to the installation manual attached to the indoor unit for wiring of indoor units etc Attach an earth leak detector and fuse to the power supply line See fig...

Page 15: ...is not starting and stopping during the test run by listening If it is starting and stopping immediately stop the machine using the remote control and check the refrigerant level etc There may be som...

Page 16: ...r R2T Thermistor coil R3T Thermistor discharge pipe R4T Thermistor suction pipe R5T Thermistor power module RC Signal receiver circuit S1NPL Pressure sensor low S1PH Pressure switch high TC Signal tra...

Page 17: ...NOTES NOTES...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN16864 1A...

Reviews: