Daikin RXYMQ36PVJU Installation Manual Download Page 6

English

2

Securely fasten the outside unit terminal cover (panel). If the 
terminal cover/panel is not installed properly, dust or water may 
enter the outside unit causing fire or electric shock.

When installing or relocating the system, keep the refrigerant 
circuit free from substances other than the specified refrigerant 
(R-410A) such as air. Any presence of air or other foreign sub-
stance in the refrigerant circuit can cause an abnormal pres-
sure rise or rupture, resulting in injury.

Do not change the setting of the protection devices. If the pres-
sure switch, thermal switch, or other protection device is 
shorted and operated forcibly, or parts other than those speci-
fied by Daikin are used, fire or explosion may occur.

CAUTION

Do not touch the switch with wet fingers. Touching a switch 
with wet fingers can cause electric shock.

Do not allow children to play on or around the unit to prevent 
injury.

Do not touch the refrigerant pipes during and immediately after 
operation as the refrigerant pipes may be hot or cold, depend-
ing on the condition of the refrigerant flowing through the 
refrigerant piping, compressor, and other refrigerant cycle 
parts. Your hands may suffer burns or frostbite if you touch the 
refrigerant pipes. To avoid injury, give the pipes time to return 
to normal temperature or, if you must touch them, be sure to 
wear proper gloves.

Heat exchanger fins are sharp enough to cut.
To avoid injury wear glove or cover the fins when working
around them.

Install drain piping to proper drainage. Improper drain piping 
may result in water leakage and property damage.

Insulate piping to prevent condensation.

Be careful when transporting the product.

Do not turn off the power immediately after stopping operation. 
Always wait for at least 5 minutes before turning off the power. 
Otherwise, water leakage may occur.

Do not use a charging cylinder. Using a charging cylinder may 
cause the refrigerant to deteriorate.

Refrigerant R-410A in the system must be kept clean, dry, and 
tight.
(a) Clean and Dry -- Foreign materials (including mineral oils such 

as SUNISO oil or moisture) should be prevented from getting 
into the system.

(b) Tight -- R-410A does not contain any chlorine, does not 

destroy the ozone layer, and does not reduce the earth’s pro-
tection again harmful ultraviolet radiation. R-410A can con-
tribute to the greenhouse effect if it is released. Therefore 
take proper measures to check for the tightness of the refrig-
erant piping installation. Read the chapter Refrigerant Pip-
ing and follow the procedures.

Since R-410A is a blend, the required additional refrigerant 
must be charged in its liquid state. If the refrigerant is charged 
in a state of gas, its composition can change and the system 
will not work properly.

The indoor unit is for R-410A. See the catalog for indoor models 
that can be connected. Normal operation is not possible when 
connected to other units.

Remote controller (wireless kit) transmitting distance can be 
shorter than expected in rooms with electronic fluorescent 
lamps (inverter or rapid start types). Install the indoor unit far 
away from fluorescent lamps as much as possible.

Indoor units are for indoor installation only. Outdoor units can 
be installed either outdoors or indoors. 

Do not install the air conditioner in the following locations:
(a) Where a mineral oil mist or oil spray or vapor is produced, 

for example, in a kitchen.
Plastic parts may deteriorate and fall off or result in water 
leakage.

(b) Where corrosive gas, such as sulfurous acid gas, is pro-

duced.
Corroding copper pipes or soldered parts may result in 
refrigerant leakage.

(c) Near machinery emitting electromagnetic waves.

Electromagnetic waves may disturb the operation of the 
control system and cause the unit to malfunction.

(d) Where flammable gas may leak, where there is carbon fiber, 

or ignitable dust suspension in the air, or where volatile 
flammables such as thinner or gasoline are handled. Operat-
ing the unit in such conditions can cause a fire.

Take adequate measures to prevent the outside unit from being 
used as a shelter by small animals. Small animals making con-
tact with electrical parts can cause malfunctions, smoke, or 
fire. Instruct the customer to keep the area around the unit 
clean.

NOTE

Install the power supply and control wires for the indoor and 
outdoor units at least 3.5 feet away from televisions or radios to 
prevent image interference or noise. Depending on the radio 
waves, a distance of 3.5 feet may not be sufficient to eliminate 
the noise.

Dismantling the unit, treatment of the refrigerant, oil and addi-
tional parts must be done in accordance with the relevant local, 
state, and national regulations.

Do not use the following tools that are used with conventional 
refrigerants: gauge manifold, charge hose, gas leak detector, 
reverse flow check valve, refrigerant charge base, vacuum 
gauge, or refrigerant recovery equipment.

If the conventional refrigerant and refrigerator oil are mixed in 
R-410A, the refrigerant may deteriorate.

This air conditioner is an appliance that should not be accessi-
ble to the general public.

The wall thickness of field-installed pipes should be selected in 
accordance with the relevant local, state, and national regula-
tions.

2.

INTRODUCTION

1.

This series uses R410A new refrigerant. Be absolutely sure to com-
ply with “

7. PRECAUTIONS ON REFRIGERANT PIPING

”, because 

even greater caution is needed to prevent impurities from entering 
R410A (mineral oils and water).

2.

The design pressure is 478PSI (3.3MPa), which means that piping 
may be thicker than conventionally, so please refer to “

7. PRECAU-

TIONS ON REFRIGERANT PIPING

”.

3.

This is a mixed refrigerant, so charge as a liquid when adding refrig-
erant. 
(If charged as a gas, the composition of the refrigerant may change, 
preventing normal operation.)

4.

The indoor unit must use R410A. See the catalog for indoor unit 
models which can be connected. (Normal operation is not possible 
when connected to other units.)

5.

The power supply of this series is single-phase, 208/230V, 60Hz.

01_EN_3PN07193-6F.fm  Page 2  Tuesday, September 1, 2009  4:13 PM

Summary of Contents for RXYMQ36PVJU

Page 1: ...his manual in a handy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r...

Page 2: ...re 40 or more 6 or more 6 or more 40 or more 20 or more 20 or more 40 or more 40 or more 8 or more 12 or more in figure 5 figure 6 1 2 3 4 20 or more 20 or more 20 or more 20 or more 40 or more 40 or...

Page 3: ...ore 8 or more 4 or more 60 or more 24 or more 120 or more H A L in 1 15 16 in 1 2 7 3 4 6 5 figure 9 figure 10 figure 11 figure 12 2 1 5 3 4 3 5 6 6 6 4 4 4 7 7 7 8 8 8 figure 15 1 2 figure 16 1 2 3 5...

Page 4: ...F2 F1 F2 F1 1 2 3 1 7 2 2 8 3 4 5 6 B A figure 19 figure 21 1 2 3 4 4 5 6 1 2 3 5 6 8 4 7 1 2 3 4 4 1 2 figure 22 figure 23 figure 24 figure 25 1 2 3 4 5 6 1 2 1 2 3 4 5 6 7 11 8 9 10 figure 26 figure...

Page 5: ...ete grounding can cause a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes could cause a gas leak and potential explosion causing severe injury or death If r...

Page 6: ...nsmitting distance can be shorter than expected in rooms with electronic fluorescent lamps inverter or rapid start types Install the indoor unit far away from fluorescent lamps as much as possible Ind...

Page 7: ...IGERANT PIPING for details on how to connect refrigerant branch kits and how many are needed 3 BEFORE INSTALLATION Transporting the Unit As shown in figure 2 bring the unit slowly Take care not to let...

Page 8: ...for indoor remote controllers place power supply wiring and transmission wiring in conduits and ground the conduits Use shielded wire for transmission wiring Refer to figure 4 1 Indoor unit 2 Branch...

Page 9: ...elation of dimensions of H A and L are shown in the table below in 5 PRECAUTIONS ON INSTALLATION Install making sure the unit is level and the foundation is sturdy enough to prevent vibration noise In...

Page 10: ...act with the piping or shutoff valve See 6 3 How to connect the power supply wiring CAUTION Use a power wire pipe for the power supply wiring Outside the unit make sure the weak electric wiring i e fo...

Page 11: ...oor units in the same system pass the wiring between the units as shown in figure 19 There is no polarity Refer to figure 19 1 Terminal block X2M 2 Use balance type shield wire with no polarity 3 Indo...

Page 12: ...d preventing normal operation NOTE The nitrogen used when brazing while flowing the nitrogen should be set to 2 9PSI 2 8PSI just enough to feel a breeze on your cheek with the decompression valve Do n...

Page 13: ...foreign objects from entering Plug the pipe through holes with putty or insulating material pro cured locally to stop up all gaps as shown in figure 27 Insects or small animals entering the outdoor un...

Page 14: ...efrigerant branch kit either refnet joint or refnet header to indoor unit 130ft Example unit 8 i 130ft Example unit 6 b h 130ft unit 8 i k 130ft Refrigerant branch kit selection Use refnet joint from...

Page 15: ...urement 11 Outdoor unit NOTE The shutoff valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of parts needed to operate the shutoff valve are sh...

Page 16: ...tanks There is a siphon pipe inside so the cylinder need not be upside down to fill with liquid Stand the cylinder upright when filling Stand the tank upside down and charge 1 Calculate the amount of...

Page 17: ...indoor unit 4 Press the fan direction and fan strength buttons on the indoor unit to see if they operate properly Precautions during temperature control checks For around 5 minutes after the compress...

Page 18: ...error Remedial action E3 The shutoff valve of an outdoor unit is left closed Open the gas side shutoff valve and the liquid side shutoff valve Refrigerant overcharge Recalculate the required amount o...

Page 19: ...n level then make similar calculations for the second then third smallest room and so until the result falls short of the maximum con centration 4 Dealing with the situations where the result exceeds...

Page 20: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3PN07193 6F EM09A020 0910 HT 00_CV_3PN07193 6F fm Page 5 Wednesday September 2 2009 4 29 PM...

Reviews: