5
• Split Sky Air • Outdoor Units
14
• Outdoor Units • R-410A • RZQ-DV1
5
Capacity tables
5 - 2
Cooling capacity tables
RZQ100DV1
Cooling
Cooling capacity
Indoor
Outdoor temp. (°CDB)
EWB
EDB
25
30
35
40
(°C)
(°C)
TC
(kW)
SHC
(kW)
CPI
(-)
TC
(kW)
SHC
(kW)
CPI
(-)
TC
(kW)
SHC
(kW)
CPI
(-)
TC
(kW)
SHC
(kW)
CPI
(-)
3D063306
SYMBOLS
AFR:
Air flow rate
(m
3
/min)
BF:
Bypass factor
EWB:
Entering wet bulb temp.
(°CWB)
EDB:
Entering dry bulb temp.
(°CDB)
TC:
Total cooling capacity
(kW)
SHC:
Sensible heating capacity
(kW)
PI:
Power input
(kW)
(comp.+outdoor fan motor)
CPI:
Coefficient of power input.
(-)
Caution:
TC and SHC are shown by kW
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark
j
show the max. at standard conditions.
On the figure the mark
Q
show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m
3
/min.) x (1
−
BF) x (DB*
−
EDB)
Add SHC* to SHC.
4. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 5.0 m
Level difference
: 0 m
5. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
6. The value contains less than 5% error acording to indoor unit type.
7. Air flow rate and BF are tabulated below.
(Pair)
Model
FCQH100D
FCQ100C
FBQ100C
FHQ100
FAQ100
FUQ100
AFR
(BF)
34
(0.17)
23.5
(0.16)
32
(0.13)
24
(0.14)
23
(0.10)
29
(0.07)
(Twin)
Model
FCQ50Cx2
FFQ50x2
FBQ50Cx2
FHQ50x2
AFR
(BF)
12.5x2
(0.28x2)
12x2
(0.16x2)
16x2
(0.16x2)
13x2
(0.1x2)
(Triple)
Model
FCQ35Cx3
FFQ35x3
FBQ35Cx3
FHQ35x3
AFR
(BF)
10.5x3
(0.28x3)
10x3
(0.25x3)
16x3
(0.15x3)
13x3
(0.2x3)
8. Rated power input of each model is tabulated below.
(Pair)
Model
FCQH100D
FCQ100C
FBQ100C
FHQ100
FAQ100
FUQ100
Cooling
2.50
2.64
2.70
3.14
3.29
2.97
(Twin)
Model
FCQ50Cx2
FFQ50x2
FBQ50x2
FHQ50x2
Cooling
2.78
2.79
2.86
3.32
(Triple)
Model
FCQ35Cx3
FFQ35x3
FBQ35x3
FHQ35x3
Cooling
2.78
2.79
2.86
3.32
Capacity range
Rated point
Cooling capacity (kW)
Coefficient
of
power
input.
(-)