• Outdoor Unit • RXYSCQ-TV1
2
• VRV Systems • RXYSCQ-TV1
4
2
Specifications
Standard Accessories : Installation manual;
Standard Accessories : Operation manual;
Standard Accessories : Connection pipes;
Piping connections
Liquid
Type
Flare connection
OD
mm
9.52
Gas
Type
Flare connection
OD
mm
15.9
Total piping length
System Actual
m
-
Level difference
OU - IU Outdoo
r unit in
highest
position
m
-
Indoor
unit in
highest
position
m
-
Heat insulation
Both liquid and gas pipes
Piping length
OU - IU Max.
m
300
Defrost method
Reversed cycle
Safety devices
Item
01
High pressure switch
02
Fan driver overload protector
03
Inverter overload protector
04
PC board fuse
PED
Category
Category I
Most critical part
Name
Compressor
Ps*V
Bar*l
167
2-2 Electrical Specifications
RXYSCQ4TV1
RXYSCQ5TV1
Power supply
Name
V1
Phase
1~
Frequency
Hz
50
Voltage
V
220-240
Voltage range
Min.
%
-10
Max.
%
10
Current
Nominal running
current (RLA) - 50Hz
Cooling
A
19.0 (5)
Current - 50Hz
Minimum circuit amps (MCA)
A
29.1
Maximum fuse amps (MFA)
A
32
Total overcurrent amps (TOCA)
A
29.1 (6)
Full load amps
(FLA)
Total
A
0.6
Wiring connections -
50Hz
For power supply
Quantity
3G
For connection with
indoor
Quantity
2
Remark
F1,F2
Power supply intake
Both indoor and outdoor unit
2-1 Technical Specifications
RXYSCQ4TV1
RXYSCQ5TV1