65

RXTQ-TAVJ9A / TAVJUA 

EDUS331608C-D

20.5  FXDQ-M

Model

FXDQ07MVJU

FXDQ09MVJU

FXDQ12MVJU

FXDQ18MVJU

FXDQ24MVJU

Printed circuit board fuse

A1P

250 V, 5 A

250 V, 5 A

250 V, 5 A

250 V, 5 A

250 V, 5 A

Fan motor thermal protector

°F

OFF: 266±9

ON: 181±27

OFF: 266±9

ON: 181±27

OFF: 266±9

ON: 181±27

OFF: 266±9

ON: 181±27

OFF: 266±9

ON: 181±27

C: 3D051758

20.6  FXSQ-TA

Model

FXSQ05TAVJU

FXSQ07TAVJU

FXSQ09TAVJU

FXSQ12TAVJU

FXSQ15TAVJU

Printed circuit board fuse

250 V, 3.15 A

250 V, 3.15 A

250 V, 3.15 A

250 V, 3.15 A

250 V, 3.15 A

Printed circuit board fuse (Fan driver)

250 V, 6.3 A

250 V, 6.3 A

250 V, 6.3 A

250 V, 6.3 A

250 V, 6.3 A

Drain pump thermal fuse

°F (°C)

Model

FXSQ18TAVJU FXSQ24TAVJU FXSQ30TAVJU FXSQ36TAVJU FXSQ48TAVJU FXSQ54TAVJU

Printed circuit board fuse

250 V, 3.15 A

250 V, 3.15 A

250 V, 3.15 A

250 V, 3.15 A

250 V, 3.15 A

250 V, 3.15 A

Printed circuit board fuse (Fan driver)

250 V, 6.3 A

250 V, 6.3 A

250 V, 6.3 A

250 V, 6.3 A

250 V, 6.3 A

250 V, 6.3 A

Drain pump thermal fuse

°F (°C)

 3D112398

20.7  FXMQ-PB

Model

FXMQ07PBVJU

FXMQ09PBVJU

FXMQ12PBVJU

FXMQ15PBVJU

FXMQ18PBVJU

Printed circuit board fuse

250 V, 3.15 A

250 V, 3.15 A

250 V, 3.15 A

250 V, 3.15 A

250 V, 3.15 A

Printed circuit board fuse (Fan driver)

250 V, 5 A

250 V, 5 A

250 V, 5 A

250 V, 6.3 A

250 V, 6.3 A

Drain pump thermal fuse

°F (°C)

293 (145)

293 (145)

293 (145)

293 (145)

293 (145)

Model

FXMQ24PBVJU

FXMQ30PBVJU

FXMQ36PBVJU

FXMQ48PBVJU

FXMQ54PBVJU

Printed circuit board fuse

250 V, 3.15 A

250 V, 3.15 A

250 V, 3.15 A

250 V, 3.15 A

250 V, 3.15 A

Printed circuit board fuse (Fan driver)

250 V, 6.3 A

250 V, 6.3 A

250 V, 6.3 A

250 V, 6.3 A

250 V, 6.3 A

Drain pump thermal fuse

°F (°C)

293 (145)

293 (145)

293 (145)

293 (145)

293 (145)

C: 3D086916B

20.8  FXHQ-M

Model

FXHQ12MVJU

FXHQ24MVJU

FXHQ36MVJU

Printed circuit board fuse

250 V, 5 A

250 V, 5 A

250 V, 5 A

Fan motor thermal fuse

°F

Fan motor thermal protector

°F

OFF: 266±9

ON: 176±36

OFF: 266±9

ON: 176±36

OFF: 266±9

ON: 176±36

C: 3D049334A

Summary of Contents for RXTQ-TAVJ9A

Page 1: ...EDUS331608C D 202002 Engineering Data Heat Pump 1 phase 208 230 V 60 Hz Design Manual RXTQ TAVJ9A TAVJUA...

Page 2: ......

Page 3: ...s 14 7 Dimensions 17 8 Service Space 20 9 Center of Gravity 24 10 Piping Diagrams 26 11 Wiring Diagrams 29 12 Field Wiring 32 13 Electrical Characteristics 34 14 Operation Limits 35 15 Sound Levels Re...

Page 4: ...64 20 4 FXEQ P 64 20 5 FXDQ M 65 20 6 FXSQ TA 65 20 7 FXMQ PB 65 20 8 FXHQ M 65 20 9 FXAQ P 66 20 10 FXLQ M FXNQ M 66 20 11 FXTQ TA 66 Appendix 67 1 Introduction 68 1 1 ED Book List 68 1 2 Publicatio...

Page 5: ...th under 39 991 mm in height and over 25 smaller as compared to Easier to install with over 39 weight reduction compared to Low sound levels for comfort in sound sensitive applications Engineered with...

Page 6: ...America 9 Minor model change Power supply symbol VJ 1 phase 208 230 V 60 Hz Indicates major design category Capacity indication in cooling 36 36 000 Btu h 48 48 000 Btu h 60 57 500 Btu h Refrigerant...

Page 7: ...0 Btu h 30 30 000 Btu h 60 60 000 Btu h 12 12 000 Btu h 36 36 000 Btu h 15 15 000 Btu h 42 42 000 Btu h Refrigerant Q R410A Shape F Ceiling mounted cassette Round flow with sensing Z VISTA 2 2 cassett...

Page 8: ...n cooling 48 48 000 Btu h Refrigerant Q R410A Shape M Ceiling mounted duct Series category X Inverter Unit category F Indoor unit for air cooled type Outdoor Air Processing Unit U G 300 V A M VJ Stand...

Page 9: ...D 3 Model Names 3 1 Outdoor Units Capacity range 3 ton 4 ton 5 ton Power supply Standard Capacity index 36 48 57 Heat pump 208 230 V RXTQ 36TA VJ9A 48TA 60TA VJUA Note VJ 1 phase 208 230 V 60 Hz U VJU...

Page 10: ...8P 24P 30P 36P One way blow cassette type FXEQ 07P 09P 12P 15P 18P 24P Slim ceiling mounted duct type FXDQ 07M 09M 12M 18M 24M MSP concealed ducted unit FXSQ 05TA 07TA 09TA 12TA 15TA 18TA 24TA 30TA 36...

Page 11: ...31608C D 3 3 Air Treatment Equipment Outdoor Air Processing Unit Series Model name Power supply Standard FXMQ 48MF VJU Energy Recovery Ventilator VAM series Series Model name Power supply Standard VAM...

Page 12: ...10 RXTQ TAVJ9A TAVJUA EDUS331608C D 4 External Appearance 4 1 Outdoor Units RXTQ60TAVJUA RXTQ36TAVJ9A RXTQ48TAVJUA 3 4 ton 5 ton...

Page 13: ...pressure FXMQ PB VISTA 2 2 cassette unit FXZQ TA Shown with BYFQ60C3W1W Shown with BYFQ60C3W1S Ceiling suspended type FXHQ M 4 way blow ceiling suspended type FXUQ P Wall mounted type FXAQ P One way b...

Page 14: ...12 RXTQ TAVJ9A TAVJUA EDUS331608C D 4 3 Air Treatment Equipment Outdoor air processing unit FXMQ MF Energy recovery ventilator VAM series VAM G...

Page 15: ...onnection ratio Max connection ratio Types of connected indoor units VRV indoor units Single outdoor units 50 130 5 2 Outdoor Unit Combination Model name RXTQ36TAVJ9A RXTQ48TAVJUA RXTQ60TAVJUA Capacit...

Page 16: ...reference data Cooling dB 75 Heating dB 79 Connecting pipes Liquid pipe in mm f3 8 9 5 C1220T flare connection Gas pipe in mm f5 8 15 9 C1220T flare connection Weight lbs kg 172 78 Safety devices Hig...

Page 17: ...ce data Cooling dB 76 Heating dB 78 Connecting pipes Liquid pipe in mm f3 8 9 5 C1220T flare connection Gas pipe in mm f5 8 15 9 C1220T flare connection Weight lbs kg 176 80 Safety devices High pressu...

Page 18: ...e data Cooling dB 74 Heating dB 77 Connecting pipes Liquid pipe in mm f3 8 9 5 C1220T flare connection Gas pipe in mm f3 4 19 1 C1220T flare connection Weight lbs kg 225 102 Safety devices High pressu...

Page 19: ...17 RXTQ TAVJ9A TAVJUA EDUS331608C D 7 Dimensions RXTQ36TAVJ9A 3D126496...

Page 20: ...18 RXTQ TAVJ9A TAVJUA EDUS331608C D RXTQ48TAVJUA 3D126497...

Page 21: ...19 RXTQ TAVJ9A TAVJUA EDUS331608C D RXTQ60TAVJUA 3D126498...

Page 22: ...20 RXTQ TAVJ9A TAVJUA EDUS331608C D 8 Service Space RXTQ36TAVJ9A RXTQ48TAVJUA 2D102479B...

Page 23: ...21 RXTQ TAVJ9A TAVJUA EDUS331608C D RXTQ36TAVJ9A RXTQ48TAVJUA 2D102479B...

Page 24: ...22 RXTQ TAVJ9A TAVJUA EDUS331608C D RXTQ60TAVJUA 2D102480B...

Page 25: ...23 RXTQ TAVJ9A TAVJUA EDUS331608C D RXTQ60TAVJUA 2D102480B...

Page 26: ...24 RXTQ TAVJ9A TAVJUA EDUS331608C D 9 Center of Gravity RXTQ36TAVJ9A RXTQ48TAVJUA 4D101439A Unit in mm 4D101440A Unit in mm...

Page 27: ...25 RXTQ TAVJ9A TAVJUA EDUS331608C D RXTQ60TAVJUA 4D101441A Unit in mm...

Page 28: ...26 RXTQ TAVJ9A TAVJUA EDUS331608C D 10 Piping Diagrams RXTQ36TAVJ9A 3D082498F...

Page 29: ...27 RXTQ TAVJ9A TAVJUA EDUS331608C D RXTQ48TAVJUA 3D088594A...

Page 30: ...28 RXTQ TAVJ9A TAVJUA EDUS331608C D RXTQ60TAVJUA 3D088595A...

Page 31: ...29 RXTQ TAVJ9A TAVJUA EDUS331608C D 11 Wiring Diagrams RXTQ36TAVJ9A 3D124497...

Page 32: ...30 RXTQ TAVJ9A TAVJUA EDUS331608C D RXTQ48TAVJUA 3D124499...

Page 33: ...31 RXTQ TAVJ9A TAVJUA EDUS331608C D RXTQ60TAVJUA 3D124502...

Page 34: ...32 RXTQ TAVJ9A TAVJUA EDUS331608C D 12 Field Wiring RXTQ36TAVJ9A RXTQ48TAVJUA 3D127111...

Page 35: ...33 RXTQ TAVJ9A TAVJUA EDUS331608C D RXTQ60TAVJUA 3D127113...

Page 36: ...34 RXTQ TAVJ9A TAVJUA EDUS331608C D 13 Electrical Characteristics RXTQ36TAVJ9A RXTQ48 60TAVJUA 3D126394...

Page 37: ...35 RXTQ TAVJ9A TAVJUA EDUS331608C D 14 Operation Limits RXTQ36TAVJ9A RXTQ48 60TAVJUA 3D115457...

Page 38: ...36 RXTQ TAVJ9A TAVJUA EDUS331608C D 15 Sound Levels Reference Data RXTQ36TAVJ9A Cooling 4D101947D...

Page 39: ...37 RXTQ TAVJ9A TAVJUA EDUS331608C D RXTQ36TAVJ9A Heating 4D101948E...

Page 40: ...38 RXTQ TAVJ9A TAVJUA EDUS331608C D RXTQ48TAVJUA Cooling 4D102719C...

Page 41: ...39 RXTQ TAVJ9A TAVJUA EDUS331608C D RXTQ48TAVJUA Heating 4D102720D...

Page 42: ...40 RXTQ TAVJ9A TAVJUA EDUS331608C D RXTQ60TAVJUA Cooling 4D101949D...

Page 43: ...41 RXTQ TAVJ9A TAVJUA EDUS331608C D RXTQ60TAVJUA Heating 4D101950E...

Page 44: ...l Accessories RXTQ36TAVJ9A RXTQ48 60TAVJUA Optional accessories RXTQ36TAVJ9A RXTQ48TAVJUA RXTQ60TAVJUA ABC I P printed circuit board kit BRP2A82 Distributive piping REFNET header KHRP26M22H9 Max 4 bra...

Page 45: ...of the peak load of each room Define required total heat load to outdoor unit Indoor unit capacity corrected for indoor air temperature WB Required heat load Safety factor for the indoor units Yes No...

Page 46: ...00 11 0 11 0 6 8 6 8 6 2 8 0 49 8 16 00 12 1 12 2 5 4 5 0 7 0 8 0 49 7 Total heat load MBH From the above heat load calculation the maximum heat load for the system system peak load is 49 8 MBH Level...

Page 47: ...5 1 41 5 55 8 39 0 56 8 37 4 TC Total capacity MBH SHC Sensible heat capacity MBH Selection results of indoor units Room A Room B Room C Room D Room E Room F Max heat load MBH 12 1 12 2 6 8 6 8 10 5 1...

Page 48: ...indoor units Total CI 7 5 2 12 2 15 2 69 2 Provisionally select an outdoor unit based on the total CI of the indoor units The connection ratio of RXTQ TA shall be between 50 and 130 As the total CI of...

Page 49: ...it calculate the capacity B corrected for outdoor air temperature indoor air temperature and connection ratio In case the outdoor air temperature the indoor air temperature or the connection ratio fal...

Page 50: ...ing K1 and K2 Corrected capacity of RXTQ60TAVJUA C B K1 K2 add defrost correction factor for heating capacity Therefore C 62 7 0 94 1 07 55 1 MBH If the corrected capacity C is the same or greater tha...

Page 51: ...49 RXTQ TAVJ9A TAVJUA EDUS331608C D 18 Caution Label 18 1 RXTQ36TAVJ9A 2P435101 1C...

Page 52: ...50 RXTQ TAVJ9A TAVJUA EDUS331608C D 2P435101 1C...

Page 53: ...51 RXTQ TAVJ9A TAVJUA EDUS331608C D 2P435101 1C...

Page 54: ...52 RXTQ TAVJ9A TAVJUA EDUS331608C D 2P435101 1C...

Page 55: ...53 RXTQ TAVJ9A TAVJUA EDUS331608C D 18 2 RXTQ48TAVJUA 2P435103 1B...

Page 56: ...54 RXTQ TAVJ9A TAVJUA EDUS331608C D 2P435103 1B...

Page 57: ...55 RXTQ TAVJ9A TAVJUA EDUS331608C D 2P435103 1B...

Page 58: ...56 RXTQ TAVJ9A TAVJUA EDUS331608C D 2P435103 1B...

Page 59: ...57 RXTQ TAVJ9A TAVJUA EDUS331608C D 18 3 RXTQ60TAVJUA 2P435104 1A...

Page 60: ...58 RXTQ TAVJ9A TAVJUA EDUS331608C D 2P435104 1A...

Page 61: ...59 RXTQ TAVJ9A TAVJUA EDUS331608C D 2P435104 1A...

Page 62: ...60 RXTQ TAVJ9A TAVJUA EDUS331608C D 2P435104 1A...

Page 63: ...of refrigerant gas is not exceeded in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum ch...

Page 64: ...ility is divided into 2 entirely independent refrigerant systems then use the amount of refrigerant with which each separate system is charged Step 2 Calculate the smallest room volume ft 3 In case li...

Page 65: ...ed If the result of the above calculation exceeds the maximum concentration level then make similar calculations for the second then third smallest room and so until the result falls short of the maxi...

Page 66: ...t board fuse 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A Fan motor thermal fuse F C Fan motor thermal protector F C Drain pump fuse F C C 4D110603 20 3 FXUQ P Model F...

Page 67: ...rd fuse Fan driver 250 V 6 3 A 250 V 6 3 A 250 V 6 3 A 250 V 6 3 A 250 V 6 3 A 250 V 6 3 A Drain pump thermal fuse F C 3D112398 20 7 FXMQ PB Model FXMQ07PBVJU FXMQ09PBVJU FXMQ12PBVJU FXMQ15PBVJU FXMQ1...

Page 68: ...20 or less OFF 275 18 135 10 ON 248 120 or less C 3D045646B 20 11 FXTQ TA Model FXTQ09TAVJUA FXTQ12TAVJUA FXTQ18TAVJUA FXTQ24TAVJUA FXTQ30TAVJUA Model with factory disconnect FXTQ09TAVJUD FXTQ12TAVJUD...

Page 69: ...67 RXTQ TAVJ9A TAVJUA EDUS331608C D Appendix 1 Introduction 68 1 1 ED Book List 68 1 2 Publication List of Engineering Data for VRV Products 69...

Page 70: ...P EDUS391437 F15 One Way Blow Cassette Type FXEQ P EDUS391533 F16 Slim Ceiling Mounted Duct Type FXDQ M EDUS39 600 F2 MSP Concealed Duct Unit FXSQ TA EDUS391777 F17 Ceiling Mounted Duct Type FXMQ PB...

Page 71: ...1706C C H P 208 230 V 460 V RXYQ TATJA TAYDA USA Canada Design manual EDUS341703B D Jan 2020 Capacity table EDUS341703B C 575 V RXYQ TAYCA Canada Design manual EDUS341824A D Capacity table EDUS341824A...

Page 72: ...Type FXAQ07 24PVJU USA EDUS391100 F6 Jan 2012 Floor Standing Type Concealed Floor Standing Type FXLQ07 24MVJU FXNQ07 24MVJU USA EDUS391502 F7 Jul 2015 Air Handling Unit FXTQ09 60TAVJUA FXTQ09 60TAVJUD...

Page 73: ......

Page 74: ......

Page 75: ......

Page 76: ...r explosion Use only those parts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessorie...

Reviews: