Basic Control
SiBE34-802
50
Function
2.2
Compressor PI Control
Compressor PI Control
Carries out the compressor capacity PI control to maintain Te at constant during cooling
operation and Tc at constant during heating operation to ensure stable unit performance.
[Cooling operation]
[Heating operation]
RXYSQ4 · 5 · 6PA
Controls compressor capacity to adjust Te to
achieve target value (TeS).
Te : Low pressure equivalent saturation temperature
(°C)
Te setting (Set in Set-up mode 2)
TeS : Target Te value
(Varies depending on Te setting, operating
frequency, etc.)
L
M (Normal)
(factory
setting)
H
3
6
9
Controls compressor capacity to adjust Tc to
achieve target value (TcS).
Tc : High pressure equivalent saturation temperature
(°C)
Tc setting
TcS : Target Tc value
(Varies depending on Tc setting, operating
frequency, etc.)
L
M (Normal)
(factory
setting)
H
43
46
49
STn
INV(Fullload) INV(Unload)
STn
INV(Fullload) INV(Unload)
STn
INV(Fullload) INV(Unload)
1
36.0Hz
11
80.0Hz
21
140.0Hz
2
39.0Hz
12
86.0Hz
22
146.0Hz
3
43.0Hz
13
92.0Hz
23
152.0Hz
4
47.0Hz
14
98.0Hz
24
158.0Hz
5
52.0Hz
15
104.0Hz
25
164.0Hz
6
52.0Hz
57.0Hz
16
110.0Hz
26
170.0Hz
7
57.0Hz
64.0Hz
17
116.0Hz
27
175.0Hz
8
62.0Hz
71.0Hz
18
122.0Hz
28
180.0Hz
9
68.0Hz
78.0Hz
19
128.0Hz
29
185.0Hz
10
74.0Hz
20
134.0Hz
30
190.0Hz
31
195.0Hz
∗
Compressors may operate in a pattern other than those listed in above tables subject to the operating conditions.
Selection of full load operation to/from unload operation is made with the unload circuit solenoid valve
(Y3S=SVUL). The full load operation is performed with the SVUL set to OFF, while the unload operation is
performed with the SVUL set to ON.
Summary of Contents for RXYSQ4-5-6PA7V1B
Page 1: ...SiBE34 802 RXYSQ4 5 6PA7Y1B PA7V1B R 410A Heat Pump 50Hz ...
Page 11: ...Introduction SiBE34 802 x ...
Page 39: ...Specifications SiBE34 802 28 Specifications ...
Page 49: ...List of Electrical and Functional Parts SiBE34 802 38 List of Electrical and Functional Parts ...
Page 133: ...Field Setting SiBE34 802 122 Test Operation ...
Page 234: ...SiBE34 802 Piping Diagrams Appendix 223 RXYSQ4 5 6PA7V1B 3D052712 ...
Page 239: ...Wiring Diagrams SiBE34 802 228 Appendix RXYSQ4 5 6PA7V1B 3D05811B ...
Page 240: ...SiBE34 802 Wiring Diagrams Appendix 229 2 2 Field Wiring RXYSQ4 5 6PA7Y1B 3D057919 ...
Page 241: ...Wiring Diagrams SiBE34 802 230 Appendix RXYSQ4 5 6PA7V1B 3D052597 ...
Page 242: ...SiBE34 802 Wiring Diagrams Appendix 231 2 3 Indoor Unit FXCQ20M 25M 32M 63MV3 ...
Page 243: ...Wiring Diagrams SiBE34 802 232 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 244: ...SiBE34 802 Wiring Diagrams Appendix 233 FXFQ20P 25P 32P 40P 50P 63P 80P 100P 125P7VE ...
Page 245: ...Wiring Diagrams SiBE34 802 234 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 246: ...SiBE34 802 Wiring Diagrams Appendix 235 FXKQ25MA 32MA 40MA 63MAVE 3D039564C ...
Page 248: ...SiBE34 802 Wiring Diagrams Appendix 237 FXDQ20M8 25M8V3 ...
Page 249: ...Wiring Diagrams SiBE34 802 238 Appendix FXSQ20M 25M 32M 40M 50M 63M8V3 ...
Page 250: ...SiBE34 802 Wiring Diagrams Appendix 239 FXSQ80M 100M 125M8V3 ...
Page 252: ...SiBE34 802 Wiring Diagrams Appendix 241 FXHQ32MA 63MA 100MAVE 3D039801D ...
Page 255: ...Wiring Diagrams SiBE34 802 244 Appendix FXUQ71MA 100MA 125MAV1 3D044973A ...
Page 256: ...SiBE34 802 Wiring Diagrams Appendix 245 BEVQ71MA 100MA 125MAVE 3D044901B ...
Page 261: ...Example of Connection SiBE34 802 250 Appendix ...