Procedure to Remove Propeller Fan and Fan Motor

Removal Procedure

3

2. Procedure to Remove Propeller Fan and Fan 

Motor

Procedure

Warning

Be sure to wait for 10 minutes or more after turning off all power 
supplies before disassembling work.

Step

Procedure

Points

„

Remove the front and top 
panels in accordance with 
the Procedure to remove 
Outside Panels.

1. Remove the propeller fan

1

Unscrew the 4 screws 
that fix the air discharge 
grille and disengage the 
4 hooks at the top and 
bottom of the grille, and 
then remove this air 
discharge grille.

2

Unfasten the fan lock 
nut that fixes the 
propeller fan.

2. Remove the fan motor

„

In order to disconnect the 
connector, do not pull the 
lead wire. Hold the 
connector part and then 
press the hooks.

„

Cautions in mounting the 
motor
Be sure to fix the motor lead 
wire with a clamp. Not 
heeding this caution will 
cause the entanglement of 
the lead wire around the fan, 
which will result in damage 
to the fan.

1

Remove the connector 
for the fan motor from 
the PCB.
(X206A, X207A)

2

The lead wire is 
clamped in 3 places. 
(Click on partition 
plate×3 places)

3

Unscrew the 3 screws 
that fix the front panel 
and then pull up the 
lead wire.

4

Unfastening the 4 lock 
bolts from the fan motor 
enables the removal of 
this fan motor.

Air discharge grille

Fan lock nut

Propeller fan

Hooks

Hooks

Hooks

Connector for fan motor

Screws 
(3 numbers)

Clamp

Bolts (4 numbers)

Lead wire

Propeller fan

Summary of Contents for RZQ100HY4A

Page 1: ...REMOVAL PROCEDURE S E R V I C E M A N U A L Outdoor Unit Inverter Pair Type 4 5 6 HP Class Si281317...

Page 2: ...Service Manual Removal Procedure Outdoor Unit Applicable Models zHeat Pump RZQ100HY4A RZQ125HY4A RZQ160HY4A...

Page 3: ...3 3 Procedure to Remove Switch Box 4 4 Procedure to Remove PCB Assy 1 6 5 Procedure to Remove PCB Assy 2 7 6 Procedure to Remove PCB Assy 3 8 7 Procedure to Remove Low Pressure Sensor Electronic Expan...

Page 4: ...ownward to disassemble it 2 For the front panel side front panel unscrew a single mounting screw and then press this panel downward to remove it 3 For the top panel unscrew the 8 mounting screws and t...

Page 5: ...fan 2 Remove the fan motor In order to disconnect the connector do not pull the lead wire Hold the connector part and then press the hooks Cautions in mounting the motor Be sure to fix the motor lead...

Page 6: ...panel 1 Remove all connectors and Fasten terminals which have a connection to the switch box Remove the lead wire from the terminal of the high pressure switch Remove the lead wire of the compressor f...

Page 7: ...val Procedure 5 2 Unscrew the 2 screws that fix the switch box 3 In order to remove the switch box disengage the 3 hooks 1 on the right and 2 on the left and then pull out this switch box frontward or...

Page 8: ...om the terminal cover of the compressor Remove the lead wire from the terminal of the high pressure switch and low pressure sensor Disconnect the respective connectors from the following parts on the...

Page 9: ...r 1 Disconnect all connectors Unscrew the 3 screws that fix the mounting plate of electrical components for control 2 Disengage the hooks in 2 places to remove the mounting plate of electrical compone...

Page 10: ...urning off all power supplies before disassembling work Step Procedure Points 3 Remove the PCB unit for inverter 1 Unscrew the 4 screws that fix the PCB and the radiation fin 2 Disengage the 2 hooks a...

Page 11: ...ard 2 Strip off the brazed sections in 2 places on the body of the valve and then remove this body 2 Remove the high pressure switch 1 Disconnect the terminals from the high pressure switch and then s...

Page 12: ...e pipe thermistor pinch the mounting spring and pull out this thermistor 2 For the heat exchanger distributor pipe thermistor pull the clamp frontward and then remove this thermistor 3 In order to rem...

Page 13: ...in the unit before starting this removal In order to prevent a gas welding flame from having influence on other pipes protect them with a sheet or iron plate used for welding operation Caution While...

Page 14: ...sections are directly stripped off from the pipes oil may catch fire Be sure to cut the pipes in advance with a pipe cutter 1 Unscrew the 5 screws from the stop valve mounting plate 2 Disconnect the g...

Page 15: ...Revision History Month Year Version Revised contents 01 2013 Si281317 First edition...

Page 16: ...ries supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation of parts and acce...

Reviews: