17
|
Piping installation
Installer and user reference guide
80
RYYQ+RYMQ+RXYQ
VRV IV+ heat pump
4P546228-1C – 2021.11
Maximum allowable length after branch
The pipe length from the first refrigerant branch kit to the indoor unit ≤40 m.
Example 1: unit 8: b+c+d+e+f+g+p≤40 m
Example 2: unit 6: b+h≤40 m, unit 8: i+k≤40 m
Example 3: unit 8: i≤40 m, unit 2: c≤40 m
17.1.8 Piping length: VRV DX and RA DX
For system containing VRV DX indoor units and RA DX indoor units:
System setup
H5
H4
a
c
f
e
h
H1
BP1
6
i
j
g
b
d
A
B
7
k
l
BP2
5
4
3
2
1
H2
H6
Header
BP box
1~5
RA DX indoor units
6,7
VRV DX indoor units
Maximum allowable length
▪
Between outdoor unit and indoor unit.
Actual piping length
100 m
Example:
a+b+g+l≤100 m
Equivalent length
(a)
120 m
Total piping length
250 m
Example:
a+b+d+g+l+k+c+e+f+h+i+j≤250 m
(a)
Assume equivalent piping length of refnet joint=0.5 m and refnet header=1 m (for
calculation purposes of equivalent piping length, not for refrigerant charge calculations).
▪
Between BP unit and indoor unit.
Indoor unit capacity index
Pipe length
<60
2~15 m
60
2~12 m
71
2~8 m
Remark:
Minimum allowable length
between outdoor unit and first refrigerant
branch kit>5 m (the refrigerant noise from the outdoor unit can be transmitted).
Example: a>5 m