• Outdoor Units • R-410A • RZQ-DV1
1
5
• Split Sky Air • Outdoor Units
17
5
Capacity tables
5 - 2
Cooling capacity tables
RZQ140DV1
Cooling
Cooling capacity
Indoor
Outdoor temp. (°CDB)
EWB
EDB
25
30
35
40
(°C)
(°C)
TC
(kW)
SHC
(kW)
CPI
(-)
TC
(kW)
SHC
(kW)
CPI
(-)
TC
(kW)
SHC
(kW)
CPI
(-)
TC
(kW)
SHC
(kW)
CPI
(-)
3D063320
SYMBOLS
AFR:
Air flow rate
(m
3
/min)
BF:
Bypass factor
EWB:
Entering wet bulb temp.
(°CWB)
EDB:
Entering dry bulb temp.
(°CDB)
TC:
Total cooling capacity
(kW)
SHC:
Sensible heating capacity
(kW)
PI:
Power input
(kW)
(comp.+outdoor fan motor)
CPI:
Coefficient of power input.
(-)
Caution:
TC and SHC are shown by kW
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark
j
show the max. at standard conditions.
On the figure the mark
Q
show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m
3
/min.) x (1
−
BF) x (DB*
−
EDB)
Add SHC* to SHC.
4. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 5.0 m
Level difference
: 0 m
5. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
6. The value contains less than 5% error acording to indoor unit type.
7. Air flow rate and BF are tabulated below.
(Pair)
Model
FBQ140C
AFR
(BF)
39
(0.14)
8. Rated power input of each model is tabulated below.
(Pair)
Model
FBQ140C
Cooling
4.45
Capacity range
Rated point
Cooling capacity (kW)
Coefficient
of
power
input.
(-)