background image

8 Commissioning

Installer and user reference guide

34

5TMV1B

VRV IV-S system air conditioner

4P404224-1 – 2015.03

8

Commissioning

8.1

Overview: Commissioning

After installation and once the field settings are defined, the installer
is  obliged  to  verify  correct  operation.  Therefore  a  test  run  must  be
performed according to the procedures described below.

This  chapter  describes  what  you  have  to  do  and  know  to
commission the system after it is configured.

Commissioning typically consists of the following stages:

1

Checking the "Checklist before commissioning".

2

Performing a test run.

3

If necessary, correcting errors after abnormal completion of the
test run.

4

Operating the system.

8.2

Precautions when commissioning

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING

CAUTION

Do not perform the test operation while working on the
indoor units.

When  performing  the  test  operation,  not  only  the  outdoor
unit,  but  the  connected  indoor  unit  will  operate  as  well.
Working on an indoor unit while performing a test operation
is dangerous.

CAUTION

Do not insert fingers, rods or other objects into the air inlet
or  outlet.  Do  not  remove  the  fan  guard.  When  the  fan  is
rotating at high speed, it will cause injury.

INFORMATION

Note  that  during  the  first  running  period  of  the  unit,
required  power  input  may  be  higher.  This  phenomenon
originates from the compressor that requires a 50 hour run
elapse before reaching smooth operation and stable power
consumption. Reason is that the scroll is made out of iron
and  that  it  takes  some  time  to  smooth  the  surfaces  that
make contact.

NOTICE

Be  sure  to  turn  on  the  power  6  hours  before  operation  in
order  to  have  power  running  to  the  crankcase  heater  and
to protect the compressor.

During test operation, the outdoor unit and the indoor units will start
up.  Make  sure  that  the  preparations  of  all  indoor  units  are  finished
(field  piping,  electrical  wiring,  air  purge,  ...).  See  installation  manual
of the indoor units for details.

8.3

Checklist before commissioning

After the installation of the unit, first check the following items. Once
all below checks are fulfilled, the unit must be closed, only then can
the unit be powered up.

You  read  the  complete  installation  and  operation
instructions,  as  described  in  the 

installer  and  user

reference guide

.

Installation

Check that the unit is properly installed, to avoid abnormal
noises and vibrations when starting up the unit.

Field wiring

Be  sure  that  the  field  wiring  has  been  carried  out
according  to  the  instructions  described  in  the  chapter

"6.8  Connecting  the  electrical  wiring"  on  page  23

,

according  to  the  wiring  diagrams  and  according  to  the
applicable legislation.

Power supply voltage

Check the power supply voltage on the local supply panel.
The  voltage  must  correspond  to  the  voltage  on  the
identification label of the unit.

Earth wiring

Be  sure  that  the  earth  wires  have  been  connected
properly and that the earth terminals are tightened.

Insulation test of the main power circuit

Using  a  megatester  for  500  V,  check  that  the  insulation
resistance  of  2  MΩ  or  more  is  attained  by  applying  a
voltage of 500 V DC between power terminals and earth.
Never use the megatester for the transmission wiring.

Fuses, circuit breakers, or protection devices

Check  that  the  fuses,  circuit  breakers,  or  the  locally
installed  protection  devices  are  of  the  size  and  type
specified 

in 

the 

chapter 

"5.4.2 

Safety 

device

requirements" on page 14

. Be sure that neither a fuse nor

a protection device has been bypassed.

Internal wiring

Visually  check  the  electrical  component  box  and  the
inside  of  the  unit  on  loose  connections  or  damaged
electrical components.

Pipe size and pipe insulation

Be  sure  that  correct  pipe  sizes  are  installed  and  that  the
insulation work is properly executed.

Stop valves

Be  sure  that  the  stop  valves  are  open  on  both  liquid  and
gas side.

Damaged equipment

Check  the  inside  of  the  unit  on  damaged  components  or
squeezed pipes.

Refrigerant leak

Check the inside of the unit on refrigerant leakage. If there
is  a  refrigerant  leak,  try  to  repair  the  leak.  If  the  repair  is
unsuccessful,  call  your  local  dealer.  Do  not  touch  any
refrigerant  which  has  leaked  out  from  refrigerant  piping
connections. This may result in frostbite.

Oil leak

Check  the  compressor  for  oil  leakage.  If  there  is  an  oil
leak, try to repair the leak. If the repairing is unsuccessful,
call your local dealer.

Air inlet/outlet

Check  that  the  air  inlet  and  outlet  of  the  unit  is  not
obstructed  by  paper  sheets,  cardboard,  or  any  other
material.

Additional refrigerant charge

The amount of refrigerant to be added to the unit shall be
written  on  the  included  "Added  refrigerant"  plate  and
attached to the rear side of the front cover.

Installation date and field setting

Be  sure  to  keep  record  of  the  installation  date  on  the
sticker  on  the  rear  of  the  front  panel  according  to
EN60335‑2‑40 and keep record of the contents of the field
setting(s).

Summary of Contents for RXYSCQ4TMV1B

Page 1: ...Installer and user reference guide VRV IV S system air conditioner English Installer and user reference guide VRV IV S system air conditioner RXYSCQ4TMV1B RXYSCQ5TMV1B...

Page 2: ...e pipe end 17 6 4 6 To braze the pipe end 17 6 4 7 Using the stop valve and service port 17 6 4 8 To connect the refrigerant piping to the outdoor unit 18 6 4 9 To connect the refrigerant branching ki...

Page 3: ...Symptom The system does not operate 55 20 2 2 Symptom Fan operation is possible but cooling and heating do not work 56 20 2 3 Symptom The fan strength does not correspond to the setting 56 20 2 4 Sym...

Page 4: ...tall or operate the unit contact your dealer NOTICE Improper installation or attachment of equipment or accessories could result in electric shock short circuit leaks fire or other damage to the equip...

Page 5: ...re is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case re charge is required refer to the nameplate of the unit It states the type o...

Page 6: ...ake sure it is compatible with the inverter resistant to high frequency electric noise to avoid unnecessary opening of the earth leakage protector Install power cables at least 1 metre away from telev...

Page 7: ...to be brought in 3 2 Outdoor unit 3 2 1 To unpack the outdoor unit 1 2 3 2 2 To handle the outdoor unit Carry the unit slowly as shown CAUTION To avoid injury do NOT touch the air inlet or aluminum fi...

Page 8: ...oor units and is intended for R410A use only For an overview which units are available you can consult the product catalogue for VRV IV S An overview is given indicating the allowed combinations of in...

Page 9: ...o guarantee that interference will not occur in a particular installation It is therefore recommended to install the equipment and electric wires keeping proper distances away from stereo equipment pe...

Page 10: ...n cold climates Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up a b c c d a Snow cover or shed b Pedestal minimum height 150 mm c Prevailing win...

Page 11: ...s installed In a case such as the following calculate the volume of A B as a single room or as the smallest room A Where there are no smaller room divisions B Where there is a room division but there...

Page 12: ...r the change over from inch to mm pipes field supply The additional refrigerant calculation has to be adjusted as mentioned in 6 7 3 To determine the additional refrigerant amount on page 21 A Piping...

Page 13: ...erence The piping lengths and height differences must comply with the following requirements Two patterns will be discussed Outdoor with 100 VRV DX indoor units Outdoor with 100 RA DX indoor units Req...

Page 14: ...tems with input current 16 A and 75 A per phase 5 4 2 Safety device requirements The power supply must be protected with the required safety devices i e a main switch a slow blow fuse on each phase an...

Page 15: ...e outdoor unit 3 Providing drainage 4 Preventing the outdoor unit from falling over 5 Protecting the unit against snow and wind by installing a snow cover and baffle plates See Preparing installation...

Page 16: ...nvolves Connecting the refrigerant piping to the outdoor unit Connecting refrigerant branch kits Connecting the refrigerant piping to the indoor units see the installation manual of the indoor units I...

Page 17: ...re the pipe Set exactly at the position as shown in the following illustration A Conventional flare tool Flare tool for R410A clutch type Clutch type Ridgid type Wing nut type Imperial type A 0 0 5 mm...

Page 18: ...handle the service port Always use a charge hose equipped with a valve depressor pin since the service port is a Schrader type valve After handling the service port make sure to tighten the service po...

Page 19: ...ered on the expansion valves will initialise This means that they will close Leak test and vacuum drying of field piping and indoor units is impossible when this happens Therefore there will be explai...

Page 20: ...t for leaks by applying a bubble test solution to all piping connections 3 Discharge all nitrogen gas NOTICE Make sure to use a recommended bubble test solution from your wholesaler Do not use soap wa...

Page 21: ...sure to turn on the power 6 hours before operation in order to have power running to the crankcase heater and to protect the compressor NOTICE If operation is performed within 12 minutes after the in...

Page 22: ...erant charge mode instructions Charging refrigerant in manual additional refrigerant charge mode The remaining additional refrigerant charge can be charged by operating the outdoor unit by means of th...

Page 23: ...a Field power supply with earth leakage protector b Main switch c Earth connection d Outdoor unit e Indoor unit f User interface g Power supply wiring sheathed cable 230 V h Transmission wiring sheat...

Page 24: ...After finishing the electrical work confirm that each electrical component and terminal inside the electrical components box is connected securely Make sure all covers are closed before starting up t...

Page 25: ...ring on the outdoor unit NOTICE Follow the wiring diagram delivered with the unit located at the inside of the service cover Make sure the electrical wiring does NOT obstruct proper reattachment of th...

Page 26: ...htening torque does NOT exceed 4 1 N m 5 7 Configuration 7 1 Overview Configuration This chapter describes what you have to do and know to configure the system after it is installed It contains inform...

Page 27: ...indoor unit is installed 7 LEDs display The display gives feedback about the field settings which are defined as Mode Setting Value H1P Shows the mode H2P H7P Shows the settings and values represented...

Page 28: ...mode 2 BS1 5 s 3 Select setting 8 X depends on the setting that you want to select BS2 X binary 8 Action Button display 4 Select value 4 8 C a Display the current value b Change to 4 X depends on the...

Page 29: ...rface they can be checked again through this monitoring settings For the content or reason behind the malfunction code see 11 3 Solving problems based on error codes on page 36 where most relevant mal...

Page 30: ...e level of operation Depending on the chosen level the noise level will be lowered The start and stop moments for this function are defined under setting 2 26 and 2 27 default Deactivated Level 1 Leve...

Page 31: ...ral patterns are available and explained below Modify the parameters to the needs of your building and to realize the best balance between energy consumption and comfort No matter which control is sel...

Page 32: ...sed in conjunction with setting 2 9 Quick Overshoot during heating operation or undershoot during cooling operation is allowed compared to the requested refrigerant temperature in order to achieve the...

Page 33: ...porating temperature Quick Powerful Mild Room temperature evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful 7 3 4 Example Automatic mode...

Page 34: ...abnormal noises and vibrations when starting up the unit Field wiring Be sure that the field wiring has been carried out according to the instructions described in the chapter 6 8 Connecting the elect...

Page 35: ...trol Cooling stable condition Communication check Stop valve check Pipe length check Pump down operation Unit stop INFORMATION During the test operation it is not possible to stop the unit operation f...

Page 36: ...essure leading to worse performance 10 4 About service mode operation Refrigerant recovery operation vacuuming operation is possible by applying setting 2 21 Refer to 7 2 Making field settings on page...

Page 37: ...nction R2T open circuit short circuit A1P X12A Check connection on PCB or actuator Suction temperature sensor malfunction R3T A1P X12A R5T A1P X12A Check connection on PCB or actuator Liquid temperatu...

Page 38: ...he piping and wiring of the specified indoor unit are not connected correctly to the outdoor unit Open the stop valve on both the gas and liquid side Confirm that the piping and wiring of the specifie...

Page 39: ...in mm 40 490 485 495 170 620 150 60 101 30 460 30 37 52 823 940 88 60 19 100 151 52 102 118 59 62 216 130 20 98 21 89 32 17 69 17 104 53 95 289 313 53 95 19 80 3D089312 j b h i g a f e d f c f a Gas p...

Page 40: ...250 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 500 HB HU HB HD HD HU 250 1000 1000 500 H...

Page 41: ...A2 A1 If there is danger of drainage dripping and freezing between the upper and lower units A2 Then install a roof between the upper and lower units Install the upper unit high enough above the lowe...

Page 42: ...id e Stop valve gas f Service port refrigerant charge g Service port high pressure h Switch box i Cable tie mountings to fix the field wiring with cable ties to ensure stress relief j Accumulator k Fa...

Page 43: ...exchanger i Service port high pressure j Muffler k Check valve l Compressor accumulator m Capillary tube n Service port refrigerant charge o Accumulator M1C Compressor M1F Fan motor R1T Thermistor ai...

Page 44: ...N RED ORG YLW X81A Z7C N 2 Z5C N 1 Z6C N 2 TO OUT D TO IN D Z7C N 1 GRN Z5C N 3 X2M F1 F2 F1 F2 X99A FRONT DETAIL OF ELECTRICAL COMPONENT BOX BACK Position of compressor terminal NOTE 6 NOTE 7 OUTDOOR...

Page 45: ...L1R L3R Reactor M1C Motor compressor M1F Motor fan PS Switching power supply R1 R2 Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction 1 R4T Thermistor heat exchanger de icer...

Page 46: ...Heating nominal b Capacity 12 1 kW 14 0 kW COP 3 81 3 58 PED Category 1 Most critical part Compressor PS V 167 bar l Maximum number of indoor units connected c 64 Heat exchanger Type Cross fin Treatm...

Page 47: ...50 Hz Voltage 220 240 V Current Nominal running current RLA a 19 0 A Starting current MSC b MCA Minimum circuit amps MCA c 29 1 A Maximum fuse amps MFA d 32 A Total overcurrent amps TOCA e 29 1 A Full...

Page 48: ...s needs to be within the specified range The connection ratio CR 50 CR 130 HP class of outdoor unit 50 minimum CR VRV DX 80 minimum CR RA DX 100 nominal CR 130 maximum CR 4 50 80 100 130 5 62 5 100 12...

Page 49: ...erface dedicated depending on indoor unit type e BP box required to connect Residential Air RA or Sky Air SA direct expansion DX indoor units f Residential Air RA direct expansion DX indoor units g Us...

Page 50: ...creases and the system needs to go into defrost operation to be able to deliver enough heat to the indoor units The indoor unit will stop fan operation the refrigerant cycle will reverse and energy fr...

Page 51: ...ect expansion DX indoor unit d User interface dedicated depending on indoor unit type e BP box required to connect Residential Air RA or Sky Air SA direct expansion DX indoor units f Residential Air R...

Page 52: ...s equipped with advanced energy saving functionality Depending on the priority emphasises can be put on energy saving or comfort level Several parameters can be selected resulting in the optimal balan...

Page 53: ...may be required depending on the applicable legislation Please contact your installer for more information WARNING The refrigerant in the air conditioner is safe and normally does not leak If the ref...

Page 54: ...table indicates main components Refer to your maintenance and inspection contract for more details The table indicates recommended intervals of replacement cycles However in order to keep the unit ope...

Page 55: ...ir thermistor malfunction indoor Movement detector or floor temperature sensor malfunction indoor User interface thermistor malfunction indoor PCB malfunction outdoor High pressure switch was activate...

Page 56: ...or U5 and stops but then restarts after a few minutes This is because the user interface is intercepting noise from electric appliances other than the air conditioner The noise prevents communication...

Page 57: ...the product and or operates the product Applicable legislation All international European national and local directives laws regulations and or codes that are relevant and applicable for a certain pro...

Page 58: ......

Page 59: ......

Page 60: ...4P404224 1 2015 03 Copyright 2015 Daikin...

Reviews: