background image

Installation manual

1

RZQ71~12 RZQ100~140B8W1B

Split System air conditioners

4PW23691-1A

C

ONTENTS

Page

Safety considerations ........................................................................ 1

Before installation.............................................................................. 2

Selecting installation site................................................................... 3

Precautions on installation ................................................................ 4

Installation servicing space ............................................................... 4

Refrigerant pipe size and allowable pipe length ................................ 5

Precautions on refrigerant piping ...................................................... 6

Refrigerant piping.............................................................................. 7

Evacuating......................................................................................... 9

Charging refrigerant ........................................................................ 10

Electrical wiring work....................................................................... 11

Test operation.................................................................................. 13

Disposal requirements .................................................................... 14

Wiring diagram ................................................................................ 15

S

AFETY

 

CONSIDERATIONS

The precautions listed here are divided into the following two types.
Both cover very important topics, so be sure to follow them carefully.

RZQ71B9V3B

RZQ100B8W1B

RZQ100B9V3B

RZQ125B8W1B

RZQ125B9V3B

RZQ140B8W1B

Split System air conditioners

Installation manual

READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.

IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.

IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.

WARNING

If the warning is not observed, it may cause 
serious casualties.

CAUTION

If the caution is not observed, it may cause 
injury or damage to the equipment.

WARNING

For year round cooling applications with low indoor
humidity conditions, such as Electronic Data
Processing rooms, contact your dealer or see the
engineering databook or the service manual.

For use of air-conditioning units in applications with
temperature alarm settings it is advised to foresee a
delay of 10 minutes for signalling the alarm in case
the alarm temperature is exceeded. The air-
conditioning unit may stop for several minutes during
normal operation for “defrosting of the indoor unit” or
when in “thermostat-stop” operation.

WARNING

Ask your dealer or qualified personnel to carry out
installation work.  Do not install the machine by
yourself.
Improper installation may result in water leakage,
electric shocks or fire.

Perform installation work in accordance with this
installation manual.
Improper installation may lead to water leakage,
electric shocks or fire.

When a unit is installed in a small room, it is
necessary to take measures so that the leaked
refrigerant amount does not exceed the limit even if it
leaks. As for the measures to prevent the leak from
not exceeding the limit, please consult with your
distributor.
If the leaked amount exceeds the limit, it may cause
an oxygen deficiency accident.

Be sure to use only the specified accessories and
parts for installation work.
Failure to use the specified parts may result in water
leakage, electric shocks, fire, or the unit falling.

Install the air conditioner on a foundation that can
withstand its weight.
Insufficient strength may result in the fall of equipment
and causing injury.

Carry out the specified installation work in consideration
of strong winds, typhoons, or earthquakes.
Improper installation work may result in accidents due
to fall of equipment.

Make certain that all electrical work is carried out by
qualified personnel according to the local laws and
regulations and this installation manual, using a
separate circuit.
Insufficient capacity of the power supply circuit or
improper electrical construction may lead to electric
shocks or fire.

Make sure that all wiring is secure, using the specified
wires and ensuring that external forces do not act on
the terminal connections or wires.
Incomplete connection or fixing may cause a fire.

When wiring between the indoor and outdoor units,
and wiring the power supply, form the wires so that
the frontside panel can be securely fastened.
If the frontside panel is not in place, overheat of the
terminals, electric shocks or a fire may be caused.

If refrigerant gas leaks during installation work,
ventilate the area immediately.
Toxic gas may be produced if refrigerant gas comes
into contact with fire.

After completing the installation work, check to make
sure that there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks
into the room and comes into contact with a source of
fire, such as a fan heater, stove or cooker.

Before touching electric terminal parts, turn off power
switch.

Summary of Contents for RZQ100B9V3B

Page 1: ...INSTALLATION MANUAL RZQ71B9V3B RZQ100B9V3B RZQ125B9V3B RZQ100B8W1B RZQ125B8W1B RZQ140B8W1B Split System air conditioners...

Page 2: ...9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B...

Page 3: ...ea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmis t...

Page 4: ...ourself Improper installation may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage...

Page 5: ...be according to national regulations Do not connect the earth wire to gas or water pipes lightning conductor or telephone earth wire Incomplete grounding may cause electric shocks Gas pipe Ignition o...

Page 6: ...ation due to rise of high pressure When a strong wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures for installation of this unit...

Page 7: ...pipe disposal If drain pipe disposal from the outdoor unit causes trouble for example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain...

Page 8: ...f piping work Be sure to open the shut off valve after piping installing and vacuming is complete Running the system with the valve closed may break the compressor It is forbidden to discharge refrige...

Page 9: ...y refrigerant gas leaks while working on the unit ventilate the room thoroughly right away Use R410A only when adding refrigerant Installation tools Make sure to use installation tools gauge manifold...

Page 10: ...If the indoor or outdoor units were disconnected from the piping for a long period of time water or dirt might have gotten into the piping If copper piping is corroded Flares should not be re used but...

Page 11: ...areful not to let the indoor and outdoor branch piping come into contact with the compressor terminal cover If the liquid side piping insulation might come into contact with it adjust the height as sh...

Page 12: ...sed before leak test or vacuuming Set up for vacuuming and leak test see figure 8 Procedure for leak test Leak test must satisfy EN378 2 1 Evacuate the pipes and check vacuum 1 No pressure increase fo...

Page 13: ...kg Example 1 1 G1 L1 35 m G2 L2 L3 7 5 12 2 Over 30 m a G1 30 5 m 9 5 R1 0 5 kg b G2 12 m 6 4 R2 0 6 kg 3 Refrigerant charge amount R R1 R2 0 5 0 6 1 1 kg Example 2 1 G1 L1 5 m G2 L2 L3 L4 17 17 20 54...

Page 14: ...h clamping material as shown in the figure below so that it does not come in contact with the piping particulary on the high pressure side Make sure no external pressure is applied to the terminal con...

Page 15: ...overheating When connecting wires of the same gauge connect them according to the below figure Use the correct screwdriver to tighten the terminal screws Small screwdrivers can damage the screw head...

Page 16: ...bol all the time and the unit will switch to heating operation automatically after elapse of that time 2 In case you cannot operate the unit in test run mode for any unusual reason refer to Failure di...

Page 17: ...he product in case of an abnormality when the product is started up When the reversed phase protection circuit forced the unit to stop check if all phases are existing If this is the case shut off the...

Page 18: ...ld supply R1 R2 Resistor R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge pipe R4T Thermistor suction pipe R5T Thermistor power module RC Signal receiver circuit S1NPL Pressure sensor l...

Page 19: ...NOTES NOTES...

Page 20: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW23691 1A...

Reviews: