Troubleshooting by Indication on the Centralized Remote Controller
SiBE34-802
206
Troubleshooting
4. Troubleshooting by Indication on the Centralized
Remote Controller
4.1
“
UE
”
Malfunction of Transmission between Centralized
Remote Controller and Indoor Unit
Remote Controller
Display
UE
Applicable
Models
AII indoor unit models
Centralized Remote Controller
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and central remote controller is
normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Malfunction of transmission between optional controllers for centralized control and indoor unit
Connector for setting master controller is disconnected.
Failure of PC board for central remote controller
Defect of indoor unit PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
power supply turned
on for indoor units displaying
malfunction?
Is
transmission wiring
disconnected or wired
incorrectly?
Is the
transmission wiring
with the master controller
disconnected or wired
incorrectly?
Is the
master controller's
connector for setting
master controller
disconnected?
Set the group No. correctly.
Replace indoor unit PC
board.
Fix the wiring correctly.
Fix the wiring correctly.
Connect the connector
correctly.
Replace the central PC board.
Reset power supply
simultaneously for all optional
controllers for centralized
control.
YES
YES
NO
YES
YES
YES
YES
Turn indoor unit's power
supply.
YES
NO
NO
NO
NO
NO
NO
Has
an indoor unit once
connected been remove
or its address
changed?
Is the group
No. of malfunctioning
indoor units set?
Is transmission
with all indoor units
malfunctioning?
(V2832)
Summary of Contents for RXYSQ4-5-6PA7V1B
Page 1: ...SiBE34 802 RXYSQ4 5 6PA7Y1B PA7V1B R 410A Heat Pump 50Hz ...
Page 11: ...Introduction SiBE34 802 x ...
Page 39: ...Specifications SiBE34 802 28 Specifications ...
Page 49: ...List of Electrical and Functional Parts SiBE34 802 38 List of Electrical and Functional Parts ...
Page 133: ...Field Setting SiBE34 802 122 Test Operation ...
Page 234: ...SiBE34 802 Piping Diagrams Appendix 223 RXYSQ4 5 6PA7V1B 3D052712 ...
Page 239: ...Wiring Diagrams SiBE34 802 228 Appendix RXYSQ4 5 6PA7V1B 3D05811B ...
Page 240: ...SiBE34 802 Wiring Diagrams Appendix 229 2 2 Field Wiring RXYSQ4 5 6PA7Y1B 3D057919 ...
Page 241: ...Wiring Diagrams SiBE34 802 230 Appendix RXYSQ4 5 6PA7V1B 3D052597 ...
Page 242: ...SiBE34 802 Wiring Diagrams Appendix 231 2 3 Indoor Unit FXCQ20M 25M 32M 63MV3 ...
Page 243: ...Wiring Diagrams SiBE34 802 232 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 244: ...SiBE34 802 Wiring Diagrams Appendix 233 FXFQ20P 25P 32P 40P 50P 63P 80P 100P 125P7VE ...
Page 245: ...Wiring Diagrams SiBE34 802 234 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 246: ...SiBE34 802 Wiring Diagrams Appendix 235 FXKQ25MA 32MA 40MA 63MAVE 3D039564C ...
Page 248: ...SiBE34 802 Wiring Diagrams Appendix 237 FXDQ20M8 25M8V3 ...
Page 249: ...Wiring Diagrams SiBE34 802 238 Appendix FXSQ20M 25M 32M 40M 50M 63M8V3 ...
Page 250: ...SiBE34 802 Wiring Diagrams Appendix 239 FXSQ80M 100M 125M8V3 ...
Page 252: ...SiBE34 802 Wiring Diagrams Appendix 241 FXHQ32MA 63MA 100MAVE 3D039801D ...
Page 255: ...Wiring Diagrams SiBE34 802 244 Appendix FXUQ71MA 100MA 125MAV1 3D044973A ...
Page 256: ...SiBE34 802 Wiring Diagrams Appendix 245 BEVQ71MA 100MA 125MAVE 3D044901B ...
Page 261: ...Example of Connection SiBE34 802 250 Appendix ...