background image

English

4

[Drainage through Drainpipe]

• Make sure that the drainpipe is installed prop-

erly to drain water.

If no water is discharged from the drainpipe while 
the air conditioner is cooling operation, the drain-
pipe may be clogged with dust or dirt and water 
leakage from the indoor units may result.
Stop operating the air conditioner and consult 
your dealer.

2. SPECIFICATIONS

[RXYQ] 

 

[REYQ]

Model name

RXYQ72PYDN

RXYQ96PYDN RXYQ120PYDN

Power supply

Phase

3~

3~

3~

Frequency

(Hz)

60

60

60

Voltage

(V)

460

460

460

Nominal cooling capacity

(MBh)

72

96

120

Nominal heating capacity

(MBh)

81

108

135

66-1/8×

66-1/8×

66-1/8×

Dimensions H×W×D

(inch)

36-5/8×30-1/8

36-5/8×30-1/8

36-5/8×30-1/8

Mass

(Ib)

573

573

573

Refrigerant

type

R410A

R410A

R410A

charge (*1)

(Ib)

18.1

19.8

20.1

Design pressure

High side

(psig)

478

478

478

Low side

(psig)

320

320

320

Model name

RXYQ144PYDN RXYQ168PYDN RXYQ192PYDN

Power supply

Phase

3~

3~

3~

Frequency

(Hz)

60

60

60

Voltage

(V)

460

460

460

Nominal cooling capacity

(MBh)

144

168

192

Nominal heating capacity

(MBh)

162

189

216

(66-1/8×36-5/

8×30-1/8)+

(66-1/8×36-5/

8×30-1/8)+

(66-1/8×36-5/

8×30-1/8)+

Dimensions H×W×D

(inch)

(66-1/8×36-5/

8×30-1/8)

(66-1/8×36-5/

8×30-1/8)

(66-1/8×36-5/

8×30-1/8)

Mass

(Ib)

573+573

573+573

573+573

Refrigerant

type

R410A

R410A

R410A

charge (*1)

(Ib)

18.1+18.1

18.1+19.8

18.1+20.1

Design pressure

High side

(psig)

478

478

478

Low side

(psig)

320

320

320

Model name

RXYQ216PYDN RXYQ240PYDN

Power supply

Phase

3~

3~

Frequency

(Hz)

60

60

Voltage

(V)

460

460

Nominal cooling capacity

(MBh)

216

240

Nominal heating capacity

(MBh)

243

270

(66-1/8×36-5/

8×30-1/8)+

(66-1/8×36-5/

8×30-1/8)+

Dimensions H×W×D

(inch)

(66-1/8×36-5/

8×30-1/8)

(66-1/8×36-5/

8×30-1/8)

Mass

(Ib)

573+573

573+573

Refrigerant

type

R410A

R410A

charge (*1)

(Ib)

19.8+20.1

20.1+20.1

Design pressure

High side

(psig)

478

478

Low side

(psig)

320

320

Model name

RXYQ72PTJU

RXYQ96PTJU

RXYQ120PTJU

Power supply

Phase

3~

3~

3~

Frequency

(Hz)

60

60

60

Voltage

(V)

208-230

208-230

208-230

Nominal cooling capacity

(MBh)

72

96

120

Nominal heating capacity

(MBh)

81

108

135

Dimensions H×W×D

(inch) 66-1/8×36-5/8×

30-1/8

66-1/8×36-5/8×

30-1/8

66-1/8×36-5/8×

30-1/8

Mass

(Ib)

560

560

560

Refrigerant

type

R410A

R410A

R410A

charge (*1)

(Ib)

18.1

19.8

20.1

Design pressure

High side

(psig)

478

478

478

Low side

(psig)

320

320

320

Model name

RXYQ144PTJU RXYQ168PTJU RXYQ192PTJU

Power supply

Phase

3~

3~

3~

Frequency

(Hz)

60

60

60

Voltage

(V)

208-230

208-230

208-230

Nominal cooling capacity

(MBh)

144

168

192

Nominal heating capacity

(MBh)

162

189

216

Dimensions H×W×D

(inch)

66-1/8×

51-3/16×

30-1/8

(66-1/8×36-5/8×

30-1/8)+

(66-1/8×36-5/8×

30-1/8)

(66-1/8×36-5/8×

30-1/8)+

(66-1/8×36-5/8×

30-1/8)

Mass

(Ib)

747

560+560

560+560

Refrigerant

type

R410A

R410A

R410A

charge (*1)

(Ib)

24.5

18.1+19.8

18.1+20.1

Design pressure

High side

(psig)

478

478

478

Low side

(psig)

320

320

320

Model name

RXYQ216PTJU RXYQ240PTJU

Power supply

Phase

3~

3~

Frequency

(Hz)

60

60

Voltage

(V)

208-230

208-230

Nominal cooling capacity

(MBh)

216

240

Nominal heating capacity

(MBh)

243

270

Dimensions H×W×D

(inch)

(66-1/8×36-5/8×

30-1/8)+

(66-1/8×36-5/8×

30-1/8)

(66-1/8×36-5/8×

30-1/8)+

(66-1/8×36-5/8×

30-1/8)

Mass

(Ib)

560+560

560+560

Refrigerant

type

R410A

R410A

charge (*1)

(Ib)

19.8+20.1

20.1+20.1

Design pressure

High side

(psig)

478

478

Low side

(psig)

320

320

Model name

REYQ72PYDN

REYQ96PYDN REYQ120PYDN

Power supply

Phase

3~

3~

3~

Frequency

(Hz)

60

60

60

Voltage

(V)

460

460

460

Nominal cooling capacity

(MBh)

72

96

120

Nominal heating capacity

(MBh)

81

108

135

66-1/8×

66-1/8×

66-1/8×

Dimensions H×W×D

(inch)

51-1/4×30-1/8

51-1/4×30-1/8

51-1/4×30-1/8

Mass

(Ib)

732

732

732

Refrigerant

type

R410A

R410A

R410A

charge (*1)

(Ib)

22.7

23.4

23.8

Design pressure

High side

(psig)

478

478

478

Low side

(psig)

320

320

320

01_EN_3P215731-1D.fm  Page 4  Tuesday, February 5, 2008  6:35 PM

Summary of Contents for RXYQ72PYDN

Page 1: ...2PTJU RXYQ216PTJU RXYQ240PTJU Read these instructions carefully before installation Keep this manual in a handy place for future reference This manual should be left with the equipment owner English F...

Page 2: ...1 RXYQ REYQ F 2 3 F F 4 5 6 7 1 7 3 7 2...

Page 3: ...F 8 9 F F 10 11 12 Ceiling Suspended Wall Mounted Double flow Multi flow Corner Ceiling Suspended Wall Mounted Double flow Multi flow Corner 13 1 13 2 15 14...

Page 4: ...or moderate injury It may also be sued to alert against unsafe practices NOTE Indicates a situation that may result in the unit or property damage only accidents Keep these warning sheets handy so tha...

Page 5: ...will cause injury Operating the air conditioner with wet hands could result in a shock hazard Check the unit stand for damage on a contin uous basis especially if it has been in use for a long time If...

Page 6: ...etergent squeeze it well and wipe the panel clean And wipe it with another dry cloth Dismantling of the unit treatment of the refrig erant oil and eventual other parts should be done in accordance wit...

Page 7: ...0 1 20 1 20 1 Design pressure High side psig 478 478 Low side psig 320 320 Model name RXYQ72PTJU RXYQ96PTJU RXYQ120PTJU Power supply Phase 3 3 3 Frequency Hz 60 60 60 Voltage V 208 230 208 230 208 230...

Page 8: ...eating capacity MBh 243 270 66 1 8 36 5 8 30 1 8 66 1 8 36 5 8 30 1 8 Dimensions H W D inch 66 1 8 36 5 8 30 1 8 66 1 8 36 5 8 30 1 8 Mass Ib 573 573 573 573 Refrigerant type R410A R410A charge 1 Ib 1...

Page 9: ...he chapter 6 4 PROGRAMMING START AND STOP OF THE SYSTEM WITH TIMER 18 Temperature setting button Use this button for setting the desired temperature Refer to the chapter 6 1 COOLING HEATING AUTOMATIC...

Page 10: ...n REYQ only In this operation mode cool heat changeover is automatically conducted The operation mode cannot be changed with the remote controller whose display shows changeover under control Change t...

Page 11: ...r will return to the previous state in approximately 5 to 15 minutes Hot start In order to prevent cold air from blowing out of an indoor unit at the start of heating oper ation the indoor fan is auto...

Page 12: ...LOW DIREC TION Refer to figure 6 only for Dou ble flow Multi flow Corner Ceiling suspended and Wall mounted Press the air flow direction adjust but ton to select the air direction The air flow flap di...

Page 13: ...3 hours and start the system after 4 hours the system will stop after 3 hours and start 1 hour later 6 5 SETTING THE MASTER REMOTE CON TROLLER In the case of the system as shown in figure 14 only the...

Page 14: ...setting of group control and two remote controller control systems 7 OPTIMUM OPERATION Observe the following precautions to ensure the system operates properly Prevent direct sunlight from entering a...

Page 15: ...to conserve energy Clean the exterior See the operation manual included with the indoor unit for details on how to clean it 9 FOLLOWING SYMPTOMS ARE NOT AIR CONDITIONER TROUBLES 9 1 THE SYSTEM DOES NO...

Page 16: ...on Moisture generated by defrost becomes steam and is exhausted 9 8 NOISE OF AIR CONDITIONERS Indoor unit A zeen sound is heard immediately after the power supply is turned on The electronic expansion...

Page 17: ...operation The operation mode selector button does not work well Turn off the power If the display the unit number and the operation lamp flash and the malfunction code appears Refer to figure 12 1 In...

Page 18: ...on the remote controller Name address telephone number Repair after the warranty term is expired Contact your dealer If necessary to repair pay service is available Minimum storage period of important...

Page 19: ...ended lengths of time until the need arises for maintenance work in order to ensure the product is operational as long as possible Use for appropriate maintenance design budgeting maintenance and insp...

Page 20: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 1D EM07A037A 0803 HT...

Reviews: