3
|
Troubleshooting
Service manual
19
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
Possible cause:
Faulty indoor unit heat exchanger thermistor.
5
Perform a check of the indoor unit main PCB. See
97].
Possible cause:
Faulty indoor unit main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.5.3 A6-00 – Indoor unit fan motor abnormality
Trigger
Effect
Reset
The rotation speed of the
fan motor is NOT
detected while the output
voltage to the fan is at its
maximum.
Unit will stop operating.
Power reset via the
outdoor unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the indoor unit main PCB. See
97].
Possible cause:
Faulty indoor unit main PCB.
2
Perform a check of the indoor unit fan motor. See
Possible cause:
Faulty indoor unit fan motor.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.5.4 AH-00 – Streamer unit abnormality
Trigger
Effect
Reset
Streamer unit starts
electric discharge when
operation starts after
approximately 90 to
180 seconds.
Unit will NOT stop
operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the streamer unit. See
167].
Possible cause:
Faulty streamer unit.
Summary of Contents for RXTA30B2V1B