background image

English

8

NOTE

• For machine protection the system may con-

trol the air flow rate automatically.

• The air flow rate may be adjusted automati-

cally depending on the room temperature or 
the fan may stop immediately. This is not a 
malfunction.

• It may take sometime for finishing to change 

the air flow rate.
This is normal operation.

Press air flow direction adjust button.
Refer to the chapter “6-3 ADJUSTING THE 
AIR FLOW DIRECTION” for details.

STOPPING THE SYSTEM (Refer to figure 4)

Press the on/off button once again.
The operation lamp goes off and the system 
stops operation.

NOTE

• The fan may keep on running for about 

1 minute after the heating operation stops 
for removing the heat in the indoor unit.

• Do not turn off the power immediately after 

the unit stops.
The system need at least 5 minutes for 
residual operation of drain pump device.
Turning off the power immediately will cause 
water leak or trouble.

EXPLANATION OF HEATING OPERATION

• For general heating operation, it may take longer to 

reach the set temperature than in cooling operation. 
We recommend starting the operation which was 
used before using timer operation.

• The following operation is performed in order to 

prevent the heating capacity from dropping or 
cold air from blowing.

Defrost operation

• In heating operation, freezing of the outside 

unit coil increases. Heating capability 
decreases and the system goes into defrost 
operation.

• The airflow will be set to breeze or stop.
• If stopped, the display of the remote control-

ler shows “

”.

• Once the airflow is set to breeze or stop, the 

air conditioner will return to the previous 
state in approximately 5 to 15 minutes.

Hot start

• In order to prevent cold air from blowing out 

of an indoor unit at the start of heating oper-
ation, the indoor fan is automatically 
stopped. The display of the remote controller 
shows “

”.

• The heating capacity drops as the outside tem-

perature falls. If this happens, use another heat-
ing device together with the unit. (When using the 
appliances which produce open fire together, ven-
tilate a room constantly.)
Do not place appliances which produce open fire 
in places exposed to the air flow from the unit or 
under the unit.

• It takes some time for the room to warm up from 

the time the unit is started since the unit is a hot-
air circulatory system to warm the entire room.

• If the hot air rises to the ceiling, leaving the area 

above the floor cold, we recommend using the cir-
culator (the indoor fan for circulating air). Contact 
your dealer for details.

6-2 PROGRAM DRY OPERATION

• The program dry function deprives the room 

of moisture while the air conditioner is in inter-
mittent weak cooling operation so that the 
room temperature will not become too low.

• The microcomputer automatically controls 

the temperature and fan speed, so these 
cannot be set using the remote controller.

• This function is not available if the room tem-

perature is 68°F or lower.

• This function does not controls the humidity.
• FXL and FXN type indoor unit can not oper-

ate program dry operation.

FOR SYSTEMS WITHOUT COOL/HEAT SELEC-
TOR (Refer to figure 5)

NOTE

If “

” (Cooling operation) is not displayed, refer 

to “6-1 COOLING, HEATING, AUTOMATIC AND 
FAN ONLY OPERATION”, and set “

” (Cooling 

operation). 
Unless the air conditioner is set to “

” (Cooling 

operation), the air conditioner cannot be switched 
over to “

” (program dry operation).

5

6

01_EN_3P215731-1D.fm  Page 8  Tuesday, February 5, 2008  6:35 PM

Summary of Contents for RXYQ72PYDN

Page 1: ...2PTJU RXYQ216PTJU RXYQ240PTJU Read these instructions carefully before installation Keep this manual in a handy place for future reference This manual should be left with the equipment owner English F...

Page 2: ...1 RXYQ REYQ F 2 3 F F 4 5 6 7 1 7 3 7 2...

Page 3: ...F 8 9 F F 10 11 12 Ceiling Suspended Wall Mounted Double flow Multi flow Corner Ceiling Suspended Wall Mounted Double flow Multi flow Corner 13 1 13 2 15 14...

Page 4: ...or moderate injury It may also be sued to alert against unsafe practices NOTE Indicates a situation that may result in the unit or property damage only accidents Keep these warning sheets handy so tha...

Page 5: ...will cause injury Operating the air conditioner with wet hands could result in a shock hazard Check the unit stand for damage on a contin uous basis especially if it has been in use for a long time If...

Page 6: ...etergent squeeze it well and wipe the panel clean And wipe it with another dry cloth Dismantling of the unit treatment of the refrig erant oil and eventual other parts should be done in accordance wit...

Page 7: ...0 1 20 1 20 1 Design pressure High side psig 478 478 Low side psig 320 320 Model name RXYQ72PTJU RXYQ96PTJU RXYQ120PTJU Power supply Phase 3 3 3 Frequency Hz 60 60 60 Voltage V 208 230 208 230 208 230...

Page 8: ...eating capacity MBh 243 270 66 1 8 36 5 8 30 1 8 66 1 8 36 5 8 30 1 8 Dimensions H W D inch 66 1 8 36 5 8 30 1 8 66 1 8 36 5 8 30 1 8 Mass Ib 573 573 573 573 Refrigerant type R410A R410A charge 1 Ib 1...

Page 9: ...he chapter 6 4 PROGRAMMING START AND STOP OF THE SYSTEM WITH TIMER 18 Temperature setting button Use this button for setting the desired temperature Refer to the chapter 6 1 COOLING HEATING AUTOMATIC...

Page 10: ...n REYQ only In this operation mode cool heat changeover is automatically conducted The operation mode cannot be changed with the remote controller whose display shows changeover under control Change t...

Page 11: ...r will return to the previous state in approximately 5 to 15 minutes Hot start In order to prevent cold air from blowing out of an indoor unit at the start of heating oper ation the indoor fan is auto...

Page 12: ...LOW DIREC TION Refer to figure 6 only for Dou ble flow Multi flow Corner Ceiling suspended and Wall mounted Press the air flow direction adjust but ton to select the air direction The air flow flap di...

Page 13: ...3 hours and start the system after 4 hours the system will stop after 3 hours and start 1 hour later 6 5 SETTING THE MASTER REMOTE CON TROLLER In the case of the system as shown in figure 14 only the...

Page 14: ...setting of group control and two remote controller control systems 7 OPTIMUM OPERATION Observe the following precautions to ensure the system operates properly Prevent direct sunlight from entering a...

Page 15: ...to conserve energy Clean the exterior See the operation manual included with the indoor unit for details on how to clean it 9 FOLLOWING SYMPTOMS ARE NOT AIR CONDITIONER TROUBLES 9 1 THE SYSTEM DOES NO...

Page 16: ...on Moisture generated by defrost becomes steam and is exhausted 9 8 NOISE OF AIR CONDITIONERS Indoor unit A zeen sound is heard immediately after the power supply is turned on The electronic expansion...

Page 17: ...operation The operation mode selector button does not work well Turn off the power If the display the unit number and the operation lamp flash and the malfunction code appears Refer to figure 12 1 In...

Page 18: ...on the remote controller Name address telephone number Repair after the warranty term is expired Contact your dealer If necessary to repair pay service is available Minimum storage period of important...

Page 19: ...ended lengths of time until the need arises for maintenance work in order to ensure the product is operational as long as possible Use for appropriate maintenance design budgeting maintenance and insp...

Page 20: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 1D EM07A037A 0803 HT...

Reviews: