Daikin RXYMQ36PVJU Installation Manual Download Page 10

English

6

6.

FIELD WIRING

CAUTION

To the electrician

• Do not operate until refrigerant piping work is completed.

(If operated before complete the piping work, the compressor may 
be broken down.)

• Be sure to install a ground fault circuit interrupter.

(This unit uses an inverter, so install the ground fault circuit inter-
rupter that be capable of handling high harmonics in order to pre-
vent malfunctioning of the ground fault circuit interrupter itself.)

6-1 Wiring connection example for whole system

• Electrical wiring work should be done by a certified professional.
• Follow the “Electrical wiring diagram face plate” when carrying out 

any electrical wiring.
Only proceed with wiring work after blocking off all power.

• Make sure the ground resistance is no greater than 4

Ω 

• Attach a ground fault circuit interrupter.
• Ground the indoor and outdoor units.
• Do not connect the ground wire to gas pipes, sewage pipes, lightning 

rods, or telephone ground wires.

Gas pipes:

 can explode or catch fire if there is a gas leak.

Sewage pipes:

 no grounding effect is possible if hard plastic pip-

ing is used.

Telephone ground wires and lightning rods:

 dangerous when 

struck by lightning due to abnormal rise in electrical potential in the 
grounding.

• Use copper wire.
• When doing the electrical wiring, always shut off the power source 

before working, and do not turn on the switch until all work is com-
plete.

• This unit has an inverter, so it must be grounded in order to reduce 

noise and prevent it affecting other appliances, and also to release 
any electrical build-up in the unit case due to leaked current.

• Do not install a power-factor improving phase-advancing capacitor 

under any circumstances.
(Not only will this not improve the power factor, but it might cause a 
fire.)

• Connect the wire securely using designated wire and fix it with 

attached clamp without applying external pressure on the terminal 
parts (terminal for power wiring, terminal for transmission wiring and 
earth terminal). See “

6-3 How to connect the power supply wir-

ing

”.

• Left-over wiring should not be wrapped and stuffed into the unit.
• To prevent the power wiring from being damaged by the knock hole 

edges, put it in a wiring pipe or plastic tube to protect it.

• Secure the wiring with the included clamp so that it does not come in 

contact with the piping or shutoff valve. 
(See “

6-3 How to connect the power supply wiring

”.)

CAUTION

• Use a power wire pipe for the power supply wiring.
• Outside the unit, make sure the weak electric wiring (i.e. for the 

remote controller cord, between units, etc.) and the strong electric 
wiring do not pass near each other, 

keeping them at least 2in. 

apart

.

Proximity may cause electrical interference, malfunctions, and 
breakage.

• Be sure to connect the power wiring to the power wiring terminal 

block and secure it as described in “

6-3 How to connect the 

power supply wiring

”.

• Transmission wiring should be secured as described in “

6-4 Trans-

mission wiring connection procedure

”.

• Secure wiring with clamp (accessory) to avoid contact with piping.
• Make sure the wiring and the front panel do not stick up above the 

structure, and close the cover firmly.

(Refer to figure 15)

1.

Branch switch and ground fault circuit interrupter

2.

Power supply

3.

Outdoor unit

4.

16V

5.

208/230V

6.

Indoor unit

7.

Remote controller

8.

Ground wire

6-2 How to lay the power supply wiring and trans-

mission wiring

Let the power supply wiring and transmission wiring with a conduit pass 
through one of the knockout holes on the front or side cover, and let the 
transmission wiring with a conduit pass through another knockout hole.

• For protection from uninsulated live parts, thread the power supply 

wiring and the transmission wiring through the included insulation 
tube and secure it with the included clamp.

Precautions knock out holes

• Open the knock holes with a hammer or the like.
• After knocking out the holes, we recommend you remove burrs in the 

knock holes and paint the edges and areas around the edges using 
the repair paint to prevent rusting.

• When passing wiring through knock holes, make sure there are no 

burrs, and protect the wiring with protective tape.

(Refer to figure 16)

1.

Screw

2.

Unfasten the screw and open the cover.

(Refer to figure 17)

1.

Shutoff valve attachment plate

2.

Power supply wiring (including ground wire) or transmission 
wiring.

3.

Backward

4.

Knockout hole

5.

Sideways

6.

Forward

7.

Terminal block

8.

Electrical Component Box

Insulation tube
(accessory)

Clamp
(accessory)

Power supply 
wiring

(3in.)

(5/8in.)

2in. 
or 
more

(5/8in.)

Insulation tube
(accessory)

Clamp
(accessory)

Transmission
wiring

(3in.)

<Power supply wiring>

<Transmission wiring>

Ground wire

If small animals might enter the 
unit, block the knock holes with an 
appropriate material (field supply).

Burr

01_EN_3PN07193-6F.fm  Page 6  Tuesday, September 1, 2009  4:13 PM

Summary of Contents for RXYMQ36PVJU

Page 1: ...his manual in a handy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r...

Page 2: ...re 40 or more 6 or more 6 or more 40 or more 20 or more 20 or more 40 or more 40 or more 8 or more 12 or more in figure 5 figure 6 1 2 3 4 20 or more 20 or more 20 or more 20 or more 40 or more 40 or...

Page 3: ...ore 8 or more 4 or more 60 or more 24 or more 120 or more H A L in 1 15 16 in 1 2 7 3 4 6 5 figure 9 figure 10 figure 11 figure 12 2 1 5 3 4 3 5 6 6 6 4 4 4 7 7 7 8 8 8 figure 15 1 2 figure 16 1 2 3 5...

Page 4: ...F2 F1 F2 F1 1 2 3 1 7 2 2 8 3 4 5 6 B A figure 19 figure 21 1 2 3 4 4 5 6 1 2 3 5 6 8 4 7 1 2 3 4 4 1 2 figure 22 figure 23 figure 24 figure 25 1 2 3 4 5 6 1 2 1 2 3 4 5 6 7 11 8 9 10 figure 26 figure...

Page 5: ...ete grounding can cause a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes could cause a gas leak and potential explosion causing severe injury or death If r...

Page 6: ...nsmitting distance can be shorter than expected in rooms with electronic fluorescent lamps inverter or rapid start types Install the indoor unit far away from fluorescent lamps as much as possible Ind...

Page 7: ...IGERANT PIPING for details on how to connect refrigerant branch kits and how many are needed 3 BEFORE INSTALLATION Transporting the Unit As shown in figure 2 bring the unit slowly Take care not to let...

Page 8: ...for indoor remote controllers place power supply wiring and transmission wiring in conduits and ground the conduits Use shielded wire for transmission wiring Refer to figure 4 1 Indoor unit 2 Branch...

Page 9: ...elation of dimensions of H A and L are shown in the table below in 5 PRECAUTIONS ON INSTALLATION Install making sure the unit is level and the foundation is sturdy enough to prevent vibration noise In...

Page 10: ...act with the piping or shutoff valve See 6 3 How to connect the power supply wiring CAUTION Use a power wire pipe for the power supply wiring Outside the unit make sure the weak electric wiring i e fo...

Page 11: ...oor units in the same system pass the wiring between the units as shown in figure 19 There is no polarity Refer to figure 19 1 Terminal block X2M 2 Use balance type shield wire with no polarity 3 Indo...

Page 12: ...d preventing normal operation NOTE The nitrogen used when brazing while flowing the nitrogen should be set to 2 9PSI 2 8PSI just enough to feel a breeze on your cheek with the decompression valve Do n...

Page 13: ...foreign objects from entering Plug the pipe through holes with putty or insulating material pro cured locally to stop up all gaps as shown in figure 27 Insects or small animals entering the outdoor un...

Page 14: ...efrigerant branch kit either refnet joint or refnet header to indoor unit 130ft Example unit 8 i 130ft Example unit 6 b h 130ft unit 8 i k 130ft Refrigerant branch kit selection Use refnet joint from...

Page 15: ...urement 11 Outdoor unit NOTE The shutoff valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of parts needed to operate the shutoff valve are sh...

Page 16: ...tanks There is a siphon pipe inside so the cylinder need not be upside down to fill with liquid Stand the cylinder upright when filling Stand the tank upside down and charge 1 Calculate the amount of...

Page 17: ...indoor unit 4 Press the fan direction and fan strength buttons on the indoor unit to see if they operate properly Precautions during temperature control checks For around 5 minutes after the compress...

Page 18: ...error Remedial action E3 The shutoff valve of an outdoor unit is left closed Open the gas side shutoff valve and the liquid side shutoff valve Refrigerant overcharge Recalculate the required amount o...

Page 19: ...n level then make similar calculations for the second then third smallest room and so until the result falls short of the maximum con centration 4 Dealing with the situations where the result exceeds...

Page 20: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3PN07193 6F EM09A020 0910 HT 00_CV_3PN07193 6F fm Page 5 Wednesday September 2 2009 4 29 PM...

Reviews: