background image

9

English

8-9 THE UNITS CAN GIVE OFF ODOURS

The unit can absorb the smell of rooms, furni-
ture, cigarettes, etc., and then emit it again.

8-10 THE OUTDOOR UNIT FAN DOES NOT

SPIN

During operation.

The speed of the fan is controlled in order to opti-
mize product operation.

8-11 THE DISPLAY SHOWS

This is the case immediately after the main
power supply switch is turned on and means
that the remote controller is in normal condi-
tion. This continues for one minute.

8-12 THE COMPRESSOR IN THE OUT-

DOOR UNIT DOES NOT STOP AFTER
A SHORT HEATING OPERATION

This is to prevent oil and refrigerant from
remaining in the compressor. The unit will
stop after 5 to 10 minutes.

8-13 THE INSIDE OF AN OUTDOOR UNIT IS

WARM EVEN WHEN THE UNIT HAS
STOPPED

This is because the crankcase heater is warm-
ing the compressor so that the compressor
can start smoothly.

9. TROUBLE SHOOTING

If one of the following malfunctions occur, take
the measures shown below and contact your
Daikin dealer.

The system must be repaired by a qualified ser-
vice person.

• If a safety device such as a fuse, a breaker or an

earth leakage breaker frequently actuates, or the
ON/OFF switch does not properly work;
Measure: Turn off the main power switch.

• If water leaks from unit;

Measure: Stop the operation.

• If the display “

”, the unit number and the

operation lamp flash and the malfunction code
appears;

(Refer to figure 12)

1. Inspection display
2. Indoor unit number in which a malfunction

occurs

3. Operation lamp
4. Malfunction code

Measure: Notify your Daikin dealer and report the
malfunction code.

If the system does not properly operate except
for the above mentioned cases and none of the
above mentioned malfunctions is evident, inves-
tigate the system according to the following pro-
cedures.

1. If the system does not operate at all;

• Check if there is no power failure.

Wait until power is restored. If power failure
occurs during operation, the system automati-
cally restarts immediately after the power supply
is recovered.

• Check if no fuse has blown or breaker has

worked. Change the fuse or reset the breaker if
necessary.

2. If the system goes into fan only operation, but as

soon as it goes into heating or cooling operation,
the system stops;

• Check if air inlet or outlet of outdoor or indoor unit

is not blocked by obstacles.
Remove any obstacle and make it well-ventilated.

• Check if the remote controller display shows

” (time to clean the air filter). (Refer to the

chapter “Maintenance” in the indoor unit manual.)

3. The system operates but cooling or heating is

insufficient;

• Check if air inlet or outlet of outdoor or indoor unit

is not blocked by obstacles.
Remove any obstacle and make it well-ventilated.

• Check if the air filter is not clogged. (Refer to the

chapter “Maintenance” in the indoor unit manual.)

• Check the temperature setting.
• Check the fan speed setting on your remote con-

troller.

• Check for open doors or windows. Shut doors and

windows to prevent wind from coming in.

• Check if there are too many occupants in the

room during cooling operation.

• Check if the heat source of the room is excessive.
• Check if direct sunlight enters the room.

Use curtains or blinds.

• Check if the air flow angle is not proper.

TEST

01_3P114261-3M_EN.fm Page 9 Thursday, November 6, 2003 7:23 PM

Summary of Contents for RXY5MY1

Page 1: ...40MY1 E RXY42MY1 E RXY44MY1 E RXY46MY1 E RXY48MY1 E RXY5MYL E RXY8MYL E RXY10MYL E RXY12MYL E RXY14MYL E RXY16MYL E RXY18MYL E RXY20MYL E RXY22MYL E RXY24MYL E RXY26MYL E RXY28MYL E RXY30MYL E RXY32MY...

Page 2: ...tilizar el artefacto El manual explica c mo usar la unidad correctamente y lo ayuda en caso de que surjan problemas Despu s de leerlo gu rdelo para referencia futura Muito obrigado por ter adquirido e...

Page 3: ...2 1 RXY 4 2 3 5 4 00_3P114261 3M_CV fm Page 3 Friday November 7 2003 6 37 PM...

Page 4: ...7 3 7 2 5 7 1 6 6 8 00_3P114261 3M_CV fm Page 4 Friday November 7 2003 6 37 PM...

Page 5: ...9 10 14 11 10 Double flow Ceiling Suspended Wall Mounted Multi flow Corner 12 13 00_3P114261 3M_CV fm Page 5 Friday November 7 2003 6 37 PM...

Page 6: ...ormality such as smell of fire turn off power and call your dealer for instructions Ask your dealer for installation of the air con ditioner Incomplete installation performed by yourself may result in...

Page 7: ...nd the out door unit If they touch the unit carelessly it may result in injury Do not place a flower vase and anything con taining water Water may enter the unit causing an electric shock or fire Do n...

Page 8: ...13 Display defrost hot start Refer to the chapter Operation procedure Explanation of heating operation 14 Timer mode start stop button Refer to the chapter Operation procedure Programming start and s...

Page 9: ...tion To avoid condensation and water dripping out the unit If the temperature or the humidity is beyond these conditions safety devices may work and the air con ditioner may not operate 6 OPERATION PR...

Page 10: ...ler shows 6 2 PROGRAM DRY OPERATION The function of this program is to decrease the humidity in your room with a minimum temperature decrease The micro computer automatically deter mines temperature a...

Page 11: ...The display flashes For setting the timer stop For setting the timer start Press the programming time button and set the time for stopping or starting the system Each time this button is pressed the t...

Page 12: ...ing operation by using curtains or blinds Ventilate often Extended use requires special attention to venti lation Keep doors and windows closed If the doors and windows remain open air will flow out o...

Page 13: ...ied service person Immediately after the cooling operation stops and if the room temperature and humidity are low This is because warm refrigerant gas flows back into the indoor unit and generates ste...

Page 14: ...and report the malfunction code If the system does not properly operate except for the above mentioned cases and none of the above mentioned malfunctions is evident inves tigate the system according...

Page 15: ...3P114261 3M EM03A053A 0401 HT 00_3P114261 3M_CV fm Page 6 Friday November 7 2003 6 37 PM...

Reviews: